Modulation: System Sensor, Outdoor Reset Operation (Standalone)
NOTE: Outdoor Reset Module (PN: W8735S1000) required.
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates with variable
setpoint determined by
outdoor reset curve
•
Modulates on system sensor
•
Heat demand is generated
when Remote Operator is
closed.
1)
Connect Remote Operator
2)
Connect System sensor to System/Outdoor
contacts
3)
Connect Outdoor Sensor to J3 ECOM connector
4)
Place both toggle switches in
LOCAL
5)
Press
and
6)
Press
Outdoor Reset Configuration
7)
Press the to arrive at
Central Heat
8)
Select
Enable: Enable
9)
Select
Maximum outdoor temperature
(WWSD)
10)
Select
Minimum outdoor temperature
(Outdoor
Design)
11)
Select
Low Water Temperature
(Min. Water
Temp.)
12)
Select
Outdoor boost maximum off point
(Design Max.)