Camus Hydronics VTech 0080 Installation And Service Manual Download Page 37

 

 

34 
 

CAUTION

 

Never use a pressure washer to clean the burner 

The burner may best be cleaned by immersing the burner port 
area  in  a  solution  of  dishwashing  detergent  and  hot  water. 
Allow the burner to remain in the solution for a short period of 
time to loosen dust, dirt and oil or grease laden contaminants. 
Rinse  the  burner  thoroughly  with  clean  water  to  remove  any 
residue from the detergent cleaner.  The burner should be air 
dried after removal from the cleaning solution and rinsing. 

DO 

NOT 

use chlorine based solvents or cleaning agents. 

9.5 

– Check the Condensate Neutralizer –6 Months 

Neutralizer medium is expected to last approximately three to six 
months depending on the amount of condensate produced.  

  Condensate Produced, USgal/h = [KBtu/h Input / 100] 

In higher temperature systems less condensate will be produced, 
extending the life of the neutralizer media. Media viability can be 
verified with pH test strips (i.e. litmus paper). Replace media as 
needed  to maintain  neutral state  of  discharged  condensate,  as 
required by code. 

9.6 

– Draining and Flushing – Annual 

It  is  recommended  that  the  water  heater  tank  be  drained  and 
flushed  annually  to  reduce  sediment buildup.  The  water heater 

should  be  drained  if  being  shut  down  during  freezing 
temperatures.  

9.7 

– Complete the Service 

 

Update  the  appliance  service  records  immediately  upon 
completing service. 

  Restore electrical power and gas supply to appliance.

 

 

Cycle  unit  and  check  for  proper  operation.  At  minimum  the 
following  parameters  should  be  checked  to  verify  they  fall 
within  acceptable  limits.  Deviation  from  the  readings  made 
during  commissioning  can  also  indicate  a  problem  that  is 
otherwise undetectable. 

o

 Verify  all  combustion  settings,  including  incoming  gas 

pressure, differential air pressure, and 

CO

settings (see 

Section 8).

 

o

 

Visually inspect burner flame to verify combustion.

 

  Confirm proper operation of all safety devices. 

  Check for gas leaks and proper vent operation.  

  Check control settings. 

  Install  top  cover  once  all  checks  and  adjustment  are 

complete. 

 

 

9.8 

– Troubleshooting 

SYMPTOM 

FAILURE MODE 

ANALYSIS 

Incoming Power 

• Two wires interchanged 

• No effect on safety 
• Live and Neutral wires are interchanged. 

Transformer Tripped 

• The 24Volts and 120 Volts 

wired are interchanged 

• Transformer immediately burns out, replace transformer 

Relief Valve 

• System pressure exceeds 

relief valve setting 

• Replace the standard relief valve with a higher rated valve up to the maximum 

pressure of the heat exchanger. 

• Improperly sized expansion tank. 

Low Water Cut-Off 

• LWCO contacts are open 

• Verify for closed valves or obstructions in water heater piping 
• Verify that all air has been purged from the system 
• Verify that wiring is correct 

Stack Temperature 

Limit Trips 

• Stack temperature has 

exceeded the limit set on 
the water heater. 

• Error: FLUE MAX  

• PVC: Reduce desired setpoint to less than 140

o

F. 

• Measure the resistance of the flue sensor at room temperature, it should be 

approximately 10kΩ. 

• PVC: 149

o

• CPVC: 194

o

• PPE: 230

o

• Stainless Steel, AL29-4C: 250

o

Blocked Flue Switch 

• 

Error: FLUE OPEN

 

• Blocked flue switch wire(s) is/are loose 
• Blocked flue switch is set too light if it trips at full fan speed, reduce sensitivity by 

turning screw 1 turn clockwise. 

Fan Not Turning 

• Fan refuses to rotate 
• 

Error: BLOW SPD

 

• Check fan power wires 
• Fan signal wires are interchanged 
• Minimum fan speed must be greater than 10% 

Flame Disappears 

During a Run Cycle 

(Pressing the manual 
OK button on the 
VTech Control Panel to 
restart the ignition 
sequence)

 

• The VTech water heater 

was running and flame 
signal suddenly 
disappeared. 

• Verify that all air has been purged from gas line 
• Inspect hot surface igniter and related wiring for damage and connection errors. 
• Inspect flame sensor and associated wiring. Replace if necessary 
• Verify that water heater is properly grounded 
• Verify incoming gas supply pressure and that it coincides with Table 9. 
• Verify that the gas line connections to the water heater are adequate 
• Verify that the vent/ air inlet piping (if equipped) are correctly installed and 

obstructions are not present 

• Verify that 24 VAC is being supplied to the gas valve during ignition. If a signal 

cannot be detected, the transformer needs to be replaced 

• Inspect the burner. Refer to Burner Maintenance in section 9.7 
• Replace the VTech Controller if necessary 

Summary of Contents for VTech 0080

Page 1: ...one in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department A Qualified insta...

