background image

15

achieved at selected recovery time. It operates in both heating and
cooling. This only applies to programmable operation.
For example: Set back temperature in heating is 64

_

F. Smart

Recovery setpoint is 70

_

F at 7:00 a.m. At 5:30 a.m., the control

calculates the required temperature recovery rate (recovery temp --

set back temp or current temp if greater) / 90 minutes. If the current
temp at 5:30 = 66

_

F, the recovery rate = (70 -- 66)

_

F/90 minutes =

0.04

_

per minute. In order to achieve setpoint, the control ramps up

the setpoint 0.04

_

F / minute from 5:30 a.m. until 7:00 a.m. This

changing setpoint is displayed while it is occurring.

NOTE

: Temperatures should not be set back so far that the

equipment cannot recover in 90 minutes.

Air Filter

If

AIR FILTER

or

AIR PURIFIER

is installed in the indoor unit,

the system will perform a static pressure check of the system every
24 hours at 1:00 p.m. to monitor filter accumulation (TrueSense

t

Dirty Filter Detection) or whenever power is applied to the system

or the system is transitioned from Off to Cool or Heat modes. The
blower will run at a medium airflow for one minute.
This system operates by setting a base line static pressure based on
the highest airflow the system could run (this could be heat or cool

airflow). The measurement is taken at a low airflow and then

calculated up to the highest airflow the system could see.

Frozen Coil Detection

During cooling operation, the User Interface will monitor the static

pressure of the system. If the static pressure is increasing
dramatically, the User Interface will turn off cooling for up to one

hour, record fault in the “Last 10 Events” screen, and run the fan at

a reduced airflow. The User Interface will continue to monitor the
static pressure. If it is reduced before one hour has elapsed, it will

resume cooling operation. After one hour, cooling will be resumed.

Dehumidify Operation

Once a target cooling humidity setpoint is selected in the Advanced

Setup COOLING HUMIDITY screen, two other setup options

affect Dehumidify operation: COOLING AIRFLOW and
DEHUMIDIFY.
COOLING AIRFLOW: Setting this to

COMFORT

or

QUIET

will enable the system to use low airflow to help dehumidify the

space. If duct sweating becomes an issue, setting DEHUM
AIRFLOW to

HIGH

may resolve the problem.

DEHUMIDIFY: Located in the Cooling Humidity screen of the

Advanced Setup, this option has 2 settings:

ON

and

OFF

.

If DEHUMIDIFY is set to

ON

(factory default), then the cooling

unit will be allowed to overcool the space up to 3

_

F (2

_

C) if the

humidity level is above the cooling humidity target setpoint.
The amount of over--cooling allowed varies with the

dehumidification demand, the cooling demand, and the actual

space temperature. More over--cooling is allowed with greater
dehumidification demand.
When the space temperature is at or above 75

_

F (24

_

C) and the

dehumidify demand is high, over--cooling up to 3

_

F (2

_

C)

is

allowed. As the space temperature approaches 70

_

F (21

_

C), less

over--cooling is allowed. At 70

_

F (21

_

C) space temperature, no

more over--cooling is allowed no matter how great the dehumidify

demand. This is done to protect the equipment.
If DEHUMIDIFY is set to

OFF

and Cooling Airflow is set to

COMFORT

, normal dehumidification mode is enabled. For

normal dehumidification, no over--cooling is allowed when the
cooling humidity is above the target setpoint, but airflow will be

reduced during a normal cooling mode to reduce humidity. The
airflow depends on the amount of dehumidify demand. If Cooling

Airflow is set to

EFFICIENCY

or

MAXIMUM

, only

Dehumidify (over--cooling to dehumidify) will be performed.

Hybrid Heat Setup / Operation

Furnace Lockout

(

in HYBRID HEAT SETUP menu) is the

outside temperature above which the furnace will not run except
for defrost (otherwise known as the aux heat lockout).

Heat Pump Lockout

— (in HYBRID HEAT SETUP) is the

outside temperature below which the heat pump will not run

(otherwise known as the balance point).
These values can be set identical to each other. If they are not
identical, the system will stage up and down normally from heat

pump to furnace when the outside temperature is between these
settings. The User Interface will not allow the heat pump lockout

setting to be above the furnace lockout setting.
The factory default settings for both of these is NONE (no
lockouts). Even though a heat pump lockout temperature may be

set, the system will still use the furnace in defrost operation, and
may stage back down to heat pump when defrost is completed after

a 2 minute delay.

Hybrid Heat Defrost

— (in HYBRID HEAT SETUP) When the

outdoor unit needs a defrost cycle, the furnace will run during

defrost regardless of lockout temperature, unless told not to in the
Hybrid Heat Setup screen. After defrost, the system may stage

down to heat pump after a 2 minute delay.
If the room temperature falls below 40

_

F (4

_

C) and a furnace

lockout is in enabled, the furnace lockout will be overridden to

bring on the furnace.

UID

01

--

D

Summary of Contents for SYSTXBBUID01--D

Page 1: ...tential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Page 2: ...S In areas with poor air circulation such as behind a door or in an alcove Remote Room Sensor Option A Remote Room Sensor can be used with the Evolution Control to take the place of the User Interface...

Page 3: ...To remove the control from the base insert a flat screw driver into each of the four slots two on each side and pry towards yourself to release the holding tabs Refer to Fig 7 to locate the slots A100...

Page 4: ...ABCD connector will cause the Evolution System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power CAUTION 9 Push any excess wire int...

Page 5: ...5 Fig 13 Power Up Sequence NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected be...

Page 6: ...ress right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipme...

Page 7: ...g temperature using the RIGHT Up Down button 7 Press the blue COOL button Cooling temperature will be gin flashing 8 Set the cooling temperature using the RIGHT Up Down button 9 Set the remaining peri...

Page 8: ...ttings S Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings S Yes No to reset install settings in Install Service menus to factory default settings La...

Page 9: ...supply products e g fresh air make up air dampers S FAN SPEED select Low Med High for all zones when G terminal is energized S SHUTDOWN shuts off fan and equipment when initiated This function is not...

Page 10: ...alue limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Elect Heat Lockout S NONE default S 5 to 55_F 15 to 13_C Outside temperature above w...

Page 11: ...e settings YES NO HP TO FURNACE STAGING TIME Adjust the minimum amount of time the heat pump will run before furnace will be allowed to run S Default 15 MIN S Available settings 15 60 minutes If a dem...

Page 12: ...own in Fig 28 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 28 Checkout Menu Checkout Furnace or Gas PAC Make sure the furnace is properly installed...

Page 13: ...S Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service Fan Coil Status Electric Heat S OFF LOW MED HIGH Displays stages...

Page 14: ...he same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsat...

Page 15: ...ings ON and OFF If DEHUMIDIFY is set to ON factory default then the cooling unit will be allowed to overcool the space up to 3_F 2_C if the humidity level is above the cooling humidity target setpoint...

Page 16: ...ectly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage...

Page 17: ...e over as the system controller putting the regular system user interface to sleep The screen on the regular user interface will display IN SERVICE MODE The D model user interface will then learn all...

Page 18: ...hange at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 0...

Reviews: