• Thoroughly clean the lower chamber.
• Assemble the ceramic elements back
into the lower chamber in reverse order
– back (
5
), both sides (
3
and
4
) and
bottom (
2
and
1
).
5. Cleaning of fume exhaust tubes of
boiler.
Diagram 16
• Upper cleaning opening is located on top
of boiler. It is protected by two covers.
Unscrew the two wing nuts. Disassemble
the decorative lid of upper cleaning
opening on boiler casing (
1
)
• Unscrew the two wing nuts. Disassemble
the lid of upper cleaning opening on
boiler body (
2
)
Diagram 17
• Remove the cleaning system (diagram
17) using a wrench S13 and S7.
Thoroughly clean fume exhaust tubes
(
3
) of soot deposits. Use the brush from
equipment delivery.
• Lower cleaning opening is located behind
the boiler, low down. It is protected by
two covers. Unscrew the two wing nuts.
Disassemble the decorative lid of lower
cleaning opening on boiler casing (
4
)
• Lower cleaning opening. Unscrew
the two wing nuts. Disassemble the
decorative lid of lower cleaning opening
on boiler casing (
5
).
• Remove soot accumulation after the
cleaning of fume exhaust tubes
• Assemble the lid of upper cleaning
opening on boiler body (
2
). Make sure
the lid is placed correctly and tight.
• Assemble the decorative lid of upper
cleaning opening on boiler casing (
1
).
• Assemble the lid of lower cleaning
opening on boiler body (
5
). Make sure
the lid is placed correctly and tight.
• Assemble the decorative lid of lower
cleaning opening on boiler casing (
4
).
9.4. Important recommendations for
long-lasting and correct operation of the
boiler
• Please perform periodic maintenance of
the boiler as described in instructions,
section 9.2.
• The allowed moisture content of the fuel
used must not exceed 15% ÷ 20%.
• Gas emission in the combustion
chamber may result in the formation of
tar and condensate (acids). Therefore,
a mixing valve must be installed and it
must be adjusted so that the minimum
temperature of the water returning in
the boiler is 65°С. This extends the life
span of the boiler and its warranty. The
operating temperature of the water in
Summary of Contents for Lambda series