Page 2: ...1...

Page 3: ...trol Valve 16 4 4 Gas Pressure Switches 17 4 4 1 Low Gas Pressure 17 4 4 2 High Gas Pressure 17 4 5 Air Pressure Switches 17 4 5 1 Blocked Flue Switch 17 4 5 2 Low Air Switch 17 4 6 Combustion Air Blo...

Page 4: ...ect all gas and flue connections Installation and service must be performed by CAMUS qualified factory trained service technicians Water heaters are heat producing appliances To avoid damage or injury...

Page 5: ...465 0100 53 27 41 11 3 4 49 1 2 11 1 2 48 41 7 1 4 4 1 2 3 3 2 4 2 1 2 465 0125 66 27 54 11 3 4 62 1 2 11 1 2 61 54 7 1 4 4 1 2 3 3 2 4 2 1 2 520 0150 66 27 54 11 3 4 62 1 2 11 1 2 61 54 7 1 4 4 1 2 3...

Page 6: ...222 840 258 977 317 1200 436 1650 0150 202 765 222 840 251 950 293 1109 365 1382 507 1919 0199 262 992 289 1094 327 1238 383 1450 478 1809 667 2525 0250 303 1147 337 1276 385 1457 456 1726 575 2177 8...

Page 7: ...utomatically Fired Boilers ASME CSD 1 All water heaters conform to the latest edition of the ASME Boiler and Pressure Vessel Code Section II Where required by the authority having jurisdiction the ins...

Page 8: ...ions can be taken to protect the appliance from damage If for any reason the unit is to be shut off where danger of freezing exists the following precautionary measures must be taken Shut off gas supp...

Page 9: ...e As the pH number increases in numerical value the relative acidity of the discharge decreases The neutralized condensate may then be discharged into a suitable drain system without fear of damaging...

Page 10: ...ng of Equipment and Air Supply for Appliances of the CSA B149 1 15 and CSA B149 2 15 installation code or applicable provisions of the local building codes Horizontal runs of vent pipe shall be secure...

Page 11: ...engineer must be used to prevent the extra suction from decreasing the pressure at the breeching If the vent cannot support a negative draft under all conditions and a positive pressure will be develo...

Page 12: ...asonry chimney must NOT be used to vent the products of combustion from a positive pressure appliance or any condensing appliances whether positive or negative pressure Category II III or IV As the VT...

Page 13: ...the Building US Only If combustion air is drawn from inside the building the mechanical equipment room does not receive air from outside via louvers or vent openings and the water heater is not equipp...

Page 14: ...armful to the water heater but can be unsightly The steam can also cause discoloration on exterior building surfaces Adjacent brick or masonry surfaces should be protected with a rust resistant sheet...

Page 15: ...st be free of contaminants o Incorrect installation and or location of the air inlet cap can allow flue products to be drawn back into the appliance This can result in incomplete combustion and potent...

Page 16: ...c Venting Kits can be ordered to provide venting and combustion air supply through one opening Vent air pipe still limited a maximum 100 equivalent feet 30 5M in length each Horizontal Concentric Vent...

Page 17: ...combustion air inlet to any other appliance 12 15 cm for appliances 100 000 Btuh 30kW 36 91cm for appliances 100 000 Btuh 30kW 9 23 cm for appliances 50 000 Btuh 15kW 12 30cm for appliances 50 000 Btu...

Page 18: ...Use a cold mirror or the flame of a match or candle 6 After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above ret...

Page 19: ...appliance the complete gas train and all connections must be purged of air and tested using soap solution The appliance and its individual gas shut off valve must be disconnected from the supply pipin...

Page 20: ...witch opens during operation the unit will lock out 4 6 Combustion Air Blower The VTech use a modulating air fan to provide combustible air gas mix to the burner and push the products of combustion th...

Page 21: ...r mounting flange provides a flame view port and the mounting point for the hot surface igniter and the flame sensor The hot surface igniter and flame sensor are removable from the burner mounting fla...

Page 22: ...is loop becomes the Point of No Pressure Change since the pressure at this point will remain constant regardless of pump operation In this case always pump away from the expansion tank connection and...

Page 23: ...ctivated Whenever an appliance is supplied with both an auto reset and manual reset high limit always set the auto reset limit 10 F 5 5 C below the manual reset limit to prevent nuisance tripping 5 5...

Page 24: ...ecessary 6 2 Ignition Control All models use the same 120VAC 1PH electrical supply used to power blower to provide voltage for the ignition circuit including the hot surface igniter The VTech operates...

