C&S MRN3 Manual Download Page 21

2 1

2 1

2 1

2 1

2 1

harmonics will be rejected by the internal DFFT-digital
filter. Whereas the RMS

RMS

RMS

RMS

RMS-metering instrument measures

the RMS-

RMS-

RMS-

RMS-

RMS-value of the input signals.

6.5.2 Checking the operating and

resetting values of the over/
undervoltage functions

Note:

When the measuring voltage is connected or
disconnected, vector surge tripping or df/dt tripping can
occur. In order to ensure a trouble-free test procedure,
the vector surge function or df/dt function of the relay
have to be blocked before tests are started.
Apply three voltages with the rated value and gradually
increase (decrease) the voltages until the relay starts, i.e.
at the moment when the LED U> (or U<) lights up or the
voltage alarm output relay (contact terminals D4/E4) is
activated. Read the operating voltage indicated by the
voltmeter. The deviation must not exceed 1% of the set
operating value.
Furthermore, gradually decrease (increase) the voltages
until the relay resets, i.e. the voltage alarm output relay
is disengaged. Check that the dropout to pickup ratio for
voltage is greater than 0.97 (for overvoltage function) or
smaller than 1.03 (for undervoltage).

6.5.3 Checking the relay operating time

of the over/undervoltage functions

To check the relay’s operating time, a timer must be
connected to the trip output relay (contact terminals D1/
E1). The timer should be started simultaneously with the
voltage change from sound condition to a faulty condition
and stopped by the trip relay contact. The operating time
measured by timer should have a deviation about 3% of
the set value or < 20 ms.

6.5.4 Checking the operating and reset-

ting values of the over/underfre-
quency functions

Note:

Due to frequency changes, vector surge tripping or df/dt
tripping can occur during frequency tests. In order to
ensure a trouble-free test procedure, the vector surge
function or df/dt function of the relay have to be blocked
before tests are started.
During frequency tests, each of the frequency elements
should be tested separately. This makes it necessary that
the other frequency elements of the relay have to be
blocked by setting the frequency pickup values f

1

 - f

3

 to

“EXIT”. For testing the pickup and dropout to pickup
values, the test frequency has to be increased (decreased)
until the relay is engergized. This is indicated by lighting
up of LEDs f

1

 - f

3

.

When comparing the values displayed with those of the
frequency meter, the deviation must not exceed 0.01 Hz.
The dropout to pickup values are ascertained by
increasing (decreasing) the test frequency slowly until the
output relay releases.
The dropout to pickup value for overfrequency must be >
0.99, and for underfrequency < 1.01.

6.5.5 Checking the relay operating time

of the over/underfrequency
functions

The operating time of the over/underfrequency functions
can be tested in the similar manner as in chapter 6.5.3
for over/undervoltage functions.

6.5.6 Checking the vector surge function

With the help of an advanced relay test equipment a
phase shift (vector surge) on the voltage signal can be
obtained to test the vector surge function of 

MRN3

MRN3

MRN3

MRN3

MRN3 

relay.

If there is no such testing facility available, a very simple
simulation circuit may be used to test the vector surge
function of the relay with a sufficient accuracy. Figure 6.2
shows the possibility to simulate a phase shift by means of
a RC circuit. Closing or opening the switch S1 causes the
phase angle of the input voltage to change depending on
the adjustable resistor R.
The phase angle obtained may be calculated with the
following formula and is almost independent on the test
voltages.
In case of a 3-phase vector surge, the angle 

ΔΘ

 can be

calculated with the following formula if the parameters R

0

,

R and C are known:

ΔΘ = 

 arctg

- arctg

Example:

R

0

 = 1 Ohm,

R = 363 Ohm, C = 3 

μ

F

then: 

ΔΘ

 

 19°

Usually the voltage source impedance R

0

 is negligible,

hence R

0

 may be assumed zero. Thus,  the value of R may

be calculated using the follwing formula :

ΔΘ

 w = 90°- arctg

Note!

Using the above test circuit with single-phase vector surge,
the resulting measured angle 

ΔΘ

 is about half the value

of 

ΔΘ

 calculated for a 3-phase vector surge. To make

tripping possible during a one phase test procedure, the
vector surge tripping has to be set to “1Ph”.

1

R

0

.

ω

.C

1

(R

0

 +R) .

 ω 

. C

1

R.

ω

.C

Summary of Contents for MRN3

Page 1: ...High Tech Range MRN3 Mains decoupling Relay C S Protection Control Ltd L3 TRIP ENTER SELECT RESET RS L2 L1 U U 1 3 U U fN DQ T MRN3 1 FR P2 D Y f max min DQ f1 tf1 f2 f3 tf2 tf3 tU tU tU tU...

Page 2: ...ge threshold value for frequency and vector surge measuring df dt at MRN3 2 MRN3 2 MRN3 2 MRN3 2 MRN3 2 5 4 8 Adjustment of the slave address 5 4 9 Setting of Baud rate applies for Modbus Protocol onl...

Page 3: ...g z effective analog low pass filter for suppressing harmonics when measuring frequency and vector surge z digital filtering of the measured values by using discrete Fourier analysis to suppress highe...

