40
ENG
ir0300028EN rel. 1.1 - 05.05.2017
User
Par.
Description
Models
Def
Min Max UOM
Type CAREL SVP
ModBus®
R/W
rtc
C
td1…8 Defrost 1 to 8 (press Set)
SYFCH
-
-
-
-
-
-
R/W
d__
Defrost 1 to 8 - day
0
0
11
day
I
106/109/…/127 206/209/…/227 R/W
h__
Defrost 1 to 8 - hour
0
0
23
hour
I
107/110/…128
207/210/…/228 R/W
n__
Defrost 1 to 8 - minute
0
0
59
min
I
108/111/…129
208/211/…/229 R/W
C
ton
Light/aux on time
SYFCH
-
-
-
-
-
-
R/W
d__
Day
0
1
7
day
I
130
230
R/W
h__
Hour
0
0
23
hour
I
131
231
R/W
n__
Minute
0
0
59
minute I
132
232
R/W
C
toF
Light/aux off time
SYFCH
-
-
-
-
-
-
-
R/W
d__
Day
0
1
7
day
I
133
233
R/W
h__
Hour
0
0
23
hour
I
134
234
R/W
n__
Minute
0
0
59
minute I
135
235
R/W
C
tc
Date/time (press Set)
MSYFCH
-
-
-
-
R/W
y__
Date/time: year
12
0
99
year
I
1
101
R/W
m__
Date/time: month
8
1
12
month I
2
102
R/W
d__
Date/time: day of the month
1
1
31
day
I
3
103
R/W
u__
Day of the week
1
1
7
day
I
4
104
R/W
h__
Date/time: hour
0
0
23
hour
I
5
105
R/W
n__
Date/time: minute
0
0
59
minute I
6
106
R/W
7.14 Variables only accessible via serial
connection
Description
Type
CAREL SVP
Modbus
R/W
Virtual probe
A
3
3
R
Probe 1 reading
A
4
4
R
Probe 2 reading
A
5
5
R
Probe 3 reading
A
6
6
R
Probe 4 reading
A
7
7
R
Number of parameter sets available
I
137
237
R
Digital input 1 status
D
6
6
R
Digital input 2 status
D
7
7
R
Virtual probe fault alarm
D
9
9
R
Probe alarm 1
D
10
10
R
Probe alarm 2
D
11
11
R
Probe alarm 3
D
12
12
R
Probe alarm 4
D
13
13
R
Compressor status relay
D
1
1
R
Defrost relay status
D
2
2
R
Fan relay status
D
3
3
R
AUX 1 relay status
D
4
4
R
AUX 2 relay status
D
5
5
R
Digital input 1 status
D
6
6
R
Digital input 2 status
D
7
7
R
Defrost status
D
31
31
R
Defrost call command
D
34
34
RW
Continuous cycle status
D
35
35
R
Continuous cycle call command
D
36
36
RW
Door status
D
37
37
R
AUX activation command
D
57
57
RW
Light activation command
D
58
58
RW
Controller ON/OFF
D
59
59
RW
Password
I
14
114
RW
Virtual probe fault alarm
D
9
9
R
Probe 1/2/3/4/5 fault alarm
D
10/11/12/13/14
10/11/12/13/14
R
Low temperature alarm
D
15
15
R
High temperature alarm
D
16
16
R
Immediate external alarm
D
17
17
R
Delayed external alarm
D
18
18
R
Evaporator 1 defrost timeout alarm
D
19
19
R
Evaporator 2 defrost timeout alarm
D
20
20
R
Pump down timeout alarm
D
21
21
R
Low pressure alarm
D
21
21
R
High condenser temperature alarm
D
24
24
R
Door open for too long alarm
D
25
25
R
RTC error
D
26
26
R
Control parameter EEPROM error
D
27
27
R
Operating parameter EEPROM error
D
28
28
R
HA HACCP alarm
D
29
29
R
HF HACCP alarm
D
30
30
R
Alarm autostart in pump down
D
32
32
R
Summary of Contents for easy small wide