- General parameters  (“H”)

H1: Unit model
It allows to select the type of unit to be controlled:

Value

Unit

0

AIR/AIR unit (only cooling)

1

AIR/AIR heat pump

2

AIR/WATER chiller

3

AIR/WATER heat pump

4

WATER/WATER chiller

5

WATER/WATER heat pump with gas reversibility

6

WATER/WATER heat pump with water reversibility

7

Motorcondensing unit

8

Motorcondensing unit with cycle inversion

9

Water-based motorcondensing

10

Water-based motorcondensing with cycle inversion

H5: Operating logic of the Pump/Inlet fan

It sets the operating logic of the water circulation pump
or of the inlet fan (in Air/Air units). The pump can be 
disabled (H5=0), always ON (H5=1) or ON upon a call 
from the compressor (H5=2) in this case the pump/inlet 
fan will be the first device to start, followed by the 
compressor. With disabled pump the flowswitch alarm 
will not be present although the Pump Relay will be 
normally activated. When H5=3 burst mode is active 
(see page 16 parameters cd and cE); this allows the 
pump to be kept on for a set time even when the 
compressor is off.

N.B.: with H1=0.1 air units, if you use heating resistance
you must select H5=1.

H6: Cooling/heating digital input with P8/P9 = 8, 9

This parameter enables the cooling/heating selection 
from digital input if the parameters P8 or P9 = 8 or 9.

H7: ON/OFF digital input

This parameter enables the ON/OFF selection from 
digital input. If the selection is enabled (H7=1) the 
“open” state forces the machine to stop, whereas with 
the “closed” state the machine can be started or 
stopped also from the keyboard.

H8: Number of terminals

It indicates the No. of terminals connected to the unit 
H8=0 without remote control
H8=1 with remote control

H9: Lock of direct parameters modification

This parameter allows to disable the procedure through
which can modify DIRECT and USER parameters 
through keyboard or through remote control. In this 
way you will be able to display the parameter but not 
to modify them. The following functions will also be 
disabled: Cooling/Heating selection and timers reset.

Value

Remote control 

Keyboard

0

enabled

disabled

1 (default)

enabled

enabled

2

disabled

disabled

3

disabled

enabled

HA: Serial address

It indicates the address of the instrument used to carry
out serial connection by means of the card to a 
supervisory and/or telemaintenance computer.

- Parametri generali (“H”)

H1: Modello di macchina
Permette di selezionare il tipo di macchina da controllare:

Valore Macchina
0

Unità ARIA/ARIA

1

Pompa di calore ARIA/ARIA

2

Chiller ARIA/ACQUA

3

Pompa di calore ARIA/ACQUA

4

Chiller ACQUA/ACQUA

5

Pompa di calore ACQUA/ACQUA a rever. del gas

6

Pompa di calore ACQUA/ACQUA a rever. dell'acqua

7

Unità motocondensante

8

Unità motocondensante con inversione di ciclo

9

Motocondensante ad acqua

10

Motocondensante ad acqua con inversione di ciclo

H5: Modalità pompa/Ventilatore di mandata

Stabilisce la modalità di funzionamento della pompa di
circolazione dell'acqua o del ventilatore di mandata 
(nelle unità Aria/Aria). La pompa può essere disabilitata 
(H5=0), sempre accesa (H5=1) o accesa su chiamata 
del compressore (H5=2) alla richiesta di caldo o freddo
parte prima la pompa/ventilatore mandata e poi il 
compressore. Con pompa disabilitata non viene gestito
l'allarme flussostato. Con H5=3 si attiva la modalità 
burst (vedi pag. 16 param. cd e cE) che consente di 
tenere attiva la pompa a tempo anche con compressore
spento.

N.B.: con macchine ad aria H1=0,1 se si utilizzano 
resistenze per il riscaldamento si deve selezionare H5=1.

H6: Ingresso digitale estate/inverno con P8/P9 = 8, 9 

Stabilisce se la selezione estate/inverno da ingresso 
digitale è abilitata o meno con P8 o P9 selezionati 8 o 9.

