![Bürkert Type 2000 Operating Instructions Manual Download Page 10](http://html1.mh-extra.com/html/burkert/type-2000/type-2000_operating-instructions-manual_2831923010.webp)
10
Product description
Stroke limitation
•
Limit of the maximum open position/flow rate by means of
adjusting screw.
Feedback indicator
•
The device features mechanical limit switches or inductive prox-
imity switches.
device versions
5.2.2.
The angle seat valve / straight seat valve is available for the following
actuator sizes:
Type 2000: ø 40 mm to ø 125 mm
Type 2002: ø 50 mm to ø 125 mm
restrictions
5.2.3.
Warning!
risk of injury from water hammer.
A water hammer could crack the lines and device.
Due to the risk of water hammer
, valves with a flow direction
above the seat must not be used for liquid media
.
Consider the type of flow direction and the type of medium for
•
operation of the device.
intended application area
5.3.
Observe the maximum pressure range according to the
rating plate!
Neutral gases and liquids up to 16 bar,
•
Steam up to 10 bar / 180 °C,
•
Neutral and aggressive media.
•
application areas