5
Installation of the boiler
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
33
5.23.3 Connecting the gas supply
B
Make the gas connection in accordance with all locally
applicable regulations.
B
Connect the gas pipe without stress to the gas
connector.
B
Install a gas shut-off valve in the gas supply pipe.
B
Before initial start-up, check for external leakage on the
new length of piping up to the gas valve.
B
If a leak is discovered, all connections must be
checked using a frothing agent.
We recommend that a gas filter be installed
in the pipework in accordance with local
regulations.
DANGER:
Risk to life from gas explosion!
Leaks may have been created on pipes and
fittings following the commissioning work.
B
Carry out the correct leak tests.
B
Only use approved leak detection agents
for leak detection.
CAUTION:
Risk of system damage due to
short circuit!
B
Cover areas at risk prior to carrying out a
leak test.
B
Do not spray the leak solution on wiring
openings, plugs or electrical connections.
Do not allow it to drip onto them either.