background image

5

• A minimum of two (2) warning signs shall be installed, one on each side of the gate where easily

visible.

• The gate must have sufficient room when opening and closing. Swinging gates should open

inwards and not into public access areas. The gate must be properly installed and move freely in

both directions.

• Install the gate operator only when: 1) The operator is appropriate for the construction of the gate

and the usage Class of the gate, 2) All openings of a horizontal slide gate are guarded or screened

from the bottom of the gate to a minimum of 4 feet (1.2 m) above the ground to prevent a 2-1/4

inch (57.15 mm) diameter sphere from passing through the openings anywhere in the gate, and in

that portion of the adjacent fence that the gate covers in the open position, 3) All exposed pinch

points are eliminated or guarded, and 4) Guarding is supplied for exposed rollers, could be UL

approved

• The gate must be properly installed and work freely in both directions prior to the installation of

the gate operator. Do not over-tighten the operator clutch or pressure relief valve to compensate

for a damaged gate.

• For gate operators utilizing Type d protection: 1) The gate operator controls must be placed so that

the user has full view of the gate area when the gate is moving, 2) The placard as required by

52.1.1.6 shall be placed adjacent to the controls, 3) An automatic closing device (such as a timer,

loop sensor, or similar device) shall not be employed, and 4) No other activation device shall be

connected.

• Controls must be far enough from the gate (at least six feet) so that the user is prevented from

coming in contact with the gate while operating the controls. Controls intended to be used to reset

an operator after 2 sequential activations of the entrapment protection device or devices must be

located in the line-of-sight of the gate. Outdoor or easily accessible controls shall have a security

feature to prevent unauthorized use.

• For gate operators utilizing a non-contact sensor in accordance with 30A.1.1: 1) See instructions on

the placement of non-contact sensors for each Type of application, 2) Care shall be exercised to

reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the gate is still

moving, and 3) One or more non-contact sensors shall be located where the risk of entrapment or

obstruction exists, such as the perimeter reachable by a moving gate or barrier.

• For a gate operator utilizing a contact sensor in accordance with 30A.1.1: 1) One or more contact

sensors shall be located at the leading edge, trailing edge, and post mounted both inside and

outside of a vehicular horizontal slide gate. 2) One or more contact sensors shall be located at the

bottom edge of a vehicular vertical lift gate. 3)  One or more contact sensors shall be located at the

pinch point of a vehicular vertical pivot gate. 4) A hardwired contact sensor shall be located and its

wiring arranged so that the communication between the sensor and the gate operator is not

subjected to mechanical damage. 5) A wireless contact sensor such as one that transmits radio

frequency (RF) signals to the gate operator for entrapment protection functions shall be located

where the transmission of the signals are not obstructed or impeded by building structures, natural

landscaping or similar obstruction. A wireless contact sensor shall function under the intended end-

use conditions.

Requirements for UL Compliant Installation

Summary of Contents for CM6

Page 1: ...Installation and Owner s Manual Access Control Systems www calimetco com 9949 Hayward Way South El Monte CA 91733 Tel 626 452 9009 Ver 3 0 2022 03 18 Swing Gate Operator CM6 CM6 ACFP CM6 DCFP...

Page 2: ...Install Warning Signs 19 After installation 20 Dual Gate Setup 21 Emergency Release 22 Dip Switch Features 23 Circuit Board Layout 24 25 Remote Controls 26 Exit Loops 27 28 Accessory Wiring 29 Locks...

Page 3: ...0 Amp Fuse 24V DC 15 Amp 16 5 x 20 x 24 L x W x H Swing Residential Commercial 1000 lbs 18 Feet 4 F to 140 F Approximately 20 sec for 90 opening Continuous Inherent Reverse Sensor System Type A Photoe...

Page 4: ...t re test the gate operator Failure to maintain the gate operator properly can increase the risk of injury or death Use the emergency release only when the gate is not moving Keep the gate properly ma...

Page 5: ...using Slide Gates Primary Device A Secondary Device one required B1 B2 D Swing Gates Primary Device A C Secondary Device one required A B1 B2 C D Class III Industrial Locations Limited Access Vehicula...

Page 6: ...with the gate while operating the controls Controls intended to be used to reset an operator after 2 sequential activations of the entrapment protection device or devices must be located in the line o...

Page 7: ...gate during the entire path of travel of the vehicular gate The Stop and or Reset button must be located in the line of sight of the gate Activation of the reset control shall not cause the operator t...

Page 8: ...uthorized use of the gate Vehicular gates should be constructed and installed in accordance with the ASTM F2200 construction standards Electricity The CM6 is powered by 110V 120V AC power If you have...

Page 9: ...rt of the swivel arm D Length of D E 60 The length of D is 60 of E Arm should be 90 from gate when open and straight when closed Distance from the swivel arm nut to the center of the gate bracket Note...

Page 10: ...onduit 3 Pour the concrete pad 4 Use 4 wedge anchors 1 2 to secure the gate operator to the concrete Figure A Above Ground 4 Below Ground Underground depth may vary due to local building codes Reinfor...

Page 11: ...2 20 11 5 2 Install the swivel arm in accordance to the measurements below Compact Installation 31 5 Install using compact installation ONLY when the space between the OPEN gate and wall is between 2...

Page 12: ...igure A A DO NOT allow the arm to touch the gate operator s hood when the gate is in the open position Figure 8 Swivel arm is incorrectly bent Swivel arm must be straight Swivel Arm Positioning Tips 1...

Page 13: ...u re satisfied with testing the arm in the full open and closed positions weld the following 1 Short arm to gate opener metal bar 2 Gate bracket to gate 3 Gate bracket to long arm Step 3 Weld the Door...

