Camus Hydronics VTech 0080 Installation And Service Manual Download Page 9

 

 


 

Table 1: Clearances From Combustibles 

All Models

 

Top/Rear 

0" 

(0cm) 

Front 

6" 

(15cm) 

Sides 

0" 

(0cm) 

Vent 

1" 

(2.5cm) 

 

Table 2: Recommended Service Clearances 

All Models 

Top 

Right Side 

Left Side 

Back 

Front 

24” (60cm) 

12” (30cm) 

12” (30cm) 

12” (30cm) 

12” (30cm) 

 

Clearances  from  combustible  construction  are  noted  on  the 
appliance  rating  plate.  When  installed  directly  on  combustible 
flooring,  the  appliance  shall  be  installed  on  a  metal  panel 
extending beyond the full width and depth of the appliance by at 
least 3 inches (76.2mm) in any direction. The floor must be strong 
enough to support the full weight of the heater. When placing the 
appliance  be  aware  that  a  minimum  clearance  of  24”  (60cm) 
must be  provided  at the  front to  allow  easy  access  to  the  heat 
exchanger.

 

A service clearance of 24” must be provided above 

the  top  panel  to  allow  access  to  the  burner.  Maintain  specified 
clearances  for  adequate  operation.  All  installations  must  allow 
sufficient  space  for  servicing  the  vent  connections,  water  pipe 

connections, circulating pump, bypass piping and other auxiliary 
equipment, as well as the appliance. 

2.5 

– Condensate Removal and Treatment

 

This  high  efficiency  appliance  operates  in  a  condensing  mode 
due  to  the  low  temperatures  of  incoming  water  supply. 
Condensate occurs when the products of combustion are cooled 
below  their  dew  point  in  the  heat  transfer  process.  The  liquid 
condensate  formed  from  this  high  efficiency  heat  transfer 
process is mildly acidic. The condensate will typically have a pH 
ranging from 3.5 to 5.0 as it is discharged from the condensate 
drain  at  the  rear  of  the  appliance.  M

any 

codes  will  require 

neutralization  before  it  can  be  piped  to  a  drain  system. 
Neutralization is recommended with every appliance. 

The  neutralizer  consists  of  an  industrial  grade,  non-corrosive 
reservoir  for  collection  of  the  condensate,  filled  with  a 
consumable  fill  media  that  raises  the  pH  of  the  water.  As  the 
reservoir fills, it provides an extended residency time to neutralize 
the condensate. As the pH number increases in numerical value, 
the relative acidity of the discharge decreases. The neutralized 
condensate may then be discharged into a suitable drain system 
without fear of damaging the drain piping. Condensate must be 
able  to  flow  freely  from  the  appliance.  Condensate  flow  is 
accomplished by gravity, requiring a minimum downward slope 
of 1/4” per foot (21mm/m) to ensure proper flow to the neutralizer 
and/or  a  suitable  drain.  The  neutralizer 

MUST 

always  be 

mounted on the same level or lower than the condensate drain 
at the vent connection. 

The VTech and vent condensate drain requires a trap of some 
kind upstream of the neutralizer, to ensure that flue gas does not 
exit through the drain (this must be provided external of the water 
heater).  Prime  the  trap  with  water  during  commissioning.  Use 
standard  ½"  vinyl,  PVC,  CPVC  or  suitable  hose  to  run  to  floor 
drain.  Neutralizers  may  be  used  in  series  to  raise  pH.  See 
Section  3.1.2  for  more  information  on  proper  drainage  of 
condensate. 

Always check with local codes for specific pH requirements. All 
condensate piping and connections must be easily accessible for 
routine maintenance and inspection. 

2.6 

– Insulation

 

The  VTech  incorporates  a  foam  insulation  around  the  storage 
tank,  underneath  the  outer  shell.  No  additional  insulation  is 
required.  If  additional  insulation  is  used,  it  must  not  extend 
beyond  lower  edge  of  the  top  dome  of  the  water  heater  (i.e.  it 
must not cover any portion of the top of the water heater, which 
could obstruct air flow and restrict serviceability). 

2.7 

– Pump Assembly 

The pump assembly (ships loose with the water heater) needs to 
be  installed  on  all  installations.  The  pump  assembly  can  be 
installed  either  on  right  or  left  side  fof  the  unit  depending  on 
where the water connections are. 

Refer to Appendix B

 on how 

to install the pump assembly.  
Installation of pump assembly would help to reduces the build-up 
of scale, improves efficiency by creating more contact between 
the  heating  surfaces  and  the  water  and  improves  performance 
by equalizing tank temperature.  

Factory warranty does not apply to units with no pump assembly 
installed or improperly installed or operated 

pump assembly

.

