Section 5. Programming the Datalogger
5-19
*Table 1 Program
01: 2
Execution Interval (seconds)
;set up the filter and then send string 101.
1: SDM-SIO4 (P113)
1:
1
Reps
2:
0
Address
3:
1
Send/Receive Port 1
4:
2304
Command
5:
8101
1st Parameters
6:
1999
2nd Parameters
7:
0
Values per Rep
8:
0
Loc [ ]
9:
1.0
Mult
10: 0.0
Offset
;wait long enough for sensor to send data.
2: Excitation with Delay (P22)
1:
1
Ex Channel
2:
0
Delay W/Ex (units = 0.01 sec)
3:
4
Delay After Ex (units = 0.01 sec)
4:
0
mV Excitation
;get data from SDM-SIO4 and put into locations 1 and 2.
3: SDM-SIO4 (P113)
1:
1
Reps
2:
0
Address
3:
1
Send/Receive Port 1
4:
4
Command
5:
0
1st Parameters
6:
0
2nd Parameters
7:
2
Values per Rep
8:
1
Loc [ number ]
9:
1.0
Mult
10: 0.0
Offset
;At zero minutes into a 10 minute interval set the output
;so that the data from the sensor will be stored into
;final storage.
4: If time is (P92)
1:
0
Minutes (Seconds --) into a
2:
10
Interval (same units as above)
3:
10
Set Output Flag High (Flag 0)
;Time stamp.
5: Real Time (P77)
1:
1110
Year,Day,Hour/Minute
Summary of Contents for SDM-SIO4
Page 6: ...SDM SIO4 Table of Contents iv This is a blank page ...
Page 12: ...Section 1 Introduction 1 6 This is a blank page ...
Page 16: ...Section 2 Installation and Hardware Set Up 2 4 This is a blank page ...
Page 26: ...Section 3 Understanding How the SDM SIO4 Handles Data 3 10 This is a blank page ...
Page 32: ...Section 4 Programming the SDM SIO4 4 6 This is a blank page ...
Page 62: ...Section 5 Programming the Datalogger 5 30 This is a blank page ...
Page 76: ...This is a blank page ...
Page 81: ...This is a blank page ...