Electrical control panel
for 1 drainage pump
with single-phase motor
QMLD 1D 12A-FA
OPERATING INSTRUCTIONS
Index
1.
Types
2.
Operating conditions
3.
Components
3.1.
DR 1000 electronic card
3.1.1. Settings of the DR 1000 electronic card
4.
Installation
5.
Electrical connection
5.1.
Capacitor connection
5.2.
Motor connection
5.3.
Float switches connections
5.3.1. 2 float switches connections
5.3.2. 3 float switches connections
5.4.
Control panel for remote alarm connections
6.
Amperometric protection setting
7.
Operating
7.1.
Operating with 2 float switches
7.2.
Operating with 3 float switches
8.
Motors with thermal protector
8.1.
Motors with thermal protector without
external signals
8.2.
Motors without thermal protector
9.
Control panels for remote alarm
10.
Outside of box cover
11.
Inside of the box
12
Declaration of conformity
1. Types
Type
Setting
QMLD 1D 12A-FA
1 ÷ 12 A
2. Operating conditions
- Mains:
230V 1~ ±10% 50/60 Hz
(other voltages on request).
- Ambient temperature from -5 +40 °C.
- Protection IP 55.
- Dimensions 255x200x205 mm.
- Weight: kg 1,5.
3. Components
Standard construction
Control panel with protection for one submersible
drainage pump with single-phase motor, with a
12A max. nominal current.
Possibility of installing one capacitor inside the
control panel, for pump without capacitor inside
the motor.
Functions managed by a DR 1000 type electronic
card with microprocessor.
Components
- Box in thermoplastic material.
- Line selector switch with door-locking device.
- Power line fuses.
- Auxiliary circuit fuses.
- Starting-up relay.
- Amperometric transformer.
- Capacitor (on request).
- DR
1000
type
electronic
card
with
microprocessor.
- Terminals for capacitor connection.
- Terminals for float switches connection.
- Terminals for connection of remote alarm control
panel RA 100E, RA 100A type.
- Cable glands.
3.1. DR 1000 electronic card
The functioning of the pump is managed by the
DR1000 electronic card that incorporates the
following functions:
- automatic functioning test of the pump every 48
hours of inactivity (with pump in the automatic
functioning mode).
- Pump control with signals coming from:
-
2 float switches:
one for starting-up and
stopping pump, one for the alarm maximum
level (optional).
-
3 float switches:
one for starting-up pump,
one for stopping the pump and one for the
alarm maximum level (optional).