![Carel EVD Evolution Twin User Manual Download Page 59](http://html1.mh-extra.com/html/carel/evd-evolution-twin/evd-evolution-twin_user-manual_2557374059.webp)
ENG
“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
59
Fig. 12.f
Note:
the program On-line help can be accessed by pressing F1.
12.3 Copying the setup
On the Configure device page, once the new project has been created, to
transfer the list of configuration parameters to another controller:
•
read the list of parameters from the source controller with the “Read”
command;
•
remove the connector from the service serial port;
•
connect the connector to the service port on the destination controller;
•
write the list of parameters to the destination controller with the “Write”
command.
Important:
the parameters can only be copied between controllers
with the same code. Different firmware versions may cause compatibility
problems.
12.4 Setting the default parameters
When the program opens:
•
select the model from the range and load the associated list of parameters;
•
go to “Configure device”: the list of parameters will be shown, with the
default settings.
•
connect the connector to the service serial port on the destination
controller;
•
select “Write”. During the write procedure, the LEDs on the converter will
flash.
The controller parameters will now have the default settings.
12.5 Updating the controller and display
firmware
The controller and display firmware must be updated using the VPM program
on a computer and the USB/tLAN converter, which is connected to the device
being programmed (see paragraph 2.7 for the connection diagram). The
firmware can be downloaded from http://ksa.carel.com. See the VPM On-line
help.