Page 18 of 32
Installation Manual
September 2020 • Rev. 1.5
The inputs can be individually set through the host software to be supervised or non-
supervised in future release. The default input setting is non-supervised. Supervised
input points require a Cansec CA-EOL resistor pack to be placed at the device being
monitored. Supervised input points will inform the host of 4 supervised states:
Alarm
,
Secure
,
Trouble High
and
Trouble Low
. These are the same 16 input points which
can be used with the door provisioning combinations, thus devices such as the Door
Contact and RTE/REX pushbutton can used in supervised mode of operation if
necessary.
Input Wiring – Supervised or Non-Supervised
Figure 13