INSTALLATION REQUIREMENTS AND SPECIFICATIONS
Page 2-1
CHAPTER 2
INSTALLATION REQUIREMENTS
AND SPECIFICATIONS
This chapter describes the following:
•
Site guidelines that must be met before installing an
MMAC-M5FNB onto your network
•
MMAC configuration guidelines
•
Operating specifications for the MMAC-M5FNB enclosure and
power supply module
CAUTION:
Only qualified personnel should install or service this unit
and its modules.
2.1
SITE GUIDELINES
The following guidelines must be followed when you select a site for
the MMAC-M5FNB. If not, unsatisfactory network performance may
result.
•
An unrestricted free surface area of 43.2 cm (17 in.) wide,
37.6 cm (14.8 in.) deep and 37.6 cm (14.8 in.) high is
needed for the MMAC-M5FNB enclosure.
•
If the MMAC-M5FNB is to be placed on a shelving unit,
the shelf must be able to support 33.8 kg (75 lb.) of static
weight.
•
If the MMAC-M5FNB is to be rack-mounted, care must
be taken to ensure that the rack used will support the
unit and that the rack remains stable with the
MMAC-M5FNB installed. In order to allow proper
cooling within the rack, there must be 7.6 cm (3 in.) of
clearance above the unit and 5 cm (2 in.) of clearance on
either side of the unit.