7.3.1 Interface parameter
Function
Function
Function
Function
Function
PPPPParameter
arameter
arameter
arameter
arameter
Modbus-Protocol
Modbus-Protocol
Modbus-Protocol
Modbus-Protocol
Modbus-Protocol
RS485 Open Data Protocol
RS485 Open Data Protocol
RS485 Open Data Protocol
RS485 Open Data Protocol
RS485 Open Data Protocol
RS
Slave-Address
1-32
1-32
RS
Baud-Rate*
1200, 2400, 4800, 9600
9600 (fixed)
RS
Parity*
even, odd, no
“even Parity” (fixed)
TTTTTable 7.1 : Interface parameter
able 7.1 : Interface parameter
able 7.1 : Interface parameter
able 7.1 : Interface parameter
able 7.1 : Interface parameter
* only Modbus Protocol
7.3.2 Parameters for the fault recorder
Function
Function
Function
Function
Function
PPPPParamter
aramter
aramter
aramter
aramter
Adjustment example
Adjustment example
Adjustment example
Adjustment example
Adjustment example
FR
Number recordings
(1)* 2 x8 s; (3)* 4 x 4 s; (7)* 8 x 2 s (with 50 Hz)
(1)* 2 x6.66 s; (3)* 4 x 3.33 s; (7)* 8 x 1.66 s (60 Hz)
FR
Saving of the recording at the occurence
P_UP; TRIP; A_PI; TEST
FR
Pre-trigger-time
0.05 s - 8.00 s
TTTTTable 7.2 : Parameters for the fault recorder
able 7.2 : Parameters for the fault recorder
able 7.2 : Parameters for the fault recorder
able 7.2 : Parameters for the fault recorder
able 7.2 : Parameters for the fault recorder
* is written over when a new trigger signal arrives
7.4 Output relays
Relay type
Relay type
Relay type
Relay type
Relay type
TTTTTrip relays / change
rip relays / change
rip relays / change
rip relays / change
rip relays / change-----over contacts
over contacts
over contacts
over contacts
over contacts
Alarm relays / change-over contacts
Alarm relays / change-over contacts
Alarm relays / change-over contacts
Alarm relays / change-over contacts
Alarm relays / change-over contacts
MRN2
1/2
4/1
TTTTTable 7.2: Output relays
able 7.2: Output relays
able 7.2: Output relays
able 7.2: Output relays
able 7.2: Output relays
8. Order form
Mains decoupling relay
MRN3-
With voltage-, frequency and
1
vector surge supervision
Voltage, frequency and
2
df/dt-supervision
Rated voltage:
100 V
1
230 V
2
400 V
4
Housing (12TE)
19“-rack
A
Flush mounting
D
RS485
Alternatively with Modbus Protocol
-M
Technical data subject to change without notice!
2 5
2 5
2 5
2 5
2 5