C&S MRN3 Manual Download Page 12

1 2

1 2

1 2

1 2

1 2

Function

Display shows

Pressed pushbutton

Corresponding

Type of relay

LED

Trigger signal for the fault  recorder

TEST, P_UP, A_PI, TRIP

<SELECT/RESET><+><->

FR

Number of fault occurences

S=2, S=4, S=8

<SELECT/RESET><+><->

FR

Display of date and time

Y=99, M=10, D=1,

<SELECT/RESET><+><->

Ÿ

h=12, m=2, s=12

Software version

First part (e.g. D02-)

<TRIP>

Sec. part (e.g. 6.01)

one time for each part

Manual trip

TRI?

<TRIP>
three times

Inquire password

PSW?

<SELECT/RESET>/
<+>/<->/<ENTER>

Relay tripped

TRIP

<TRIP> or fault tripping

Secret password input

XXXX

<SELECT/RESET>/
<+>/<->/<ENTER>

System reset

CSPC

<SELECT/RESET>
for about 3 s

TTTTTable 5.1: possible indication messages on the display

able 5.1: possible indication messages on the display

able 5.1: possible indication messages on the display

able 5.1: possible indication messages on the display

able 5.1: possible indication messages on the display

5.2 Setting procedure

In this paragraph the settings for all relay parameters are
described in detail. For parameter setting a password has
to be entered first (please refer to 4.4 of description “MR-
Digital Multifunctional Relays”).

5.3 Systemparameter
5.3.1 Display of residual voltage U

E

 as

primary quantity (U

prim

/U

sec

The residual voltage can be shown as primary measuring
value. For this parameter the transformation ratio of the
VT has to be set accordingly. If the parameter is set to
“sek”, the measuring value is shown as rated secondary
voltage.
Example :
The voltage transformer used is of 10 kV/100V. The
transformation ratio is 100 and this value has to be set
accordingly. If still the rated secondary voltage should be
shown, the parameter is to be set to 1.

5.3.2

ΔΔΔΔΔ

/Y - Switch over

Depending on the mains voltage conditions, the input
voltage transformers can be operated in delta or Y
connection. Change-overs are effected via the <+> and
the <-> keys and stored with <ENTER>.

5.3.3 Setting of nominal frequency

For proper functioning it is necessary to first adjust the
rated frequency (50 oder 60 Hz).
For this a distinction has to be made between the settings
v = 50 Hz / f = 50 Hz or v = 60 Hz / f = 60 Hz
The difference lies in the method of voltage measuring.
With the setting “v” = 50/60 Hz voltage measuring is
independent of the existing frequency. This means, the
voltage value can be correctly measured between 30 Hz
and 80 Hz without adverse effects from the frequency.
With the setting “f” = 50/60 Hz the measured voltage
value is influenced by the frequency. (see Table 5.2)

This difference in settings is required for the fault
recorder. If the fault recorder is to be used, the setting
must be f = 50 Hz or f = 60 Hz.
The different designations “f” or “v” have no influence on
any of the other functions.
All frequency functions are determined by setting the
nominal frequency, i.e. whether the set frequency
thresholds are evaluated as over or under frequency (see
also chapter 5.4.4). Also the cycle duration (20 ms at 50
Hz and 16.67 ms at 60 Hz) derives from this setting which
determines the minimum tripping delay for frequenc y
elements f

1

 - f

3

 with an adjustable multiplier (see also

chapter 5.4.5).
During setting of the nominal frequency a value in Hz is
shown on the display.

Declination of measuring value at 50Hz

Declination of measuring value at 60Hz

[%]

100.5

100.0

44

46

48

50

52

54

56

[Hz]

99.5

99.0
98.5
98.0

97.5

54

56

58

60

62

64

66

[Hz]

[%]

100.5

100.0

99.5

99.0
98.5
98.0

97.5

Summary of Contents for MRN3

Page 1: ...High Tech Range MRN3 Mains decoupling Relay C S Protection Control Ltd L3 TRIP ENTER SELECT RESET RS L2 L1 U U 1 3 U U fN DQ T MRN3 1 FR P2 D Y f max min DQ f1 tf1 f2 f3 tf2 tf3 tU tU tU tU...

Page 2: ...ge threshold value for frequency and vector surge measuring df dt at MRN3 2 MRN3 2 MRN3 2 MRN3 2 MRN3 2 5 4 8 Adjustment of the slave address 5 4 9 Setting of Baud rate applies for Modbus Protocol onl...

Page 3: ...g z effective analog low pass filter for suppressing harmonics when measuring frequency and vector surge z digital filtering of the measured values by using discrete Fourier analysis to suppress highe...

Page 4: ...1 and MRN3 2 Fig 3 1 Connection diagram MRN3 1 and MRN3 2 Storage division Independent of the recording time the entire storage capacity can be divided int0 several cases of disturbance with a shorter...

Page 5: ...and time The window for parameter setting is located behind the measured value display The parameter window can be accessed via the SELECT RESET key 3 2 Parameter settings System parameter P P P P Par...

