“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
45
user *
Parameter/description
Def.
Min.
Max.
UOM
T
ype **
CAREL SVP
M
odbus®
Note
A
DI1 configuration
1= Disabled
2= Valve regulation optimization after defrost
3= Discharged battery alarm management
4= Valve forced open (at 100%)
5= Regulation start/stop
6= Regulation backup
7= Regulation security
Regulation
start/stop
(tLAN-RS485)
/ Regulation
backup
(pLAN)
-
-
-
I
85
212
CO
C
Language: Italiano; English
Italiano
-
-
-
-
-
-
CO
C
Auxiliary refrigerant
-1= User defined; 0 = same as main regulation
1= R22
2= R134a
3= R404A 4= R407C
5= R410A
6= R507A
7= R290 8= R600
9= R600a
10= R717
11= R744
12= R728
13= R1270
14= R417A
15= R422D
16= R413A
17= R422A 18= R423A 19= R407A 20= R427A
21= R245FA 22= R407F
23=R32 24=HTR01
25=
HTR02
26=R23
27 = R1234yf 28 = R1234ze 29 = R455A
30 = R170
31 = R442A 32 = R447A
33 = R448A
34 = R449A
35 = R450A
36 = R452A 37 = R508B
38 = R452B
39 = R513A
40 = R454B
41 = R458A
R404A
-
-
-
I
96
223
CO
PROBES
C
S1: calibration offset
0
-60(-870), -60
60(870), 60
barg (psig)
mA
A
34
33
CO
C
S1: calibration gain, 4 to 20 mA
1
-20
20
-
A
36
35
CO
C
Pressure S1: MINIMUM value
-1
-20 (-290)
Pressure S1:
MAXIMUM
value
barg (psig)
A
32
31
CO
C
Pressure S1: MAXIMUM value
9.3
Pressure S1:
MINIMUM
value
200 (2900)
barg (psig)
A
30
29
CO
C
Pressure S1: MINIMUM alarm value
-1
-20 (-290)
Pressure S1:
MAXIMUM
alarm value
barg (psig)
A
39
38
CO
C
Pressure S1: MAXIMUM alarm value
9.3
Pressure S1:
MINIMUM
alarm value
200 (2900)
barg (psig)
A
37
36
CO
C
S2: calibration offset
0
-20 (-36), -20
20 (36), 20
°C (°F), volt
A
41
40
CO
C
S2: calibration gain, 0 to 10 V
1
-20
20
-
A
43
42
CO
C
Temperature S2: MINIMUM alarm value
-50
-85(-121)
Temperature
S2: MAXIMUM
alarm value
°C (°F)
A
46
45
CO
C
Temperature S2: MAXIMUM alarm value
105
Temperature
S2: MINIMUM
alarm value
200 (392)
°C (°F)
A
44
43
CO
C
S3: calibration offset
0
-60 (-870)
60 (870)
barg (psig)
A
35
34
CO
C
S3: calibration gain, 4 to 20 mA
1
-20
20
-
A
82
81
CO
C
Pressure S3 : MINIMUM value
-1
-20 (-290)
Pressure S3:
MAXIMUM
value
barg (psig)
A
33
32
CO
C
Pressure S3: MAXIMUM value
9.3
Pressure S3:
MINIMUM
value
200 (2900)
barg (psig)
A
31
30
CO
C
Pressure S3: MINIMUM alarm value
-1
-20 (-290)
Pressure S3:
MAXIMUM
alarm value
barg (psig)
A
40
39
CO
C
Pressure S3: MAXIMUM alarm value
9.3
Pressure S3:
MINIMUM
alarm value
200 (2900)
barg (psig)
A
38
37
CO
C
S4: calibration offset
0
-20 (-36)
20 (36)
°C (°F)
A
42
41
CO
C
Temperature S4: MINIMUM alarm value
-50
-85(-121)
Temperature
S4: MAXIMUM
alarm value
°C (°F)
A
47
46
CO
C
Temperature S4: MAXIMUM alarm value
105
Temperature
S4: MINIMUM
alarm value
200 (392)
°C (°F)
A
45
44
CO
C
S1/S3 Maximum difference (pressure)
0
0
200(2900)
bar(psig)
A
114 113
CO
C
S2/S4 Maximum difference (temperature)
0
0
180(324)
°C (°F)
A
115 114
CO
C
Alarm delay S1
0
0
240
s
I
131 258
CO
C
Alarm delay S2
0
0
240
s
I
132 259
CO
C
Alarm delay S3
0
0
240
s
I
133 260
CO
C
Alarm delay S4
0
0
240
s
I
134 261
CO
C
Enable S1
0
0
1
-
D
16
15
CO
C
Enable S2
0
0
1
-
D
17
16
CO
C
Enable S3
0
0
1
-
D
18
17
CO
C
Enable S4
0
0
1
-
D
19
18
CO