 

Summary of Contents for VTech 0080

Page 1: ...one in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department A Qualified insta...

Page 2: ...1...

Page 3: ...trol Valve 16 4 4 Gas Pressure Switches 17 4 4 1 Low Gas Pressure 17 4 4 2 High Gas Pressure 17 4 5 Air Pressure Switches 17 4 5 1 Blocked Flue Switch 17 4 5 2 Low Air Switch 17 4 6 Combustion Air Blo...

Page 4: ...ect all gas and flue connections Installation and service must be performed by CAMUS qualified factory trained service technicians Water heaters are heat producing appliances To avoid damage or injury...

Page 5: ...465 0100 53 27 41 11 3 4 49 1 2 11 1 2 48 41 7 1 4 4 1 2 3 3 2 4 2 1 2 465 0125 66 27 54 11 3 4 62 1 2 11 1 2 61 54 7 1 4 4 1 2 3 3 2 4 2 1 2 520 0150 66 27 54 11 3 4 62 1 2 11 1 2 61 54 7 1 4 4 1 2 3...

Page 6: ...222 840 258 977 317 1200 436 1650 0150 202 765 222 840 251 950 293 1109 365 1382 507 1919 0199 262 992 289 1094 327 1238 383 1450 478 1809 667 2525 0250 303 1147 337 1276 385 1457 456 1726 575 2177 8...

Page 7: ...utomatically Fired Boilers ASME CSD 1 All water heaters conform to the latest edition of the ASME Boiler and Pressure Vessel Code Section II Where required by the authority having jurisdiction the ins...

Page 8: ...ions can be taken to protect the appliance from damage If for any reason the unit is to be shut off where danger of freezing exists the following precautionary measures must be taken Shut off gas supp...

Page 9: ...e As the pH number increases in numerical value the relative acidity of the discharge decreases The neutralized condensate may then be discharged into a suitable drain system without fear of damaging...

Page 10: ...ng of Equipment and Air Supply for Appliances of the CSA B149 1 15 and CSA B149 2 15 installation code or applicable provisions of the local building codes Horizontal runs of vent pipe shall be secure...

Page 11: ...engineer must be used to prevent the extra suction from decreasing the pressure at the breeching If the vent cannot support a negative draft under all conditions and a positive pressure will be develo...

Page 12: ...asonry chimney must NOT be used to vent the products of combustion from a positive pressure appliance or any condensing appliances whether positive or negative pressure Category II III or IV As the VT...

Page 13: ...the Building US Only If combustion air is drawn from inside the building the mechanical equipment room does not receive air from outside via louvers or vent openings and the water heater is not equipp...

Page 14: ...armful to the water heater but can be unsightly The steam can also cause discoloration on exterior building surfaces Adjacent brick or masonry surfaces should be protected with a rust resistant sheet...

Page 15: ...st be free of contaminants o Incorrect installation and or location of the air inlet cap can allow flue products to be drawn back into the appliance This can result in incomplete combustion and potent...

Page 16: ...c Venting Kits can be ordered to provide venting and combustion air supply through one opening Vent air pipe still limited a maximum 100 equivalent feet 30 5M in length each Horizontal Concentric Vent...

Page 17: ...combustion air inlet to any other appliance 12 15 cm for appliances 100 000 Btuh 30kW 36 91cm for appliances 100 000 Btuh 30kW 9 23 cm for appliances 50 000 Btuh 15kW 12 30cm for appliances 50 000 Btu...

Page 18: ...Use a cold mirror or the flame of a match or candle 6 After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above ret...

Page 19: ...appliance the complete gas train and all connections must be purged of air and tested using soap solution The appliance and its individual gas shut off valve must be disconnected from the supply pipin...

Page 20: ...witch opens during operation the unit will lock out 4 6 Combustion Air Blower The VTech use a modulating air fan to provide combustible air gas mix to the burner and push the products of combustion th...

Page 21: ...r mounting flange provides a flame view port and the mounting point for the hot surface igniter and the flame sensor The hot surface igniter and flame sensor are removable from the burner mounting fla...

Page 22: ...is loop becomes the Point of No Pressure Change since the pressure at this point will remain constant regardless of pump operation In this case always pump away from the expansion tank connection and...

Page 23: ...ctivated Whenever an appliance is supplied with both an auto reset and manual reset high limit always set the auto reset limit 10 F 5 5 C below the manual reset limit to prevent nuisance tripping 5 5...

Page 24: ...ecessary 6 2 Ignition Control All models use the same 120VAC 1PH electrical supply used to power blower to provide voltage for the ignition circuit including the hot surface igniter The VTech operates...

Page 25: ...ON and OFF high limit adjustment pre and post purge time adjustments modulation rate limiting light off firing rate clock adjustment and Celsius or Fahrenheit unit selection The VTech control also of...

