Regulations, standards and guidelines
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
10
3.3
Leaks
B
Carrying out the leak test.
The testing pressure is based on the normal operating
pressure of the heating system and should be 1.3 times
that pressure, and in any case no less than 1 bar.
3.4
Safety limits
Safety limits
Maximum flow temperature
120 °C
1)
1) For Germany. Always follow the national standards and
regulations of the country where the appliance is installed.
Permissible
operating pres-
sure
145 – 185 kW
4 bar
210 – 310 kW
5 bar
400 – 640 kW
5.5 bar
Maximum time constant on:
High limit safety cut-out
40 s
Control thermostat
40 s
Tab. 2
Safety limits