Carel easy small wide User Manual Download Page 15

15

ENG

ir0300028EN rel. 1.1 - 05.05.2017

2.10  Remote display connection

To connect the remote display, use the dedicated cable (P/N PSTCON0*B0) 
and the tLAN interface card (P/N IROPZDSP00). See the following diagram. 
Also set a value >0 for parameter /tE, to display the reading on the remote 
display.

Par.

Description

Def

Min

Max

UOM

/tE

Reading on remote display

0

6

6

-

0

Not fi tted

4

Probe 3

1

Virtual probe

5

Probe 4

2

Probe 1

6

Reserved

3

Probe 2

Tab. 2.b 

2.11 Network connection

Warnings:

• 

the RS485 converter (IROPZ485x0) is sensitive to electrostatic 
discharges and therefore must be handled with extreme care;

• 

check the documents on the IROPZ485x0 interface for connection 
instructions, so as to avoid damaging the controller;

• 

fasten the converter properly so as to prevent disconnection;

• 

complete the wiring without power connected;

• 

keep the IROPZ485x0 interface cables separate from the power cables 
(relay outputs and power supply).

The RS485 converter is used to connect the ir33+, ir33+ wide and easy wide 
controllers to the supervisor network for the complete management and 
monitoring of the connected controllers. The system allows a maximum 
of 207 units, with a maximum length of 1000 m. Connection requires the 
standard accessories (RS485-USB converter, CAREL P/N CVSTDUMOR0) 
and a 120 Ω terminating resistor to be installed on the terminals of the 
last connected controller. Connect the RS485 converter to the controllers 
and make the connections as shown in the fi gure. To assign the serial 
address, see parameter H0. See the instruction sheets on the converters 
for further information.

Fig. 2.ar

UPLOAD

DOWNLOAD

EXTENDED DOWNLOAD

• 

load the parameters from a controller onto the key (UPLOAD);

• 

copy from the key to a controller (DOWNLOAD);

• 

extended copy from the key to a controller (EXTENDED DOWNLOAD).

Important:

 The parameters can only be copied between 

controllers with the same part number. The UPLOAD operation can, 
however, always be performed.

Copying and downloading the parameters

The following operations are used for the UPLOAD and/or DOWNLOAD 
functions, simply by changing the settings of the dipswitches on the key:

1. 

open the rear cover on the key and position the 2 dipswitches 
according to the desired operation;

2. 

close the rear cover on the key and plug the key into the connector 
on the controller;

3. 

press the button and check the LED: red for a few seconds, then 
green, indicates that the operation was completed correctly. Other 
signals or the fl ashing of the LED indicates that problems have 
occurred: see the table below;

4. 

at the end of the operation, release the button, after a few seconds 
the LED goes off ;

5. 

remove the key from the controller.

LED signal

Error

Meaning and solution

Red LED 
fl ashing

Batteries discharged at 
start copy

The batteries are discharged, the 
copy operation cannot be perfor-
med. Replace the batteries.

Green LED 
fl ashing

Batteries discharged 
during copy or at end 
of copy

During the copy operation or at the 
end of the operation the battery le-
vel is low. Replace the batteries and 
repeat the operation.

Red/green 
LEDs fl ashing 
(orange signal)

Controller not compa-
tible

The parameter set-up cannot be 
copied as the connected controller 
model is not compatible. This error 
only occurs for the DOWNLOAD 
function; check the controller P/N 
and run the copy only for compa-
tible models.

Red and green 
LEDs on

Error in data being 
copied

Error in the data being copied. The 
EEPROM on the controller is cor-
rupted,  therefore the data cannot 
be copied to/from the key.

Red LED on 
steady

Data transfer error

The copy operation was not com-
pleted due to a serious error when 
transferring or copying the data. 
Repeat the operation, if the pro-
blem persists check the key con-
nections.

LEDs off 

Batteries disconnected

Check the batteries.

