Section 5. Programming the Datalogger
5-10
Third Value Returned
Framing errors
| | Overrun errors
| | | |
x x x x
Framing errors is a count from 0-99. This count shows how many times there
has been a receive error, caused by a character corruption or incorrect set-up.
Overrun errors is a count from 0-99. This count shows how many times
characters have been lost due to data being sent too quickly for the SDM-SIO4
to process the data.
Fourth Value Returned
NOT USED - SET TO ZERO
| | Line break errors
| | | |
x x x x
Line break errors is a count from 0-99. This count shows how many times the
line has been broken or disconnected.
First Command Option — Reset Error Counters
When command 1026 is specified in parameter 4 of Instruction 113, this
additional option can be used (parameter 5 of Instruction 113) to force the error
counters to be reset to zero.
This means that command 1026 requests data
from
the SDM-SIO4 and can also
be used to send these reset commands
to
the SDM-SIO4.
The command to reset the error counters has no effect on a port if
the command line is active.
Break reset
| Framing reset
| | Overrun reset
| | | Parity reset
| | | |
x x x x
Break reset:
0
Do nothing
1
Reset line break count to zero
Framing reset:
0
Do nothing
1
Reset framing error count to zero
Overrun reset:
0
Do nothing
1
Reset overrun error count to zero
NOTE
Summary of Contents for SDM-SIO4
Page 6: ...SDM SIO4 Table of Contents iv This is a blank page ...
Page 12: ...Section 1 Introduction 1 6 This is a blank page ...
Page 16: ...Section 2 Installation and Hardware Set Up 2 4 This is a blank page ...
Page 26: ...Section 3 Understanding How the SDM SIO4 Handles Data 3 10 This is a blank page ...
Page 32: ...Section 4 Programming the SDM SIO4 4 6 This is a blank page ...
Page 62: ...Section 5 Programming the Datalogger 5 30 This is a blank page ...
Page 76: ...This is a blank page ...
Page 81: ...This is a blank page ...