Page 26: ...Automatic Reset Codes Description 0 None 29 Burner switch turned OFF 30 Burner switch turned ON 47 Flame rod to ground leakage 49 Abnormal 24Vac voltage 50 Modulation Fault 61 Anti short Cycle 62 Fan...

Page 27: ...y USER TANK TOP Real time water temperature at the top of the tank USER TANK BOTTOM Real time water temperature at the bottom of the tank USER TANK AVG Average water temperature between the top and bo...

Page 28: ...us DIFF OFF Default 2 F Range 0 F to 15 F USER DIFF Defines the range below DIFF OFF to modulate heating output Default 15 F Range 2 F to 60 F 7 4 3 Monitor Menu Menu Description The MONITOR MENU allo...

Page 29: ...ghest recorded temperature at the tank bottom sensor USER TANK T HIGH Highest recorded temperature difference between the tank top and tank bottom sensors 7 4 4 Time Menu Menu Description The TIME MEN...

Page 30: ...takes place Adjustment of the display units to metric is through this menu Level Parameters Adjustable LOGIN ACCESS Used to login to the control at the installer level to have access to more advanced...

Page 31: ...material Material corresponds to stack temperature limits to protect the venting from damage by overheating 1 PVC 149 F 2 CPVC 194 F 3 PPS Polypropylene 230 F 4 SS Stainless Steel AL29 4C 250 F INST F...

Page 32: ...MIN MOD Minimum blower modulation speed as percent of full firing rate Set at factory INST START MOD Blower modulaiton speed at light off Set at factory INST MAX MOD Maximum blower modulation speed as...

Page 33: ...ton This level is restricted to the installer and requires a code to access Default AUTO control decides operaiton based on programmed settings Option OFF force disable Option HAND force enable Level...

Page 34: ...found in the gas train or related components DO NOT operate an appliance with a leak in the gas train valves or related gas piping Do not attempt to fire the unit with insufficient gas supply pressure...

Page 35: ...ntil combustion levels are satisfied Once settings are complete continue to run the machine for at least 5 minutes and record the final combustion data 8 3 3 Flame Monitoring Throughout the combustion...

Page 36: ...wer Annual The combustion air blower should be inspected annually to ensure it is not blocked with dust or debris The fan opening should be inspected for signs of contaminants or any other air restric...

Page 37: ...M FAILURE MODE ANALYSIS Incoming Power Two wires interchanged No effect on safety Live and Neutral wires are interchanged Transformer Tripped The 24Volts and 120 Volts wired are interchanged Transform...

Page 38: ...ottom sensor open Tank Top sensor open Flue sensor open Verify that the sensors are connected Verify that they are wired correctly Measure the resistance of the sensors 10k sensors Replace the sensor...

Page 39: ...re switch Low Gas Pressure Tripped YES Low gas pressure switch C6097A N O set to 3 w c YES Check incoming gas pressure and reset low gas pressure switch NO Turn blocked flue switch set screw 1 2 turns...

Page 40: ...is selected and PVC venting is used the setpoint must be reduced to below 150o F to avoid nuisance flame failures If a setpoint greater than 150o F is required venting with CPVC AL29 4C 316LL or PPE...

Page 41: ...38 Appendix A Electrical Schematics...

Page 42: ...39 Appendix B Parts Exploded View...

Page 43: ...40 Appendix B Controls Figure A Control Board Figure B Front Cover Assembly...

Page 44: ...41 Appendix B Gas Train Figure C Gas Train Figure D Circulator Assembly...

Page 45: ...6 01023 000 x x x x x x x x 9 1 Gas Valve 918 10250 000 x 833 25180 000 x x 833 25178 000 x x x x x x 10 1 1 2 SCH40 Pipe T B E 8 LG x x x x x x 3 4 SCH40 Pipe T B E 7 LG x 1 SCH40 Pipe T B E 6 LG x x...

Page 46: ...000 x 32 1 VT Circulator Piping Assembly 857 04406 001 x x 857 04405 001 x x 857 04404 001 x x x x 857 04403 001 x 33 1 Tank Bottom Sensor 817 04468 000 x 34 1 Tank Top Sensor 817 11088 000 x 35 1 Ven...

Page 47: ...________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ________________...

Page 48: ...heat exchanger is deemed to be repairable by CAMUS the repaired heat exchanger will be returned to the customer and a credit will not be issued Heat Exchanger shall be warranted for 20 years of the a...

Page 49: ...ing boilers as well as a supplier of specialty HVAC products Our service line is open 24 hours 7 days a week The CAMUS CERTIFIED seal assures you that Reliability Efficiency Serviceability are built i...

Reviews: