5
1.10
INSTALLATION PROCEDURE AND
LOCATION OF UNIT
Install this appliance in a clean, dry location with adequate
air supply.
•
Do not locate this appliance in an area where it will
be subject to freezing unless precautions are
taken. Radiant losses from the Dynaforce® are
minimal and should not be relied on to keep the
appliance room warm.
•
The appliance should be located close to a floor
drain in an area where leakage from the appliance
or connections will not result in damage to the
adjacent area or to lower floors in the structure,
it
is recommended that a suitable drain pan,
adequately drained, be installed under the unit.
Under no circumstances is the manufacturer to be
held responsible for water damage in connection
with this unit, or any of its components.
•
If the appliance is installed above the level of the
building’s radiation system, a low water cut-off
device must be installed above the heat
exchanger inlet/outlet connections.
Some local
codes require the installation of a low water cut-off
on all systems
•
When placing the appliance be aware that a
minimum clearance of 24” must be provided at the
front to allow easy access to the heat exchanger.
•
A service clearance of 24” must be provided
above the top panel to allow access to the burner.
•
The appliance must be installed so that the ignition
system components are protected from water
(dripping,
spraying,
etc.)
during
appliance
operation and service (circulator replacement,
control replacement, etc.)
•
Appliances located in a residential garage and in
adjacent spaces that open to the garage and are
not part of the living space of a dwelling unit must
be installed so that all burners and burner ignition
devices have a minimum clearance of not less
than 18" (46cm) above the floor. The appliance
must be located or protected so that it is not
subject to physical damage by a moving vehicle.
•
DO NOT install this appliance in any location
where
gasoline or flammable vapors are likely to
be present.
•
DO NOT install this appliance on top of carpet
flooring
•
Appliance must be installed on a level floor.
Maintain required clearances from combustible
surfaces.
•
The appliance designed for indoor installation
(Indoor Models) must be installed indoors where it
is protected from exposure to wind, rain and
weather.
•
The appliance designed for outdoor installation
(Outdoor Models) must be installed outdoors. For
outdoor installations, always consider the use of a
shelter such as a garden shed in lieu of direct
exposure of the appliance to the elements. The
additional protection afforded by the shelter will
help to minimize nuisance problems with electrical
connections and will allow easier servicing of the
appliance under severe weather conditions.
Summary of Contents for DRH300
Page 2: ......
Page 6: ......
Page 38: ...32 13 Place toggle switch setting to REMOTE for remote operation if required...
Page 69: ...63 PART 12 EXPLODED VIEW 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20...
Page 70: ...64 21 22 23 24 26 35 34 33 32 31 30 29 28 27 25 36 37 38 39 40 42 43 56...
Page 77: ...71 PART 13 ELECTRICAL DIAGRAMS...
Page 78: ...72...
Page 79: ...73...
Page 81: ...75...
Page 82: ...76...
Page 83: ...77...
Page 86: ......