H7: Ingresso digitale ON/OFF

Stabilisce se la selezione ON/OFF da ingresso digitale è
abilitata o meno. Se la selezione è abilitata (H7=1) lo 
stato “aperto” forza la macchina a spegnersi mentre 
con lo stato “chiuso” la macchina può essere spenta o 
accesa anche da tastiera.

H8: Numero di terminali

Stabilisce il numero di terminali collegati alla macchina
H8=0 senza terminale remoto
H8=1 con terminale remoto collegato

H9: Blocca modifica parametri diretti 

Permette di disabilitare la modifica dei parametri 
DIRECT e USER da tastiera e da telecomando.
Consente comunque la visualizzazione del valore dei 
parametri. Vengono disabilitate anche le funzioni 
abilitazione/disabilitazione Estate, abilitazione/
disabilitazione Inverno e reset contatori.

Valore

Telecomando

Tastiera

0

abilitato

disabilitata

1 (default)

abilitato

abilitata

2

disabilitato

disabilitata

3

disabilitato

abilitata

HA: Indirizzo seriale

Stabilisce l'indirizzo dello strumento per il collegamento
seriale, tramite scheda opzionale, ad un computer di 
supervisione e/o teleassistenza.

24

Summary of Contents for mchiller compact

Page 1: ...chiller compact Manuale d uso User guide...

Page 2: ......

Page 3: ...ratteristiche tecniche del chiller compact 45 11 Aggiornamenti software 49 11 1 Note per la versione 1 2 49 11 2 Note per la versione 1 3 49 11 3 Note per la versione 1 4 49 11 4 Note per la versione...

Page 4: ......

Page 5: ...sul display Significato dei LED a display 1 Introduction Compact chiller is a versatile electronic controller as compact as a standard thermostat specifically designed for the control of chillers and...

Page 6: ...L per pi di 5 secondi consente di accedere al men di predisposizione dei parametri FACTORY ovvero dei parametri di configurazione della macchina Tale livello protetto da un codice password differente...

Page 7: ...di funzionamento della macchina era inverno la pressione non ha alcun effetto Setting the password 0 on the display Pressing the and buttons will allow you to stop the blinking effect for a few secon...

Page 8: ...li parametri DIRECT e USER in fun zione dei valori dei parametri FACTORY Al termine dell impostazione viene visualizzata la scritta dF Enabling disabling of HEATING operating mode The Heating operatin...

Page 9: ...llarmi Visualizzazione contaore azzeramento immediato del contaore PRG All accensione scrittura parametri di default PRG All accensione copia chiave su eeprom macchina PRG All accensione copia eeprom...

Page 10: ...resent 1 NTC Carel 2 pressione 4 20mA 2 pressure 4 20mA 4 Valore pressione a 4mA F 0 5 bar 0 1 0 P Min value current input 5 Valore pressione a 20mA F 4 40 bar 0 1 30 P Max value current input 6 Calib...

Page 11: ...cE Tempo minimo accensione pompa U 1 15 min 1 3 Minimum pump on time VENTOLE Tipo Min Max U M Variazione Default Pres DVNP Nuovo FANS Type Min Max M U Variation Default Presence New F1 Uscita ventila...

Page 12: ...iazione Default Pres DVNP Nuovo DEFROSTING Type Min Max M U Variation Default Presence New d1 Esecuzione sbrinamento U 0 1 flag 1 1 NP Antigelo condensazione Defrosting cycle Condensation antifreeze 0...

Page 13: ...150 sec 1 20 Flowmeter down delayed when starting the pump P2 Ritardo allarme di flusso a regime U 0 90 sec 1 5 Flowswitch alarm delayed during normal operating P3 Ritardo allarme B P da accensione c...

Page 14: ...ator requires it 3 accesa su richiesta del regolatore e a tempo 3 start upon request of the controller and by time H6 Ingresso digitale estate inverno con U 0 1 flag 1 0 P8 e P9 selezionati a 8 9 Cool...

Page 15: ...r effettua automaticamente la conversione dei valori letti dalle sonde di temperatura NTC B1 B2 B3 nella nuova unit di misura mentre tutti gli altri parametri impostati set point differenziale ecc rim...

Page 16: ...tte di impostare il differenziale per la regolazione Inverno r5 Rotazione compressori La rotazione dei compressori permette di ripartire equamente i tempi di funzionamento La logica di attivazione di...

