
31
ENG
ir0300028EN rel. 1.1 - 05.05.2017
6.5 Autostart in pump down
As seen in the previous paragraph, on reaching the set point, the
controller closes the pump down valve and then the pressure switch
signals low pressure. If, due to valve tightness problems, the pressure
switch is activated again, the compressor can be restarted by the
Autostart function.
Par. Description
Def
Min Max UOM
c9
Autostart in pump down
0 = Disabled
1 = Pump down whenever closing pump
down valve & following low pressure switch
activation with no cooling demand
0
0
1
-
Tab. 6.e
ON
OFF
ON
OFF
t
CMP,
FAN
VPD
c7
PRESSURE
SWITCH
St
ON
OFF
AtS
ON
OFF
Sv
c7
Fig. 6.j
Key
CMP, FAN
Compressor, fan
St
Set point
VPD
Pump down valve
c7
Maximum pump down time
Pressure switch Pressure switch
t
Time
Sv
Control probe
AtS Autostart in pump down
Note:
•
in the compressor autostart function, the protection times c1 and c2
are applied, but not c3;
•
The message “AtS” is reset automatically when the next pump down
cycle terminates correctly.
Important
: in the event of “Pd” alarms, the autostart function is
deactivated.
6.6 Continuous
cycle
For information on activating the continuous cycle from the keypad, see
chapter 3. The value of parameter cc must be >0. During operation in
continuous cycle, the compressor continues to operate, independently
of the controller, for the time cc, so as to lower the temperature even
below the set point. The continuous cycle is stopped after the time “cc”
or when reaching the minimum specifi ed temperature, corresponding to
the minimum temperature alarm threshold (“AL”). If, after the end of the
continuous cycle, the temperature falls by inertia below the minimum
temperature threshold, the low temperature alarm signal can be ignored
by suitably setting parameter c6: alarm bypass after continuous cycle.
Par.
Description
Def
Min Max UOM
cc
Continuous cycle duration
0
0
15
hour
c6
Low temperature alarm bypass time after
continuous cycle
2
0
250
hr/
min
Tab. 6.f
6.7 Anti-sweat
heater
When the unit is powered on, the compressor is activated in cooling
mode and the AUX and light outputs are disabled until the control probe
measures a value less than St + Hdh. The aim is to prevent the light or the
heater connected to the AUX output from adding heat and contrasting
the work done by the compressor. When the function is active, the display
shows the corresponding icon, fl ashing.
Par.
Description
Def
Min Max UOM
Hdh Anti-sweat heater off set
0 = anti-sweat heater function disabled (°C)
32 = anti-sweat heater function disabled (°F)
0
-50
200
°C/°F
Tab. 6.g
The following example refers to the confi guration where Hdh = 2 and St
= 0, with activation of the auxiliary output (H1 = 2)
CMP,
FAN
St+ Hdh
AUX,
LIGHT
ON
OFF
Sv
ON
OFF
t
Fig. 6.k
Key
CMP, FAN Compressor, fan
LIGHT
Light
AUX
Auxiliary output
Sv
Virtual probe
St
Set point
Hdh
Off set
t
Time
ir33+
Note:
•
when alarms “HI”, “IA”, “dA”, “CHt”, “EE”, “EF” ,”rE” are active of the controller
is OFF, the anti-sweat heater function is still enabled;
•
at the end of the anti-sweat heater function, the outputs confi gured
as light or auxiliary can be controlled by the user from the keypad,
supervisor or digital inputs.
•
if AUX1 or AUX2 is confi gured as a light or auxiliary output at power on,
the output retains the same status as when previously powered down.
If the anti-sweat heater function is activated, this is no longer true: the
output at power on remains OFF while the function is active. When
the control temperature (virtual probe) reaches the value of “St+Hdh”,
the function ends, activating the light output and auxiliary output
irrespective of their status when previously powered down.
Summary of Contents for easy small wide
Page 2: ......
Page 4: ...4 ENG ir33plus 0300028EN rel 1 1 05 05 2017...
Page 6: ...6 ENG ir33plus 0300028EN rel 1 1 05 05 2017...
Page 55: ......