Page 25: ...ON and OFF high limit adjustment pre and post purge time adjustments modulation rate limiting light off firing rate clock adjustment and Celsius or Fahrenheit unit selection The VTech control also of...

Page 26: ...Automatic Reset Codes Description 0 None 29 Burner switch turned OFF 30 Burner switch turned ON 47 Flame rod to ground leakage 49 Abnormal 24Vac voltage 50 Modulation Fault 61 Anti short Cycle 62 Fan...

Page 27: ...y USER TANK TOP Real time water temperature at the top of the tank USER TANK BOTTOM Real time water temperature at the bottom of the tank USER TANK AVG Average water temperature between the top and bo...

Page 28: ...us DIFF OFF Default 2 F Range 0 F to 15 F USER DIFF Defines the range below DIFF OFF to modulate heating output Default 15 F Range 2 F to 60 F 7 4 3 Monitor Menu Menu Description The MONITOR MENU allo...

Page 29: ...ghest recorded temperature at the tank bottom sensor USER TANK T HIGH Highest recorded temperature difference between the tank top and tank bottom sensors 7 4 4 Time Menu Menu Description The TIME MEN...

Page 30: ...takes place Adjustment of the display units to metric is through this menu Level Parameters Adjustable LOGIN ACCESS Used to login to the control at the installer level to have access to more advanced...

Page 31: ...material Material corresponds to stack temperature limits to protect the venting from damage by overheating 1 PVC 149 F 2 CPVC 194 F 3 PPS Polypropylene 230 F 4 SS Stainless Steel AL29 4C 250 F INST F...

Page 32: ...MIN MOD Minimum blower modulation speed as percent of full firing rate Set at factory INST START MOD Blower modulaiton speed at light off Set at factory INST MAX MOD Maximum blower modulation speed as...

Page 33: ...ton This level is restricted to the installer and requires a code to access Default AUTO control decides operaiton based on programmed settings Option OFF force disable Option HAND force enable Level...

Page 34: ...found in the gas train or related components DO NOT operate an appliance with a leak in the gas train valves or related gas piping Do not attempt to fire the unit with insufficient gas supply pressure...

Page 35: ...ntil combustion levels are satisfied Once settings are complete continue to run the machine for at least 5 minutes and record the final combustion data 8 3 3 Flame Monitoring Throughout the combustion...

Page 36: ...wer Annual The combustion air blower should be inspected annually to ensure it is not blocked with dust or debris The fan opening should be inspected for signs of contaminants or any other air restric...

Page 37: ...M FAILURE MODE ANALYSIS Incoming Power Two wires interchanged No effect on safety Live and Neutral wires are interchanged Transformer Tripped The 24Volts and 120 Volts wired are interchanged Transform...

Page 38: ...ottom sensor open Tank Top sensor open Flue sensor open Verify that the sensors are connected Verify that they are wired correctly Measure the resistance of the sensors 10k sensors Replace the sensor...

Page 39: ...re switch Low Gas Pressure Tripped YES Low gas pressure switch C6097A N O set to 3 w c YES Check incoming gas pressure and reset low gas pressure switch NO Turn blocked flue switch set screw 1 2 turns...

Page 40: ...is selected and PVC venting is used the setpoint must be reduced to below 150o F to avoid nuisance flame failures If a setpoint greater than 150o F is required venting with CPVC AL29 4C 316LL or PPE...

Page 41: ...38 Appendix A Electrical Schematics...

Page 42: ...39 Appendix B Parts Exploded View...

Page 43: ...40 Appendix B Controls Figure A Control Board Figure B Front Cover Assembly...

Page 44: ...41 Appendix B Gas Train Figure C Gas Train Figure D Circulator Assembly...

Page 45: ...6 01023 000 x x x x x x x x 9 1 Gas Valve 918 10250 000 x 833 25180 000 x x 833 25178 000 x x x x x x 10 1 1 2 SCH40 Pipe T B E 8 LG x x x x x x 3 4 SCH40 Pipe T B E 7 LG x 1 SCH40 Pipe T B E 6 LG x x...

Page 46: ...000 x 32 1 VT Circulator Piping Assembly 857 04406 001 x x 857 04405 001 x x 857 04404 001 x x x x 857 04403 001 x 33 1 Tank Bottom Sensor 817 04468 000 x 34 1 Tank Top Sensor 817 11088 000 x 35 1 Ven...

Page 47: ...________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ________________...

Page 48: ...heat exchanger is deemed to be repairable by CAMUS the repaired heat exchanger will be returned to the customer and a credit will not be issued Heat Exchanger shall be warranted for 20 years of the a...

Page 49: ...ing boilers as well as a supplier of specialty HVAC products Our service line is open 24 hours 7 days a week The CAMUS CERTIFIED seal assures you that Reliability Efficiency Serviceability are built i...

Reviews: