Converting the boiler to propane
14
Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007
53
We reserve the right to make any changes due to technical modifications!
Buderus • http://www.buderus.net
z
Fit the right orifice for the new type of gas supply (see
table 12). Make sure not to damage the O-rings.
z
Re-assemble all parts in reverse order of disassembly.
z
Carry out the start-up activities and complete a new start-
up report.
z
Also check all joints and gaskets affected by the installa-
tion activities while carrying out the tightness test in oper-
ating conditions.
z
Place a new sticker underneath the existing rating plate
sticker indicating the type of gas supply installed. Fill out
the required information on the conversion label.
z
Fit the casing again.
Boiler
capacity
Type of
gas supply
Gas orifice diameter
in mm (inch)
24 kW
Natural gas
4.45 (0.174)
LPG
P
3.35 (0.131)
30 kW
Natural gas
4.45 (0.174)
LPG
P
3.35 (0.131)
45 kW
Natural gas
5.40 (0.213)
LPG
P
4.05 (0.158)
60 kW
Natural gas
7.50 (0.293)
LPG
P
5.40 (0.213)
Table 12 Gas orifice diameter