Page 17: ...ecreases as the outside temperature increases The deviation of the set point from the set value can reach an absolute maximum equal to parameter rF The values of the parameters described in the graph...

Page 18: ...ven if there is a request for its turning on During this phase the LED relative to the compressor blinks c3 Time interval between two successive ON routines It sets the minimum off time interval betwe...

Page 19: ...zione di richiesta di manutenzione Il valore 0 disabilita la funzione c6 Delay at start up This parameter allows to set a time delay at the compressor start up so as to balance current absorption and...

Page 20: ...eset the timer cd Minimum time between two pump starts The following is a diagram showing an example of operation with pump and burst active when H5 3 The dashed areas on the compressor diagram indica...

Page 21: ...tension threshold for Triac With fans speed regulation phase cut optional cards MCHRTF equipped with Triac are required In this case it is necessary to specify the tension delivered by the Triac to th...

Page 22: ...esterno evaporatore in modalit Inverno In caso di unit pompa calore acqua acqua a reversibilit del gas H1 5 consente di effettuare il controllo antigelo del l acqua di raffreddamento dello scambiatore...

Page 23: ...Timed or temperature based defrosting It sets a timed defrosting fixed time interval or a temperature based cycle defrosting will stop as soon as the condensation probe reaches the end defrosting tem...

Page 24: ...ra per gli Aria Aria consente una sua accensione per il tempo selezionato solamente in modalit Inverno in quanto la macchina va a riscaldare l acqua aria Se dopo questo tempo l allarme permane la macc...

Page 25: ...nze di appoggio vedi A8 A4 Set point for the activation of antifreeze supporting heaters Indicates the threshold below which the antifreeze heater will be activated also when the unit is in standby In...

Page 26: ...te avoiding any unstable signal from the sensor This delay will be applied also to the 4 way reversing valve in the gas circuit P4 Buzzer It indicates how long the buzzer will sound in the event of an...

Page 27: ...tale allarme inibito dal tempo PC PC Ritardo allarme alta temperatura all accensione Ritardo allarme alta temperatura sia all accensione del controllo power ON che da ON OFF remoto o da tastiera P5 R...

Page 28: ...by means of the card to a supervisory and or telemaintenance computer Parametri generali H H1 Modello di macchina Permette di selezionare il tipo di macchina da controllare Valore Macchina 0 Unit ARIA...

Page 29: ...2 utilizzata per la resistenza HH 1 viene utilizzata per il secondo compressore questo permette di configurare la macchina in pompa di calore con compressori tandem Hb Remote control unit password Thi...

Page 30: ...nger the alarm code disappears from the LCD If the alarm condition persists the actions described above will be performed again 4 1 Alarm table 4 2 Alarms H1 High pressure The alarm condition is detec...

Page 31: ...pressore dei ventilatori di condensazione e della pompa ventilatore di mandata negli ARIA ARIA vengono attivati il cicalino il rel di allarme ed il lampeggio del display E4 Sonda di compensazione guas...

Page 32: ...ribadisce inoltre che a macchina gi in stand by non viene rilevato nessun allar me che non sia di sistema ovvero solo gli allarmi di siste ma vengono gestiti quelli da ingresso digitali no EU EO Error...

Page 33: ...cazione da telecomando punto 1 si pu effettuare la scansione di tutti parametri utilizzando i tasti freccia e la modifica tramite il tasto SEL 5 Accessories 5 1 Infrared remote control unit The unit c...

Page 34: ...HSMLSER0 serial converter for chiller compact The electronic MCHSMLSER0 allows you to interface the chiller compact to a supervisory network in RS485 standard asynchronous and at the MCHTER00C0 remote...

Page 35: ...tion Interfacce dati TTL optoisolata per collegamento al chiller compact lunghezza massima del collegamento 90 cm tramite cavetto multipolare in dotazione optoinsulated TTL for the chiller compact con...

Page 36: ...t 180 mA Fusibile esterno obbligatorio 315 mA External fuse obligatory Condizioni di immagaz Storage conditions 10T70 10 70 C U R rH 90 non condensante not condensing Condizioni di funzion Operating c...

Page 37: ...0A 250Vac AC1 inductive load 1 3 HP 33 x100h SEL PRG mute clear MCHTER00 R C 0 Caratteristiche tecniche MCHTER00 R C 0 Technical characteristics Tensione di alimentazione dalla scheda di remotazione M...

Page 38: ...ollegabili al chiller compact senza l utilizzo di questo modulo 5 6 Card for fan speed control cod MCHRTF The cards with phase cutting signal coded MCHRTF allow the control of the rotation speed of co...

Page 39: ...ncrementando F4 la tensione non diminuir pi evitare di aumentare ulteriormente F4 onde evitare danni al motore F2 3 A questo punto l operazione conclusa 5 8 How to find minimum and maximum speed of th...

Page 40: ...uChiller 5VDC Power supply voltage supplied by the uChiller 5VDC Sonde di temperatura utilizzabili sensore NTC CAREL 50 C 90 C Temperature probes that can be used sensor NTC CAREL 50 C 90 C Errori di...

Page 41: ...te Ambient probe Termico fan Fan overload Termico fan mandata Inlet fan overload Ventilatore di mandata Inlet fan Sonda condensatore Condenser probe Ventilatore Fan Resistenze di riscaldamento Antifre...

Page 42: ...oratore Input evaporator Uscita evaporatore Output evaporator Pompa dell acqua Resistenza antigelo Antifreeze heating Bassa press Low pressure Evaporatore Evaporator Alta pressione High pressure Bassa...

Page 43: ...erload Flussostato Flow detector Ingresso evaporatore Input evaporator Uscita evaporatore Output evaporator Resistenza antigelo Antifeeze heater Valvola inversione Reversing valve Condensatore Condens...

Page 44: ...sore Compressor Termico comp Comp overload Termico fan Fan overload Ventilatore Fan Sonda condensatore Condenser probe Valvola inversione Reversing valve Alta pressione High pressure Bassa pressione L...

Page 45: ...B3 GND Sonda controllo condensazione Condensation control probe ID1 GND Ingresso multifunzione flussostato termico estate inverno fine sbrinamento Multifunction Input flow detector overload cooling h...

Page 46: ...tare diversi dispositivi quali contattori elettrovalvole ecc i quali necessiteranno di un altro trasformatore Attenzione il non corretto allacciamento della tensione di alimentazione pu danneggiare se...

Page 47: ...nsions Here below are indicated the mechanical dimensions of each component in chiller all the values are expressed in millimeters Note the dimensions include the inserted plug in connectors Remote te...

Page 48: ...of 20 pieces cod MCHTER00CM Chiave hardware di program per chiller compact Hardware programming key for chiller compact cod MCHSMLKEY0 Modulo convertitore per sonda di pressione 4 20mA cod MCHSML4200...

Page 49: ...i i rel del gruppo A devono avere comuni collegamenti come indicato nello schema Ingressi digitali Standard elettrico contatto pulito Corrente di chiusura riferita a massa 4 5 mA Massima resistenza pe...

Page 50: ...a di resistenza al calore e al fuoco D PTI dei materiali di isolamento tutti i materiali di isolamento hanno PTI 250 V Classe e struttura del software A Caratteristiche di invecchiamento ore di funzio...

Page 51: ...relays of the Group A must have the same connections as indicated on the diagram Digital inputs Electric standard clean contact Make current referred to ground 4 5 mA Make maximum resistance 50 Analog...

Page 52: ...zzer ir open air 10 C 50 C Environmental pollution normal Category of fire and heating resistance D PTI of the insulation materials all the insulation materials have PTI 250 v Software class and struc...

Page 53: ...e copied to the previous version chiller compact release 1 3 11 Aggiornamenti software 11 1 Note per la versione 1 2 La release software 1 2 rispetto alla precedente 1 1 pre senta le seguenti variazio...

Page 54: ...gramma nella precedente versione di uChiller compact release 1 4 11 4 Notes for version 2 0 Software release 2 0 features the following variations from the previous release 1 4 New parameters Fd Fan O...

Page 55: ......

Page 56: ...Cod 030221870 rel 2 0 13 02 02 Agenzia Agency CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com...

Reviews: