I-MAT_Ed2 - Operating Instructions
Page 41 / 136
PC05
Time before stop
(s)
30
PC06
Set-point pressure step up
(bar)
0,3
PC07
Pressure step up ramp
(bar/s)
0,3
PC08
Pressure step up time
(s)
3
PC09
Restart fall pressure set-up
(bar)
0,3
PC10
System dynamic
3
PC11
Pressure PID (proportional gain)
3000
PC12
Pressure PID (integral time constant)
400
PC13
Pressure PID (derivative time constant)
1000
PC14
Cascade mode start fall pressure set-up
(bar)
0,3
PC15
Cascade mode restart delay
(s)
10
PC16
Cascade mode fall pressure limit set-up
(bar)
0,6
16.5. Parameter PP – Proportional pressure settings
N°
Description
Parameter values
Standard Modifications
PP01
Percentage of the pressure with zero flow
(%)
50
PP02
Minimum run frequency proportional
pressure
(Hz)
auto
PP03
Frequency before stop proportional
pressure
(Hz)
auto
PP04
Time before stop
(s)
30
PP05
Set-point pressure step up
(bar)
0,3
PP06
Pressure step up ramp
bar/s
0,3
PP07
Pressure step up time
(s)
3
PP08
Restart fall pressure set-up
(bar)
0,3
PP09
System dynamic
3
PP10
Pressure PID (proportional gain)
3000
PP11
Pressure PID (integral time constant)
400
PP12
Pressure PID (derivative time constant)
1000
PP13
Cascade mode start fall pressure set-up
(bar)
0,3
PP14
Cascade mode restart delay
(s)
10
PP15
Cascade mode fall pressure limit set-up
(bar)
0,6
16.6. Parameter tC – Constant temperature setting
N°
Description
Parameter values
Standard Modifications
tC01
System type
HEAt
COOL
HEAt
COOL
tC02
Restart temperature
(°C)
10
tC03
System dynamic
3
tC04
Temperature PID (proportional gain)
3000
tC05
Temperature PID (integral time constant)
400
tC06
Temperature PID (derivative time constant)
1000
tC07
Set-point time limit
(s)
60
16.7. Parameter CF – Constant flow rate settings
N°
Description
Parameter values
Standard Modifications
CF01
Flow rate PID (proportional gain)
3000
CF02
Flow rate PID (integral time constant)
400
CF03
Flow rate PID (derivative time constant)
1000
CF04
Dry-run detection percentage
(%)
95
CF05
Dry-run time limit
(s)
60
16.8. Parameter MAn – Fixed speed pump settings
N°
Description
Parameter values
Standard Modifications
MAn1
Primary fixed speed operating frequency
(Hz)
45
MAn2
Secondary fixed speed operating frequency (Hz)
45
MAn3
Remote control activation
On, OFF
Off
MAn4
Minimum value for remote control
(Hz)
30
Summary of Contents for IMAT
Page 17: ...IT I MAT_Ed2 Istruzioni originali Pagina 17 136 16 Elenco parametri di programmazione...
Page 38: ...GB Page 38 136 I MAT_Ed2 Operating Instructions 16 Parameter table list...
Page 59: ...D I MAT_Ed2 Betriebsanleitung Seite 59 136 16 Verzeichnis Programmierungsparameter...
Page 101: ...E I MAT_Ed2 Instrucciones de uso P gina 101 136 16 Lista par metros de programaci n...
Page 109: ...RU I MAT_Ed2 C 109 136 3 4 3 5 ENTER 3 6 20 3 7 3 8 5 19 30 50 50 30 60 60 0 30 30 0...
Page 110: ...RU C 110 136 I MAT_Ed2 4 4 1 10 4 2 4 3 4 4 5 X 5 1 25 X 6 6 1 i 6 2 20 1 1 6 3 20 1 2...
Page 122: ...RU C 122 136 I MAT_Ed2 16...