39
ENG
ir0300028EN rel. 1.1 - 05.05.2017
User
Par.
Description
Models
Def
Min Max UOM Type CAREL SVP ModBus®
R/W
CnF
C
H0
Serial address
MSYFCH
1
0
207
-
I
60
160
R/W
C
H1
AUX output confi guration
0 = normally energised alarm
1 = normally de-energised alarm
2 = auxiliary
3 = light
4 = auxiliary evaporator defrost
5 = pump down valve
6 = condenser fan
7 = delayed compressor
8 = auxiliary with deactivation when OFF
9 = light with deactivation when OFF
10 = no function
11 = reverse with neutral zone
12 = second compressor step
13 = second compressor step with rotation
CH
1
0
13
-
I
61
161
R/W
C
H2
Disable keypad functions
MSYFCH
1
0
6
-
I
62
162
R/W
C
H4
Buzzer: 0/1=enabled/disabled
MSYFCH
0
0
1
-
D
53
53
R/W
C
H5
AUX2 output confi guration: see H1
H
3
0
13
-
I
64
164
R/W
C
H6
Terminal keypad lock confi guration
0 = all buttons enabled
MSYFCH
0
0
255
-
I
65
165
R/W
C
H7
Keypad: 0 = standard; 1 = modifi ed
MSYFCH
0
0
1
-
D
54
54
R/W
C
H8
Output switched with scheduler 0 = Light; 1= AUX
MSYFCH
0
0
1
-
D
60
60
R/W
C
H9
Set point variation with scheduler 0/1 = no/yes
MSYFCH
0
0
1
-
D
61
61
R/W
C
Hdn
Number of default parameter sets available
MSYFCH
0
0
6
-
I
137
237
R/W
C
Hdh
Anti-sweat heater off set
0 = anti-sweat heater function disabled (°C)
32 = anti-sweat heater function disabled (°F)
MSYFCH
0
-50
200
°C/°F A
37
37
R/W
C
HrL
Remote light relay status on Master: 0 = disabled
MSYFCH
0
0
1
-
D
62
62
R/W
C
HrA
Remote AUX relay status on Master: 0 = disabled
MSYFCH
0
0
1
-
D
63
63
R/W
C
HSA
Remote controller alarms on Master: 0 = disabled
MSYFCH
0
0
1
-
D
64
64
R/W
C
In
Type of unit
0 = Normal
1 = Master
2…6 = Slave 1 to 5
MSYFCH
0
0
6
-
I
138
238
R/W
User
Par.
Description
Models
Def
Min Max UOM
Type CAREL SVP ModBus®
R/W
HcP
C
HAn
Number of HA alarms
MSYFCH
0
0
15
-
I
67
167
R
C
HA…
HA2
HA HACCP alarms activated (press Set)
MSYFCH
-
-
-
-
-
-
-
R
y__
Alarm 1 to 3 - Year
-
0
0
99
years
I
70/76/82
170
R
M__
Alarm 1 to 3 - Month
-
0
1
12
month I
71/77/83
171
R
d__
Alarm 1 to 3 - Day of the month
-
0
1
7
day
I
72/78/84
172
R
h__
Alarm 1 to 3 - Hour
-
0
0
23
hour
I
73/79/84
173
R
n__
Alarm 1 to 3 - Minute
-
0
0
59
minute I
74/80/85
174
R
t__
Alarm 1 to 3 - Duration
-
0
0
99
hour
I
75/81/86
175
R
C
HFn
Number of HF alarms
MSYFCH
I
68
176…181
R
C
HF…HF2 HF HACCP alarms activated (press Set)
MSYFCH
-
-
-
-
I
-
-
R
y__
Alarm 1 to 3 - Year
0
0
99
years
I
88/94/100
188
R
M__
Alarm 1 to 3 - Month
0
1
12
month I
89/95/101
189
R
d__
Alarm 1 to 3 - Day of the month
0
1
7
day
I
90/96/102
190
R
h__
Alarm 1 to 3 - Hour
0
0
23
hour
I
91/97/103
191
R
n__
Alarm 1 to 3 - Minute
0
0
59
minute I
92/98/104
192
R
t__
Alarm 1 to 3 - Duration
0
0
99
hour
I
93/99/105
193
R
C
Htd
HACCP alarm delay
0 = Monitoring disabled
MSYFCH
0
0
250
min
I
69
169
R/W