![Carel EVD Evolution Twin User Manual Download Page 41](http://html1.mh-extra.com/html/carel/evd-evolution-twin/evd-evolution-twin_user-manual_2557374041.webp)
ENG
“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
41
user *
Parameter/description
Def.
Min.
Max.
UOM
T
ype **
CAREL SVP
M
odbus®
Note
C
CUSTOMIZED REFRIGERANT
Dew a high
-288
-32768
32767
-
I
107 234
Dew a low
-15818
-32768
32767
-
I
108 235
Dew b high
-14829
-32768
32767
-
I
109 236
Dew b low
16804
-32768
32767
-
I
110 237
Dew c high
-11664
-32768
32767
-
I
111 238
Dew c low
16416
-32768
32767
-
I
112 239
Dew d high
-23322
-32768
32767
-
I
113 240
Dew d low
-16959
-32768
32767
-
I
114 241
Dew e high
-16378
-32768
32767
-
I
115 242
Dew e low
15910
-32768
32767
-
I
116 243
Dew f high
-2927
-32768
32767
-
I
117 244
Dew f low
-17239
-32768
32767
-
I
118 245
Bubble a high
-433
-32768
32767
-
I
119 246
Bubble a low
-15815
-32768
32767
-
I
120 247
Bubble b high
-15615
-32768
32767
-
I
121 248
Bubble b low
16805
-32768
32767
-
I
122 249
Bubble c high
30803
-32768
32767
-
I
123 250
Bubble c low
16416
-32768
32767
-
I
124 251
Bubble d high
-21587
-32768
32767
-
I
125 252
Bubble d low
-16995
-32768
32767
-
I
126 253
Bubble e high
-24698
-32768
32767
-
I
127 254
Bubble e low
15900
-32768
32767
-
I
128 255
Bubble f high
10057
-32768
32767
-
I
129 256
Bubble f low
-17253
-32768
32767
-
I
130 257
C
Faulty closure alarm status
0/1=no/yes
0
0
1
-
D
49
48
C
Battery charge delay
0
0
250
min
I
135 262
CO
ALARM CONFIGURATION
C
Low superheat alarm delay (LowSH)
(0= alarm disabled)
300
0
18000
s
I
43
170
-
C
Low evaporation temperature alarm delay (LOP)
(0= alarm disabled)
300
0
18000
s
I
41
168
-
C
High evaporation temperature alarm delay (MOP)
(0= alarm disabled)
600
0
18000
s
I
42
169
-
C
High condensing temperature alarm delay (HiTcond)
SELECT WITH PROG. CONT.
600
0
18000
s
I
44
171
CO
C
Low suction temperature alarm threshold
-50
-85 (-121)
200 (392)
°C (°F)
A
26
25
-
C
Low suction temperature alarm delay
(0= alarm disabled)
300
0
18000
s
I
9
136
-
VALVE
C
EEV minimum steps
50
0
9999
step
I
30
157
-
C
EEV maximum steps
480
0
9999
step
I
31
158
-
C
EEV closing steps
500
0
9999
step
I
36
163
-
C
EEV rated speed
50
1
2000
step/s
I
32
159
-
C
EEV rated current
450
0
800
mA
I
33
160
-
C
EEV holding current
100
0
250
mA
I
35
162
-
C
EEV duty cycle
30
1
100
%
I
34
161
-
C
Synchronise position in opening
1
0
1
-
D
20
19
-
C
Synchronise position in closing
1
0
1
-
D
21
20
-
Tab. 8.a
* User level: A= Service (installer), C= manufacturer.