25
7.4.2
– Setup Menu
Menu Description
The
SETUP MENU
allows adjustment of basic operating parameters. The
setpoint is adjustable to the user at this level.
Level
Parameters - Adjustable
USER
SETPOINT
–
This is the desired setpoint.
Default
–
140°F
Range
–
70°F to 190°F
USER
DIFF ON
–
Used to activate the unit if the TANK TOP temperature drops to
the setpoint minus DIFF ON.
Default
–
5°F
Range
–
0°F to 15°F
USER
DIFF OFF
– Used to de-activate the unit if the TANK TOP temperature
reaches the setpoint minus DIFF OFF.
Default
–
2°F
Range
–
0°F to 15°F
USER
DIFF
– Defines the range below DIFF OFF to modulate heating output.
Default
–
15°F
Range
–
2°F to 60°F
7.4.3
– Monitor Menu
Menu Description
The
MONITOR MENU
allows viewing of more detailed operaitonal data than
the
VIEW MENU
. This menu will also record historical data for later
reference. Press
CLEAR
for three (3) seconds to clear any of these
parameters. This level is accessible to the user.
Level
Parameters - Read-Only
USER
BURNER RUN TIME
–
Burner operaitonal time as recorded in hours.
USER
CYCLES
–
Number of operating cycles on the appliance.
tank
140
SETPOINT
SETUP
MENU
DIFF OFF
tank
40
TANK DIFF
tank
10
tank
DIFF ON
50
MONITOR
MENU
CYCLES
0
BURNER