NL200/201 Network Link Interface
14
o
Set
SDC address
. (Note that if multiple peripherals are connected to
a datalogger’s CS I/O port, each must have a unique SDC address.)
o
Set
Beacon Interval
and
Verify Interval
as described above. Often
the default values can be used.
x
On the Network Services tab:
o
Make note of the
PakBus\TCP Server Port
. (The default
PakBus/TCP Server Port
is 6785. Unless firewall issues exist, it is
not necessary to change the port from its default value.)
7.1.3
LoggerNet
Setup
x
In the
LoggerNet Setup
screen, press
Add Root
and choose
IPPort
. Input
the NL200/201’s IP address and port number. The IP address and port
number are input on the same line separated by a colon.
x
Add a PakBus® Port (PakBusPort).
x
Add a PakBus® Router (pbRouter). Input the PakBus address of the
NL200/201. The NL200/201’s default PakBus address is 678.
x
Add the datalogger and input the PakBus® address of the datalogger.
x
Press
Apply
to save the changes.
FIGURE 7-1. PakBus® router LoggerNet setup