Tab. 2.a 

Note: 

the DOWNLOAD operation (normal or extended) is possible 

even if the operating and control parameters are incorrect; in this case, 
they will be recovered from the key. Be careful when recovering the unit 
parameters from a key, as these determine the low-level operation of the 
controller (unit model, type of interface, assignment of logical relay to 
physical relay, brightness of the display, level of modulation of the relay 
control signal …). The unit parameters from the original model must 
therefore be restored to ensure correct operation of the controller.

Summary of Contents for easy small wide

Page 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s ir33 platform ir33 ir33 wide ir33 small wide easy wide y easy small wide Electronic controller User manual...

Page 2: ......

Page 3: ...ot use corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those specified in the technical manual All of the above suggestions...

Page 4: ...4 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Page 5: ...ter 31 6 8 Light and Aux outputs 32 6 9 Defrost 32 6 10 Evaporator fans 34 6 11 Condenser fans 35 6 12 Duty setting par c4 35 6 13 Running time defrost par d10 d11 35 7 PARAMETER TABLE 36 7 14 Variabl...

Page 6: ...6 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Page 7: ...by different icons according to the category temperature control with virtual control probe and set point variation at night digital inputs to activate alarms enable or activate defrosts door curtain...

Page 8: ...nstruction sheet 050003920 IREVXGD000 PST00VR100 Fig 1 g Fig 1 h RS485 serial interface P N IROPZ48500 and IROPZ485S0 Plugged directly into the programming key connector this provides connection to th...

Page 9: ...Fig 2 e 2 2 Panel mounting To install the ir33 ir33 wide and ir33 small wide controllers use the 2 brackets shown in the figure 1 2 Fig 2 f 2 3 Rear panel mounting The models with separate membrane k...

Page 10: ...o ir33 165 mm 21 mm 55 mm 26 1 mm Fig 2 j easy wide easy small wide STEP 1 Apply the two covered brackets to the controller Drill the holes with the spacing shown in the figure and make the opening fo...

Page 11: ...xAxxxx 115 V 50 mA max SERIAL and KEY Fig 2 t 6 7 8 4 A 8A 2FLA 12LRA 1 2 3 4 5 8 9 10 11 12 PROBES DI DI L N 1 2 1 2 R1 R2 R1 R2 12 2 A 12A 5FLA 30LRA EN60730 1 UL 873 AUX 10T60 POWER SUPPLY 250 V Co...

Page 12: ...on terminal 3 12 A Ixxxxx0xxxx 12 V 300 mA max 12 18 Vdc 300 mA dc max IxxxxxLxxxx 12 24 V 300 mA max 12 30 Vdc 300 mA dc max tLAN interface SERIAL and KEY IxxxF 0 7 0 L N C 0 2 xx Fig 2 ac 6 7 tLAN...

Page 13: ...Corrente massima totale su terminale 3 12 A Maximum current on terminal 3 12 A L N 115 230 V 50 mA max tLAN interface SERIAL and KEY IxxxC 0 7 H N C 0 2 xx Fig 2 ad 6 7 8 4 A 8A 2FLA 12LRA 8 4 A 8A 2F...

Page 14: ...o not use ethanol hydrocarbons petrol ammonia and by products Use neutral detergents and water 2 9 Programming key copy set up Programming key IROPZKEY00 A0 The programming key can load up to 7 differ...

Page 15: ...g the settings of the dipswitches on the key 1 open the rear cover on the key and position the 2 dipswitches according to the desired operation 2 close the rear cover on the key and plug the key into...

Page 16: ...s of the parameters The remote display IREVXGD000 PST00VR100 shows the temperature with resolution to the tenths between 9 9 C and19 9 C Note the standard display on the user terminal and the remote d...

Page 17: ...he continuous cycle AUX DOWN SET DEF if pressed together for more than 1 second displays a submenu used to access the HACCP alarm parameters SET DEF If pressed for more than 1 s displays and or lets t...

Page 18: ...the set point differential temperature monitoring interval interval between defrosts end defrost temperature dripping time alarm thresholds alarm bypass times etc See the parameter table Procedure 1 p...

Page 19: ...P DOWN button for at least 5 seconds all the changes made to the parameters temporarily stored in the RAM can be cancelled by not pressing any button for 60 seconds thus returning to the standard disp...

