7.3 Setting ranges and steps
Function
Para-
Setting range
Steps
Tolerance
meter
Transformer ratiio
U
prim
/U
sek
(SEC) 1.01...6500
0.01; 0.02; 0.05
0.1; 0.2; 0.5; 1.0;
2.0; 5.0; 10;
20; 50
Rated frequency
f
N
f = 50 Hz / f = 60 Hz
Switch group
D/Y
D = Delta / Y = Stern
Switch over
P2/FR
SET1/SET2/B_S2/R_S2/B_FR/
R_FR/S2_FR
LED blinking at
FLSH/NOFL
pick-up
U</<<
U</<<
U
N
= 100 V:
2...200 V (EXIT)
1 V
± 1 % of set value
U
N
= 230 V:
or < 0.3 % U
N
2...460 V (EXIT)
1 V
U
N
= 400 V:
4...800 V (EXIT)
0.04...50 s (EXIT)
2 V
t
U<
0.01; 0.02; 0.05;
± 1 % or
t
U<<
0.1; 0.2; 0.5; 2.0s ± 15 ms
U>/>>
U>/>>
U
N
= 100 V:
2...200 V (EXIT)
1 V
± 1 % of set value
t
U>
U
N
= 230 V:
or < 0,3 % U
N
t
U>>
2...460 V (EXIT)
1 V
U
N
= 400 V:
4...800 V (EXIT)
2 V
0.04...50 s (EXIT)
0.01; 0.02; 0.05;
± 1 % or
0.1; 0.2; 0.5; 2.0s ± 15 ms
Frequency meas-
T
2...99 (Cycles)
1
uring repetition
Frequency
f
1
- f
3
30...49.99; EXIT; 50.01...70 Hz
1
0,1; 0,01 Hz
0.005 Hz
element 1 - 3
40...59.99; EXIT; 60.01...80 Hz
2
t
f1
- t
f3
t
f,min
3
...50 s; EXIT
0.0 1;0.02; 0.05;
± 1 % or ± 20 ms
0.1; 0.2; 0.5; 2.0s
df/dt-Step
df
0.2...10 Hz/s (EXIT)
0.1; 0.2; 0.5 Hz/s
0.1 Hz/s
df/dt-Measuring
dt
2...64 Periods
1
repetition
ΔΘ
ΔΘ
2°...22° (EXIT)
1°
± 1°
Vector surge
1/3
1Ph / 3Ph
logic
Voltage theshold
U
B
<
U
N
= 100 V:
for frequency
(LED‘f’+
5...100 V
1 V
± 1 % of set value
measuring
ΔΘ
/df)
U
N
= 230 V:
or < 0.3 % U
N
12...230 V
1 V
U
N
= 400 V:
20...400 V
2 V
TTTTTable 7.1: Setting ranges and steps
able 7.1: Setting ranges and steps
able 7.1: Setting ranges and steps
able 7.1: Setting ranges and steps
able 7.1: Setting ranges and steps
1)
At 50 Hz rated frequency
2)
At 60 Hz rated frequency
3)
t
f,min
min. time delay; t
f,min
= (T+1) x 20 ms
4)
only Modbus
2 4
2 4
2 4
2 4
2 4