Page 6: ...by a built in watchdog timer In case of a failure the watchdog timer resets the microprocessor and gives an alarm signal via the output relay self supervision 4 3 Voltage supervision The voltage elem...

Page 7: ...ripping during occurence of interference voltages and phase shifts the relay works with an adjustable measuring repetition see chapter 5 4 2 Frequency tripping is sometimes not desired by low measured...

Page 8: ...evelopment Power relays are able to pickup within 200 ms but they cannot prevent power to rise to short circuit values too Since power changes are also caused by sudden loaded alternators the use of p...

Page 9: ...a high resistance mains failure occurs then there are no vector surge nor power and frequency changes and the mains failure is not detected This can only happen if the public grid is disconnected near...

Page 10: ...3 3 3 3 df dt df dt df dt df dt df dt 1 voltage to external free program free program free program free program free program blocking input is mable mable mable mable mable applied 2 blocking input i...

Page 11: ...inseconds one time for each value tf1 frequencyelementf2 setting value in Hz SELECT RESET f2 tripping delay of frequency element f2 settingvalueinseconds one time for each value tf2 frequencyelementf3...

Page 12: ...ary voltage should be shown the parameter is to be set to 1 5 3 2 Y Switch over Depending on the mains voltage conditions the input voltage transformers can be operated in delta or Y connection Change...

Page 13: ...put Parameter switch B_FR External trigger RESET input ing of the fault recorder R_FR Blocking input External trigg ering of the fault recorder R_FR Parameter switch External trigg ering of the fault...

Page 14: ...s The minimum tripping delay tf1min of the relay depends upon the number of set measuring repetitions T periods and amounts to T tf min 2 49 T 1 20 ms 50 69 T 49 50 ms 1 s 70 99 T 69 100 ms 2 s When s...

Page 15: ...plies for Modbus Protocol only Different transmission rates Baud rate can be set for data transmission via Modbus Protocol The rate can be changed by push buttons and and saved by pressing ENTER 5 4 1...

Page 16: ...put relays 1 4 are normally off and can be assigned as alarm or tripping relays to the voltage functions which can either be done by using the push buttons on the front plate or via serial interface R...

Page 17: ...MRN3 MRN3 MRN3 offers a minimum maximum storage each for the measuring values of the vector surge as well as the frequency gradient These min max values are mainly used to appraise the system quality...

Page 18: ...LT1 FLT2 FLT3 are displayed FLT1 means the latest fault data set recorded At the same time the parameter set active at the occurence is shown z By pressing SELECT RESET the fault measuring values can...

Page 19: ...lay shows the first part of the software version of the relay e g D08 By pressing the push button TRIP twice the display shows the second part of the software version of the relay e g 4 01 The softwar...

Page 20: ...Delta connection At Delta connection At Delta connection z Phase to phase voltages LED L1 L2 L2 L3 L3 L1 The frequency is indicated on the display in Hz LED f system frequency 50 01Hz Indication 5001...

Page 21: ...kes it necessary that the other frequency elements of the relay have to be blocked by setting the frequency pickup values f1 f3 to EXIT For testing the pickup and dropout to pickup values the test fre...

Page 22: ...measures correctly 6 7 Maintenance Maintenance testing is generally done on site at regular intervals These intervals vary among users depending on many factors e g the type of protective relays empl...

Page 23: ...interruption of the auxiliarxy supply without a facting the function of the device 50 ms Influences on voltage measuring Aux voltage in the range 0 8 UH UHN 1 2 no additional influences measured Freq...

Page 24: ...0 1 0 2 0 5 2 0s 15 ms Frequency meas T 2 99 Cycles 1 uring repetition Frequency f1 f3 30 49 99 EXIT 50 01 70 Hz1 0 1 0 01 Hz 0 005 Hz element 1 3 40 59 99 EXIT 60 01 80 Hz2 tf1 tf3 tf min 3 50 s EXI...

Page 25: ...TRIP A_PI TEST FR Pre trigger time 0 05 s 8 00 s T T T T Table 7 2 Parameters for the fault recorder able 7 2 Parameters for the fault recorder able 7 2 Parameters for the fault recorder able 7 2 Par...

Page 26: ...lement s 0 04 U pickup value for overvoltage element low set V 110 250 440 tU tripping delay for overvoltage element s 0 04 U pickup value for overvoltage element high set V 120 270 480 tU tripping de...

Page 27: ...Set1 Set1 Set1 Set1 Set2 Set2 Set2 Set2 Set2 Set1 Set1 Set1 Set1 Set1 Set2 Set2 Set2 Set2 Set2 Set1 Set1 Set1 Set1 Set1 Set2 Set2 Set2 Set2 Set2 U X X U X X U X X U X X f1 X X f2 X X f3 X X X X df dt...

Page 28: ...r Reset input Low High range for Reset input Low High range for Reset input Low High range for Reset input Low High range for blockage input Low High range for blockage input Low High range for blocka...

Reviews: