INSTALLATION INSTRUCTIONS

AQUAVISION 2DETECT and

AQUAVISION 2DETECT-WI-SENS

ALARM MODULE

Brief description of the alarm module:

AQUAVISION 2DETECT

is a highly efficient leak detection control panel for both wired and wireless sensors.

These sensors are not supplied as standard; they need to be ordered separately.
This compact module is suitable for integration into the building’s computer network and in the event of a leak
will automatically send an alert to notify engineers of the problem. The integrated web server makes the module
easy

to

configure

and

all

data

can

be

viewed

remotely.

In the event of a leak, the location of the leak is visible on the module’s LCD screen and a buzzer is activated.
Automatic alerts are sent via SNMP or email and the alarm relay is enabled. All alarm data can be viewed
remotely. Each alarm is stored in the module’s memory, together with a time format and all detail data. The
location of the leak is easy to identify using a site plan in PDF format, which can be loaded into the alarm module.
Two separate wired leak circuits can be connected to this module. The maximum connection per circuit is 150
metres of leak detection cable or 10 leak detection probes. Optionally, an additional 8 wireless water leak sensors
can be connected to the alarm module.
The AQUAVISION 2DETECT can be easily integrated into any Building Management System by loading these relay
contacts or by reading the Modbus TCP/IP registry, which is present in the AQUAVISION 2DETECT module as
standard.

Alarm module for water leak detection systems with integrated web server and link to BMS via 
Modbus registry.

All data and alarms are continuously available via the LAN network.

Accurate indication of the location of the leak.

Automatic alarm alert via relay, SNMP trap and alarm mail.

Automatic shut-off of supply pipes

Connecting the alarm module:

Place the housing against the wall. Use the available holes provided on the outside of the housing. Position the
AQUAVISION 2DETECT in a central location relative to the wireless sensors.

Connect the required cables to the module according to the diagram below. Holes are provided for this
purpose in the bottom of the housing, together with the necessary rubber seals. Punch a hole in the rubber
seal to feed the cable through.

Summary of Contents for AQUAVISION 2DETECT

Page 1: ...ate wired leak circuits can be connected to this module The maximum connection per circuit is 150 metres of leak detection cable or 10 leak detection probes Optionally an additional 8 wireless water l...

Page 2: ...ng on This module has an integrated web server When correctly connected the module is accessible to each computer on the network ATTENTION Note the colour of the cables to the terminals G Green R Red...

Page 3: ...t are to be disconnected Press and hold the orange button to disconnect the wireless sensor The sensor is then removed from the AQUAVISION 2DETECT s memory Next the following screen appears Press and...

Page 4: ...l reset automatically CABLE BREAKAGE When a problem or breakage in the detection cable occurs the following message is displayed on the LCD This alarm will automatically reset as soon as the detection...

Page 5: ...enter the following address in the command bar http 10 0 0 1 The login screen appears 2 Via wired connection with a network cable Connect a network cable between the AQUAVISION 2DETECT and the comput...

Page 6: ...ce value in ohms of the Red Green detection loop Alarm timestamp this is the time that an alarm is activated The status of each wireless sensor is displayed The following statuses are possible No Leak...

Page 7: ...e Alarm on a wireless sensor The Alarm History page All alarms that are activated in the AQUAVISION 2DETECT are stored in the memory together with a timestamp These alarms can be viewed at all times T...

Page 8: ...used To retrieve the configured IP address press the button marked S_IP on the circuit board inside the housing The specified IP address is then displayed on the bottom line of the LCD screen SNMP if...

Page 9: ...DF plan of the channel This plan is then loaded into the module and can be retrieved via the Home page Service level select the sensitivity for the detection cable Unit select the unit Metres or Feet...

Page 10: ...Circuit 2 Leak location in meter Register 30011 Circuit 2 Leak Zone Register 30012 Circuit 2 Leakvalue in Register 30013 Wireless Sensor 1 Leak Status 0 No Leak 1 Leak Register 30014 Wireless Sensor...

Page 11: ...uter of laptop with the AQUAVISION 2DETECT Adjust the IP address of the computer via Network Centre which you can access through the screen Configuration Click on Proporties Select Internet Protocol i...

Page 12: ...type of device is no longer made it will be replaced by the newer release The warranty only applies to the equipment manufactured and supplied by the manufacturer All additional components that were i...

Reviews: