ENGLISH
38
7.2.7 Pt 100 Thermometer (5100536 and 5100636) - continued
Code
(EDM)
P1C
P1F
P2F
Range
-100.0 to 199.9°C
-148.0 to 199.9°F
-148.0 to 392°F
DP
111.1
1111
HiE
199.9
93.2
1999
LoE
-100.0
-100
Hi
199.9
392
Lo
-100.0
-148.0
-148
Scaling Values
P1C is the default
range set from factory.
7.2.8 Pt 100 850°C Thermometer (5100539 and 5100639)
Code
(EDM)
P2C
P3F
Sensor
type
RTD Pt 100
∝
= 0.00385
Range
-100 to 850°C
-148 to 1562°F
Resolution
1°C
2°F
Accuracy
0.2% of rdg
±3 dgt
0.4% of rdg
±6 dgt
Temperature
drift
±150 ppm/°C
±0.05 count/°C
±180 ppm/°F
±0.1 count/°F
Specifications
Code
(EDM)
P2C
P3F
Range
-100 to 850°C
-148 to 1562°F
DP
1111
HiE
1999
LoE
-235
Hi
850
1562
Lo
-100
-148
Scaling Values
P2C is the default
range set from factory.
7.2.9 Thermocouple Type J Thermometer (5100537 and 5100637)
Code
(EDM)
-JC
-JF
Sensor
type
Thermocouple
Type J
Range
-100 to 760°C
-148 to 1400°F
Resolution
1°C
2°F
Accuracy
0.1% of rdg
±4 dgt
0.1% of rdg
±8 dgt
Temperature
drift
±100 ppm/°C
±0.05 count/°C
±180 ppm/°F
±0.1 count/°F
Specifications
Code
(EDM)
-JC
-JF
Range
-100 to 760°C
-148 to 1400°F
DP
1111
HiE
1999
LoE
-264
Hi
760
1400
Lo
-100
-148
Scaling Values
-JC is the default
range set from factory.