TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
*
Caution! These parameters can
be set only by an authorized
Professional Installer.
BOILER SHOULD TEMP
- This parameter
specifies
the
maximum
working
temperature.
EXHAUST MAX TEMP
- This parameter
specifies the maximum temperature of
exhaust gases in operating mode (Work).
The controller monitors the temperature
and keeps the specified value via fan
performance management.
EXHAUST MIN TEMP
- This parameter
sets the temperature of exhaust gas at
which the controller shifts from firing up
mode to operation mode.
*
Important: In order to shift from
firing up mode to operation mode
it is necessary to be met the preset
parameter values EXHAUST MIN
TEMP and 02 GO TO REGULATION
02 MAX TEMPERATURE
- This parameter
specifies the percentage of oxygen in
the exhaust gases to be monitored and
sustained by controller in operation
mode.
02 MIN TEMPERATURE
- This parameter
sets the percentage of oxygen to be
monitored and sustained by controller in
minimum power boiler operation mode.
EXHAUST TEMP RISE
- This parameter sets
the temperature at which the controller
shifts from the loading to firing-up mode.
WAIT LAMBDA HEAT ON
- This parameter
sets the calibration time of the lambda
sensor. The minimum value is 2 min.
O2 VALUE IN IGNITION
- This parameter
specifies the percentage of oxygen
content in exhaust gas at which controller
switches mode from „
Ignition
“ to „
Burn
On
“.
MAX IGNITION TIME
- This parameter
specifies the maximum boiler time in
„
Ignition
“ mode. If the boiler does not
shift to „
Work
“ mode, there is either
a fuel problem or boiler gaskets issue -
please contact Your installer.
02 GOTO REGULATION
- This parameter
specifies the minimum percentage of
oxygen in the exhaust gas at which
controller shifts from „
Burn On
“ to
„
Work
“ mode.
EXH GOTO REGULATION
- This parameter
sets the value of exhaust gases
temperature above which shifts from
„
Burn On
“ to „
Work
“ mode
MAX BURNON TIME
- This parameter
specifies the maximum time in minutes
for the boiler to shift from „
Burn On
“ to
„
Work
“ mode.