Page 20: ...st deactivation on ir33 On Off To switch the controller off from the keypad press On Off for 3 seconds The display shows the text Off flashing for 3 seconds and then on steady Finally the text Off alt...

Page 21: ...inally press Prg for 5 seconds to save the value of the parameter HACCP menu The controller must be fitted with the RTC real time clock To enter the HACCP menu press the combination button shown the t...

Page 22: ...ple in the case of bottle coolers typically used in supermarkets where the doors are opened frequently due to the greater thermal inertia of the liquids compared to the air and the fact that the probe...

Page 23: ...ogramming key Procedure power down the controller power up while holding Prg mute the display will show the first set bn0 press UP DOWN to select set bn1 to bn6 For example select bn2 press Set to con...

Page 24: ...reasing order with that configuration Par Description Def Min Max UOM A2 Probe 2 configuration S2 M models 0 0 4 A2 Probe 2 configuration S2 0 Absent 1 Product display only 2 Defrost 3 Condenser 4 Fro...

Page 25: ...delayed external alarm is thus signal only 3 Probe shown on the display IR33M models On thermometer only models this setting selection is used to exploit the digital input in order to show on the disp...

Page 26: ...close the door If after being closed for the first time the door remains closed for longer than time d8 or d8d the controller resumes normal operation compressor and evaporator fan switched on if nee...

Page 27: ...r3 direct reverse operating mode When the contact is open the controller operates in direct mode cooling when the contact is closed in reverse mode heating A switch can therefore be connected to sele...

Page 28: ...when the internal timer is set Relay output protectors parameters c7 c8 c9 Par Description Def Min Max UOM c0 Compressor fan and AUX start delay at power on 0 0 15 min c1 Minimum time between success...

Page 29: ...r4 Automatic night time set point variation 3 0 20 20 C F 4 Virtual probe composition 0 control probe S1 100 probe S2 0 0 100 Tab 6 b Parameter 4 is used to determine the virtual probe Sv as the weigh...

Page 30: ...wn whenever closing pump down valve following low pressure switch activation with no cooling demand c10 Pump down by time or pressure 0 1 pressure time 0 0 1 Tab 6 d Note c8 is a masked parameter and...

Page 31: ...alarm signal can be ignored by suitably setting parameter c6 alarm bypass after continuous cycle Par Description Def Min Max UOM cc Continuous cycle duration 0 0 15 hour c6 Low temperature alarm bypa...

Page 32: ...me 4 heater by time with temperature control The defrost can end by temperature in which case the defrost probe Sd must be installed or by time In the first case the defrost ends when the defrost prob...

Page 33: ...valve Pump down Pump down stage FAN Evaporator fan Def Defrost V_def Hot gas valve Drip Dripping E Evaporator Post drip Post dripping C Condenser S2 Defrost probe V2 Thermostatic expansion valve L Li...

Page 34: ...situation of this type it is preferable to enable defrost on start up above all if the defrost is controlled by temperature probe on the evaporator therefore avoiding unnecessary defrosts or at least...

Page 35: ...20 C F Tab 6 o ON OFF FAN F4 F5 Sc F4 F4 0 2 First switch on t t Fig 6 t Key Sc Condenser probe Sv Virtual probe FAN Condenser fans t Time F4 Deactivation temperature F5 Differential Note if no conde...

Page 36: ...irtual probe 5 Probe 4 2 Probe 1 6 Reserved 4 Probe 3 MSYFCH 0 0 6 I 19 119 R W C P Type of probe 0 NTC Standard Range 50T90 C 1 NTC Enhanced Range 40T150 C 2 PTC Standard Range 50T150 C MSYFCH 0 0 2...

Page 37: ...shown 4 heater by time with temperature control Ed1 Ed2 not shown SYFCH 0 0 4 I 37 137 R W F dI Maximum time between consecutive defrosts 0 defrost not performed SYFCH 8 0 250 hr min I 38 138 R W F dt...

Page 38: ...ed SYFCH 0 0 250 min I 54 154 R W C A8 Enable alarms Ed1 and Ed2 end defrost by timeout 0 alarms disabled SYFCH 0 0 1 D 49 49 R W C Ado Light management with door switch Ado Light when ope ning the do...

Page 39: ...sweat heater function disabled F MSYFCH 0 50 200 C F A 37 37 R W C HrL Remote light relay status on Master 0 disabled MSYFCH 0 0 1 D 62 62 R W C HrA Remote AUX relay status on Master 0 disabled MSYFCH...

Page 40: ...of parameter sets available I 137 237 R Digital input 1 status D 6 6 R Digital input 2 status D 7 7 R Virtual probe fault alarm D 9 9 R Probe alarm 1 D 10 10 R Probe alarm 2 D 11 11 R Probe alarm 3 D...

Page 41: ...controller itself on the probes or in network communication An alarm can also be activated from an external contact immediate or delayed See paragraph 5 2 The display shows IA or dA and at the same t...

Page 42: ...year month day hours minutes and duration in minutes of the selected alarm press Prg mute again to return to the previous list In addition the HACCP alarm menu allows the following operations delete t...

Page 43: ...nal contact ON ON automatic duty setting A6 duty setting A6 OFF OFF OFF duty setting A6 dA Delayed alarm from external contact ON ON automatic duty setting A6 OFF if A7 0 OFF if A7 0 OFF if A7 0 duty...

Page 44: ...old or the contact closes the alarm is not signalled and the count is reset When a new alarm condition occurs the count starts from 0 again Parameter A6 has a similar meaning to parameter c4 duty sett...

Page 45: ...erature alarm threshold Acd Alarm delay cht High cond temperature pre alarm Sc Condenser probe CHT High condensing temperature alarm AE High condensing temperature alarm differential 8 8 Frost protect...

Page 46: ...1 FLA 6 LRA C300 30000 IRxxxx E A N R C B A M L T xxx R1 R2 8 4 A N O 6 4 A N C 100000 8 A res 2 FLA 30000 IRxxxx 0 L H N R C B A M L T xxx R2 R3 R4 2 2 A N O N C 12 LRA C300 IRxxxx E A P Q S U V X Y...

Page 47: ...ing cycles 250 V operating cycles PBEVxx E A P S V Y xxx 5A 5 1 A 100000 5A res 1FLA 6 LRA C300 30000 PBEVxx E A N C A L xxx PBEVxx O H N C A L xxx 8 A 8 4 A N O 6 4 A N C 2 2 A N O N C 100000 8 A res...

Page 48: ...5A on model IRYS0EP 8 A Programming keypad key Special functions HACCP Real Time Clock Function can be enabled when Real Time Clock option available models IR C B L T S U Y Z and on IR33 power models...

Page 49: ...twork interface Note standard Tab 9 e 9 6 easy wide part numbers Features PBEVS0EAAA PBEVY0EVD0 PBEVC0HND0 PBEVC0HNBA PBEVC0HCAA PBEVH0HNAA PBEVH0HNB0 PBEVH0HNBW PBEVS0SAFA PBEVC0SNFA PBEVC0SNFW Power...

Page 50: ...PZKEYA0 connected to the computer via the converter IROPZPRG00 When opening the VPM program choose the device to be configured ir33 The Home page is displayed with the options to create a new project...

Page 51: ...he right button choose Add set for each additional set Fig 10 i Set1 is displayed Fig 10 j Note onthecontroller Set0 Set1 Set6arenamedbn0tobn6respectively Set0 is the default set on the controller i e...

Page 52: ...d starting from the eighth defrost Note if there are two evaporators the defrost duration used to determine the defrosts to be skipped is the longer nominal defrost duration Possible operating sequenc...

Page 53: ...2 The following situations may occur if the outputs are not configured or there are probe alarms DEFROST BY TEMPERATURE Defrost probe evap output config Situation Effect Probe 2 defrost output 1 No pr...

Page 54: ...of operation ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 1 t t t t Fig 11 d ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 2 t t t t Fig 11 e ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OF...

Page 55: ......

Page 56: ...EL INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency ir33plus 0300028EN rel 1 1 05 05 2...

Reviews: