Appendix
15
Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007
55
We reserve the right to make any changes due to technical modifications!
Buderus • http://www.buderus.net
15.2 Error messages
z
Press the "Service"
e
button to display the service code
(e. g. "
3A
").
z
Press the "Service"
e
button to display the error code
(e. g. "
207
").
The error message is a combination of the service code
(e. g. "
3A
") and the error code (e. g. "
207
"). You can only
resolve the error message using the Service chapter in this
manual.
INSTRUCTION FOR INSTALLERS
The display may also show system faults (e. g.
"
A11
"). In principle, they are identified by the
initial letter "A" and they refer to faults between
the boiler and the additionally available elec-
tronic components.
Display
Meaning
6
Flame monitoring
A 227
No ionization message after ignition.
C 228
306
Ionization measured before burner start.
L 306
The flame went out during the heating phase.
P 229
Hot-surface ignitor on for too long.
7
Grid voltage
C
231
The grid power was interrupted after an error.
L 261
280
UBA fault.
8
External switching contact
Y
External switching contact, e. g. temperature
safety switch for floor heating, has taken place.
9
System faults
A 235
Communication fault between UBA and KIM.
H 237
267
272
UBA fault.
P 239
UBA fault.
L 234
238
239
Faulty gas burner fitting cable connection.
U 233
KIM out of order.
Y
Communication fault between BC10 basic
controller and UBA.
E
System faults
1, A, C,
F, H, L,
Y
Internal UBA fault.
Display
Meaning
2
Water flow / water pressure
E
207
System pressure too low < 3 psi (0.2 bar).
F
271
Temperature difference between safety and supply
sensors too much or no temperature increase after
starting the burner.
L 266
Test of pump operation via a pressure increase in the
heating system (during pump start).
P
Temperature increase of safety sensor or supply
sensor too high.
U
Temperature difference between supply and return
sensor too much.
Y
Pump feedback fault.
3
Fan speed
A 264
Fan unit failed during operation.
F
273
Continuous 24 hour operation.
L
214
Fan shut down during security test.
P
216
Fan unit is running too slowly.
Y
215
Fan unit is running too fast.
4
Temperatures
A
218
Supply sensor over 220 °F (105 °C).
E
278
Sensor test failed
L 220
Safety sensor affected by short circuit or higher than
266 °F (130 °C).
P
221
Loose contact or defective safety sensor.
U 222
Supply sensor affected by short circuit.
Y
223
Loose contact or faulty supply sensor.