Page 14: ...onnect the white wire to the white wire NEUTRAL using a wire nut 5 Connect the black wire to the black wire HOT LINE using a wire nut 6 All operators MUST be properly grounded in order to prevent an e...

Page 15: ...tch 6 Figure A on the bottom of the gate operator circuit board controls the open direction ON opens to the right OFF opens to the left Clockwise Opens to the right Set dip switch 6 to ON Counter Cloc...

Page 16: ...lector to the opposite side Make sure the alignment laser hits inside the circle of the reflector Figure A Figure B 6 Press the orange button on the photocell sensor to turn off the alignment laser Im...

Page 17: ...tocell sensor Outside Property Swing Gate Swing Gate Inside Property Photocell sensor Reflector Secondary Photocell Sensor Wiring Use the same green terminal block input as your primary photocell sens...

Page 18: ...se close distance 2 If gate opens to the left counter clockwise The top limit cam controls the close limit Turn the top limit cam counter clockwise to increase close distance Turn the top limit cam cl...

Page 19: ...n Right Clockwise More Force required to stop the gate Recommended for heavier long gates WARNING Never increase force beyond the minimum amount required to move the gate Too much force may seriously...

Page 20: ...be installed directly on the gate or a nearby wall or post Use screws not supplied to install the warning signs WARNING KEEP CLEAR Gate may move at any time without prior warning Do not let children...

Page 21: ...rator Dual Gate Installation For double gates visit the Dual Gate Setup page for more installation instructions HomeLink Most modern cars come with a feature called Homelink that lets you open your ga...

Page 22: ...oard Figure 2 Use a flathead screwdriver to release the 2 locks on the top of the green terminal 5 Using the electrical wire connect the DATA on the primary gate opener to the DATA on the secondary ga...

Page 23: ...n finished step on the pedal and move it back to the top left Figure B Figure C Emergency Release Right side The emergency release is pressed down allowing you to manually push open the gate Figure B...

Page 24: ...gate operator only set the 5 SLAVE switch to ON If single gate installation set to OFF Gate Open Direction set the direction of which the gate opens when viewed from inside the property Left or Right...

Page 25: ...er Knob 6 Auto Close Timer Knob 7 Open and Close ERD Knob 8 Open Close Stop Reset Buttons 9 Plug in Loop Detetcor Input 10 Electric Lock Input 11 Limit Switch Inputs 12 Loop Detectors Wire Input 13 Co...

Page 26: ...lectric Lock Input 11 Loop Wire for Loop Detectors 12 Open Close Limit Relay 13 Loop Detector Wire Relay Inputs 14 Common Global Input 15 Strobe Light Relay 16 Alarm Relay 17 Master Slave Dual Gate Re...

Page 27: ...his gate operator can add up to 50 different remote controls To add more than 50 remote controls add a receiver which can add up to 100 additional remote controls Calimet remote controls use 418 MHz f...

Page 28: ...exit loop is a device that opens the gate automatically when a car approaches the gate A reverse loop is a loop that reverses the direction of the gate if a car drives over it It will also hold a gat...

Page 29: ...installed in the brackets below figure A The loop wires are installed in the LOOPDETECTOR Relay See the loop detector instruction manual for more installation instructions For other brand exit loops...

Page 30: ...ing the gate operator to power the accessory use 24 VDC and the 24V COM input Figure A Exit Loop Terminals Located on the right side of the circuit board Figure B Relay Terminals Located on the outsid...

Page 31: ...glock Normal Open N O Exit Loop Normal Close N C CL Push To Exit Button Normal Open N O Exit Loop Normal Close N C CL If using the gate operator to power the accessory use 24 VDC and the 24V COM input...

Page 32: ...res electricity Keypad For the Calimet CM9 535 Wireless keypad follow the separate keypad instruction manual for installation details For wired and non calimet brand keypads use a 20 gauge stranded el...

Page 33: ...erator Model Solar Compatibility CM6 ACFP not solar compatible CM6 DCFP solar ready CM6 ACFP Not battery compatible CM6 DCFP Included already installed Solar Panel Accessories Battery 24V Batteries ar...

Page 34: ...Name CL Status Light ON when CLOSE input is activated PED SW SAFETY PHANTOM EXITLOOP LIMIT1 LIMIT2 RADIO RESET POWER B L POWER M S LINK TIMER OPENING CLOSING MON FAULT MON OPEN MON CLOSE ON when Stand...

Page 35: ...l and move it to the upper left E Replace circuit board A No Power B Remote control has no battery C Gate is damaged misaligned or obstructed D Foot pedal is set to manual release E Circuit board Malf...

Page 36: ...pressing the remote control and the study button until the flashing light turns solid about 2 seconds B Downgrade sensitivity on the loop detector A Radio Frequency Interference from another nearby ga...

Page 37: ...o resistance 2 month Electrical 1 year Check wiring connections to make sure none are loose or damaged Check all gate operator accessories including remotes loop detectors keypad etc to make sure they...

Page 38: ...be sent to the warrantor at the consumer s expense to CALIMET CO INC 9949 HAYWARD WAY SOUTHE EL MONTE CA 91733 The warrantor will return the repaired or replaced unit to the customer at the consumer s...

Page 39: ...38 Notes Date Installed Model Number Serial Number Installer Name Installer Company Installer Address Installer Contact NOTES...

Page 40: ...9949 Hayward Way South El Monte CA 91733 Tel 626 452 9009 Alternate 626 482 3066 Fax 626 452 9010 Email info calimetco com www calimetco com...

Reviews: