2
Information about the appliance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
8
System temperatures 50/30 °C
Rated output
Full load
kW
145
185
240
310
400
510
640
Partial load
kW
59.2
75.6
97.8
126.3
162.4
208.8
261.5
Logatop VM
Full load
kW
145
185
230
310
–
–
–
Partial load
kW
51.8
66.1
82.1
110.6
–
–
–
Flue gas temperature
6)
Full load
°C
40
40
46
46
42
44
44
Partial load
°C
33
33
35
34
37
35
32
Flue gas mass flow rate
Full load
kg/s
0.0552
0.0704
0.0928
0.1200
0.1528
0.1969
0.2466
Partial load
kg/s
0.0217
0.0277
0.0360
0.0465
0.0603
0.0770
0.0958
Logatop VM
Full load
kg/s
0.0633
0.0808
0.1010
0.1350
–
–
–
Partial load
kg/s
0.0220
0.0283
0.0352
0.0474
–
–
–
System temperatures 80/60 °C
Rated output
Full load
kW
132.7
169.2
218.9
282.8
365.2
467.9
585.4
Logatop VM
Full load
kW
132.7
169.2
210.7
282.8
–
–
–
Partial load
kW
50.6
64.5
80.2
108.1
–
–
–
Flue gas temp.
6)
Full load
°C
66
66
71
71
68
69
71
Partial load
°C
45
45
45
44
45
44
44
Flue gas mass flow rate
Full load
kg/s
0.0579
0.0738
0.0956
0.1235
0.1592
0.2040
0.2555
Partial load
kg/s
0.0231
0.0295
0.0383
0.0494
0.0637
0.0816
0.1022
Logatop VM
Full load
kg/s
0.0633
0.0808
0.1010
0.1350
–
–
–
Partial load
kg/s
0.0220
0.283
0.0352
0.0474
–
–
–
1) In conjunction with Logatop VM.
2) According to EN 1092-1 PN6
3) According to EN 1092-1 PN16
4) With Logano plus SB615 with third party burner
5) Safety limit (High limit safety cut-out). Max. possible flow temperature = safety limit (STB) – 18K.
Example: Safety limit (STB): 100 °C, max. possible flow temperature = 100 - 18 = 82 °C
6) To DIN EN 303. Minimum flue gas temperatures for chimney design calculations in accordance with EN 13394-1
Æ
Technical Guide "Boiler
characteristic values for the dimensioning of flue gas systems".
Specifications for Logano plus SB615 Gas
Boiler size
Unit
145
185
230
1)
/240 310
400
510
640
Tab. 1
Specification