46
ENG
ir0300028EN rel. 1.1 - 05.05.2017
9. TECHNICAL
SPECIFICATIONS
9.1 ir33+ technical specifi cations
Power supply
Model
Voltage
Power
IREVxxExxxx
230 V~, 50/60 Hz
3 VA, 25mA ~ max
IREVxxAxxxx
115 V~, 50/60 Hz
3 VA, 50mA ~ max
IREVxxHxxxx
115/230 V~, 50/60 Hz
6 VA, 50mA ~ max
IREVxxLxxxx
12 to 24 V ~, 50/60 Hz, 12/30 Vdc
3 VA, 300 mA ~/ mAdc max
IREVxx0xxxx
12 V ~, 50/60 Hz, 12/18 Vdc
Only use SELV power supply
Insulation guaranteed
by the power supply
IREVxxExxxx
IREVxxAxxxx
insulation from extra low voltage parts
reinforced, 6 mm clearance, 8 mm creepage, 3750V insulation
IREVxxHxxxx
insulation from relay outputs
basic, 3 mm clearance, 4 mm creepage, 1250V insulation
IREVxxLxxxx
insulation from extra low voltage parts
to be guaranteed externally by safety transformer (SELV)
IREVxx0xxxx
insulation from relay outputs
reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation
Inputs
S1 (probe 1)
NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)
S2 (probe 2)
NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)
DI1
voltage-free contact, contact resistance < 10
, closing current 6 mA
S3
NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)
DI2
voltage-free contact, contact resistance < 10
, closing current 6 mA
S4
NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)
Maximum distance between probes and digital inputs less than 10 m
Note:
in the installation it is recommended to separate the power and load connections from the probe, digital input, display and supervi-
sor cables.
Probe type
Std. Carel NTC
10k
at 25°C, range from –50T90°C
measurement error:
1°C in the range –50T50°C
3°C in the range +50T90°C
High temperature
NTC
50k
at 25°C, range –40T150°C
measurement error:
1.5°C in the range –20T115°C
4°C in the range outside of -20T115°C
Standard Carel PTC
985
at 25°C, range from -50T150°C
measurement error
2°C in the range from –50T50°C4°C in the range from +50T150°C
Relay
outputs
depending on the model
EN60730-1
UL 873
model
relay
250 V~
operating cycles 250 V~
operating cycles
IRxxxx(E,A)(P,Q,S,U,V,X,Y,Z)xxx
R2(*)
5 (1) A
100000
5 A res 1 FLA
6 LRA C300
30000
IRxxxx(E,A)(N, R, C, B,A,M,L, T)xxx
R3(*)
5 (1) A
100000
5 A res 1 FLA
6 LRA C300
30000
IRxxxx(E,A)(N, R, C, B, A, M, L, T)xxx
R1, R2
8 (4)A N.O. 6(4) A N.C. 100000
8 A res 2 FLA
30000
IRxxxx(0, L, H)(N, R, C, B, A, M, L, T)xxx
R2, R3, R4 (*)
2(2) A N.O./N.C.
12 LRA C300
IRxxxx(E,A)(P, Q, S, U, V, X, Y, Z)xxx
R1
12 (2)A N.O./ N.C.
100000
12 A res 5 FLA
30000
IRxxxx(0, L, H)(N, R, C, B, A, M, L, T)xxx
R1
12 (2)A N.O./ N.C.
100000
30 LRA C300
insulation from extra low voltage parts
reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation
insulation between independent relay outputs
basic, 3 mm clearance, 4 mm creepage, 1250 V insulation
SSR outputs Max output voltage 12 Vdc
Output resistance 600
Max output current 20 mA
Connections Cable cross-section from 0.5 to 2.5 mm2 max current 12 A
(*): Relay not suitable for fl uorescent loads (neon lights, etc.) that use starters (ballasts) with phase shifting capacitors. Fluorescent lamps with electronic controllers
or without phase shifting capacitors can be used, depending on the operating limits specifi ed for each type of relay.
The correct sizing of the power and connection cables between the instrument and the loads is the installer’s responsibility. Depending on the model, the maxi-
mum current at common terminals 1, 3 or 5 is 12 A. If using the controller at maximum operating temperature and at full load, the cables used must be suitable for
operation at least up to 105 °C.
Clock
error at 25° C ±10 ppm (±5 min/year)
error at 25° C -10T60 °C -50 ppm (27 min/year)
Operating temperature
-10T60 °C for all versions
Operating humidity
< 90% RH non-condensing
Front panel ingress protection
assembly on smooth and indeformable panel with IP65 gasket
Environmental pollution
2 (normal situation)
PTI of insulating materials
printed circuits 250, plastic and insulating materials 175
Period of stress across the insulating parts
long
Heat and fi re resistance category
category D and category B (UL 94-V0)
Class of protection against voltage surge
category II
Type of action and disconnection
1.B relay contacts (microswitching)
Construction of the control device
built-in, electronic
Classifi cation according to protection against electric shock
class II when appropriately integrated
Maximum distance between interface and display
10 m
Programming key
available on all models
Safety standards
compliant with relevant European standards
Tab. 9.a