ENGLISH
25
2. To select a new relay status, press to select the normally
energized status (the display will show ) or press to
select the normally de-energized status (the display will
show ).
Press to accept and pass on to the next selection.
4.3.5.6 Relay Status in Overflow Condition
You can choose how the relay shall react in overflow conditions as well,
namely whether the relay has to be ON or OFF.
1. The display will show for relay ON in overflow conditions or it
will show for relay OFF in overflow conditions.
Press to keep the current value and pass on.
2. If you will change the status, press to select relay ON (the
display will show ) or press to select relay OFF (the
display will show ). Press to terminate setpoint 1
programming.
All parameters are now programmed (with a 1 relay output module in-
stalled) and the programming mode is terminated automatically. This
will be shown in the display with . The system restarts and is back
in run-mode.
4.3.5.7 Setpoint 2
If a 2 relay output module is installed the display will show after
the termination of 4.3.5.6 Relay Status in Overflow Condition.
To select the parameters for setpoint 2, proceed as explained for set-
point 1.
After programming all parameters for setpoint 2, the programming
mode is terminated automatically and shown in the display as .
The system restarts and is back in run-mode.
▲
▼