Operation and maintenance instructions
CPU PROFINET Series CX06 module
5000004825
Versione 01
47
With a double click on the object you access to its properties and on the right side of the
screen are displayed the modules that are used to configure the node. The various input and
output modules can be dragged in the appropriate section until forming the desired data
size. There are no specific limitations on the order in which the modules are placed in the
configuration. The only constraint to be respected is the maximum number of bytes: 128 for
inputs and outputs. The user must calculate the minimum size of the data necessary for the
functioning of CX06 node and the modules connected to it. The information regarding the
size of the data occupied by the individual modules and their meaning (correspondence
between bits and input / physical output) are contained in the manual "
Operating and
Maintenance Instructions - Bus System Internal Camozzi
".
Furthermore the
CX-Configurator
software calculates automatically the size of the data used
by the CX06 node and by the modules connected to it. For more details on using the
configurator and in particular of this feature, refer to the manual "
Operating and
Maintenance Instructions - CX Configurator
".
The PLC recognizes the different nodes connected to the network through the node name
and then assigns them all the necessary parameters to the Ethernet communication
(address, gateway, and subnet mask). The default values of these parameters are as follows:
Name: empty
IP Address: 0.0.0.0
Gateway: 0.0.0.0
Subnet mask: 255.255.255.0