Installation
6
16
Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007
Buderus • http://www.buderus.net
We reserve the right to make any changes due to technical modifications!
Fig. 11
Schematic representation of the boiler with the
hydraulic set connected to an optional hot water tank
with one or multiple zones including one pump and
zone valves
pos. 1: pressure relief valve
pos. 2: PT meter (pressure and
temperature meter)
pos. 3: drain valve
pos. 4: DHW pump
pos. 5: secondary pump
pos. 6: shut-off valve
pos. 7: shut-off valve
pos. 8: zone valve
pos. 9: primary pump
GB142
GB142
GB142
Additional
Additional
DHW
DHW
Tank
Tank
Optional
DHW
Tank
Aditional zones
zones
Radiant
FLUE GAS
PT
AIR INTAKE
9
1
2
4
5
6
3
7
8
WARNING
No valve is to be placed between the relief valve
and the tank. Discharge of the relief valve must
be conducted to a suitable place for disposal
when relief occurs and no reducing coupling or
other restriction may be installed in the
discharge line.
Fig. 12
Schematic representation of the boiler with the
Hydronic set connected to an optional hot water tank
with one or multiple zones and zone pumps
pos. 1: pressure relief valve
pos. 2: PT meter (pressure and
temperature meter)
pos. 3: drain valve
pos. 4: DHW pump
pos. 5: shut-off valve
pos. 6: shut-off valve
pos. 7: zone pump
pos. 8: primary pump
GB142
GB142
GB142
Additional
Additional
DHW
DHW
Tank
Tank
Optional
DHW
Tank
Aditional zones
zones
Radiant
FLUE GAS
PT
AIR INTAKE
8
1
2
3
6
7
5
4
NOTICE
Primary boiler pump must have an internal
check valve.