Page 4: ...1 and MRN3 2 Fig 3 1 Connection diagram MRN3 1 and MRN3 2 Storage division Independent of the recording time the entire storage capacity can be divided int0 several cases of disturbance with a shorter...

Page 5: ...and time The window for parameter setting is located behind the measured value display The parameter window can be accessed via the SELECT RESET key 3 2 Parameter settings System parameter P P P P Par...

Page 6: ...by a built in watchdog timer In case of a failure the watchdog timer resets the microprocessor and gives an alarm signal via the output relay self supervision 4 3 Voltage supervision The voltage elem...

Page 7: ...ripping during occurence of interference voltages and phase shifts the relay works with an adjustable measuring repetition see chapter 5 4 2 Frequency tripping is sometimes not desired by low measured...

Page 8: ...evelopment Power relays are able to pickup within 200 ms but they cannot prevent power to rise to short circuit values too Since power changes are also caused by sudden loaded alternators the use of p...

Page 9: ...a high resistance mains failure occurs then there are no vector surge nor power and frequency changes and the mains failure is not detected This can only happen if the public grid is disconnected near...

Page 10: ...3 3 3 3 df dt df dt df dt df dt df dt 1 voltage to external free program free program free program free program free program blocking input is mable mable mable mable mable applied 2 blocking input i...

Page 11: ...inseconds one time for each value tf1 frequencyelementf2 setting value in Hz SELECT RESET f2 tripping delay of frequency element f2 settingvalueinseconds one time for each value tf2 frequencyelementf3...

Page 12: ...ary voltage should be shown the parameter is to be set to 1 5 3 2 Y Switch over Depending on the mains voltage conditions the input voltage transformers can be operated in delta or Y connection Change...

Page 13: ...put Parameter switch B_FR External trigger RESET input ing of the fault recorder R_FR Blocking input External trigg ering of the fault recorder R_FR Parameter switch External trigg ering of the fault...

Page 14: ...s The minimum tripping delay tf1min of the relay depends upon the number of set measuring repetitions T periods and amounts to T tf min 2 49 T 1 20 ms 50 69 T 49 50 ms 1 s 70 99 T 69 100 ms 2 s When s...

Page 15: ...plies for Modbus Protocol only Different transmission rates Baud rate can be set for data transmission via Modbus Protocol The rate can be changed by push buttons and and saved by pressing ENTER 5 4 1...

Page 16: ...put relays 1 4 are normally off and can be assigned as alarm or tripping relays to the voltage functions which can either be done by using the push buttons on the front plate or via serial interface R...

Page 17: ...MRN3 MRN3 MRN3 offers a minimum maximum storage each for the measuring values of the vector surge as well as the frequency gradient These min max values are mainly used to appraise the system quality...

Page 18: ...LT1 FLT2 FLT3 are displayed FLT1 means the latest fault data set recorded At the same time the parameter set active at the occurence is shown z By pressing SELECT RESET the fault measuring values can...

Page 19: ...lay shows the first part of the software version of the relay e g D08 By pressing the push button TRIP twice the display shows the second part of the software version of the relay e g 4 01 The softwar...

Page 20: ...Delta connection At Delta connection At Delta connection z Phase to phase voltages LED L1 L2 L2 L3 L3 L1 The frequency is indicated on the display in Hz LED f system frequency 50 01Hz Indication 5001...

Page 21: ...kes it necessary that the other frequency elements of the relay have to be blocked by setting the frequency pickup values f1 f3 to EXIT For testing the pickup and dropout to pickup values the test fre...

Page 22: ...measures correctly 6 7 Maintenance Maintenance testing is generally done on site at regular intervals These intervals vary among users depending on many factors e g the type of protective relays empl...

Page 23: ...interruption of the auxiliarxy supply without a facting the function of the device 50 ms Influences on voltage measuring Aux voltage in the range 0 8 UH UHN 1 2 no additional influences measured Freq...

Page 24: ...0 1 0 2 0 5 2 0s 15 ms Frequency meas T 2 99 Cycles 1 uring repetition Frequency f1 f3 30 49 99 EXIT 50 01 70 Hz1 0 1 0 01 Hz 0 005 Hz element 1 3 40 59 99 EXIT 60 01 80 Hz2 tf1 tf3 tf min 3 50 s EXI...

Page 25: ...TRIP A_PI TEST FR Pre trigger time 0 05 s 8 00 s T T T T Table 7 2 Parameters for the fault recorder able 7 2 Parameters for the fault recorder able 7 2 Parameters for the fault recorder able 7 2 Par...

Page 26: ...lement s 0 04 U pickup value for overvoltage element low set V 110 250 440 tU tripping delay for overvoltage element s 0 04 U pickup value for overvoltage element high set V 120 270 480 tU tripping de...

Page 27: ...Set1 Set1 Set1 Set1 Set2 Set2 Set2 Set2 Set2 Set1 Set1 Set1 Set1 Set1 Set2 Set2 Set2 Set2 Set2 Set1 Set1 Set1 Set1 Set1 Set2 Set2 Set2 Set2 Set2 U X X U X X U X X U X X f1 X X f2 X X f3 X X X X df dt...

Page 28: ...r Reset input Low High range for Reset input Low High range for Reset input Low High range for Reset input Low High range for blockage input Low High range for blockage input Low High range for blocka...

Reviews: