Operation and maintenance instructions
CPU PROFINET Series CX06 module
5000004825
Versione 01
37
This illustrates the pins of the M12 connector located on the upper section CPU module:
POWER Connector M12A 5 poles male
Pin Signal
Description
1
L24V
24Vdc power supply (logic, digital input, analog I/O): connect to the
positive pole of the 24Vdc power supply (ref.
GND)
.
2
P24V
24Vdc power supply (digital output): connect to the positive pole of the
24Vdc power supply (ref.
GND)
.
3
GND
Common (reference pin 1 and 2): connect to the negative pole of the
24Vdc power supply (compulsory).
4
EARTH
Earth connection
5
NC
Not connected
BUS IN Connector M12D 4 poles Female
Pin Signal
Description
1
TD+
Transmit data +
2
RD+
Receive data +
3
TD-
Transmit data -
4
RD-
Receive data -
BUS OUT Connector M12D 4 poles Female
Pin Signal
Description
1
TD+
Transmit data +
2
RD+
Receive data +
3
TD-
Transmit data -
4
RD-
Receive data -
For electrical connection are available the following wired connectors.
CONNECTOR
CODE
DESCRPTION
POWER
CS-LF04HB
Power supply straight connector
CS-LR04HB
Power supply angled connector
BUS IN
BUS OUT
CS-SM04H0
Bus-In and Bus-OUT straight M12 male connector
CS-SB04HB-D100
CS-SB04HB-D500
CS-SB04HB-DA00
Straight moulded cable
CS-SC04HB-D100
CS-SC04HB-D500
CS-SC04HB-DA00
Angled moulded cable