background image

14

HP = Heat Pump
AC = Air Conditioner
FN = Furnace
FC = Fan Coil
SPP = Packaged product
SAM = System Access Module

Service -- Run / Fault History

The indoor unit and outdoor unit (if communicating) have the

following histories:

NOTE

: For Critical Fault Screens, see Troubleshooting section in

this document.

Resettable Faults:

S

Fault counters for each piece of equipment that can be reset.

Cycle Counters:

S

Number of heat/cool/power cycles the unit has performed.

Run Times:

S

Lifetime hours of operation in heating, cooling, and how long
the unit has been powered.

S

Kilowatt hours used of electric reheat for dehumidification.

Service -- Today’s Date

This menu item allows the installer to enter the current date. It is

used for time/date stamping of system faults. This should be

verified every time prior to viewing “LAST 10 SYSTEM
EVENTS” section.

Service -- Model / Serial Numbers

This menu item allows the installer to view the model number and
serial number (if available) of all communicating pieces of

equipment in the system. This is only available in original factory

supplied circuit board. If a circuit board is replaced, the model and
serial number information is no longer available.

Service -- Service Phone Number

This menu item allows the installer to enter a name and phone
number that the homeowner can call for future service of the

system. This name and phone number will appear to the
homeowner whenever a service reminder pop--up message is

displayed (i.e. Change Filter, etc.).
To edit:

S

Use Right Up/Down button to move cursor left and right.

S

Use Left Up/Down button to select numbers and letters.

S

Use Scroll button to move up and down between NAME and
NUMBER.

OPERATIONAL INFORMATION

Continuous Fan Operation

Pressing FAN button will scroll through the following:

S

AUTO = No fan operation except during equipment operation.

S

LOW = Approximately 50% of High Speed operation.

S

MED = Half way between High and Low speed operation.

S

HIGH = Highest of either High Heating or High Cooling CFM.

Continuous fan operation is programmable. The programming

option must be enabled in the Thermostat Setup. See the
Homeowner’s Manual for detailed instructions on programming

the fan.

Five--Minute Compressor Timeguard

This timer prevents compressor from starting unless it has been off

for at least 5 minutes. It can be defeated by simultaneously pressing

the Fan and Right Up buttons.

Emergency Heat (for heat pump applications)

To activate Emergency Heat, you must press and hold the HEAT

button for 3 seconds to activate. Repeat to deactivate.

Heat Source Selection (Hybrid or Hydronic Heat)

If user wishes to override normal operation in Hybrid Heat or
Hydronic Heat applications, press and hold the heat button for 3

seconds to select desired heat source.

Keypad Lockout

Keypad can be locked by pressing “Fan” and “Humidity/Oat”
buttons at the same time for 3 seconds. When keys are locked, a

lock symbol will appear in the upper left corner of screen. Follow
same procedure to unlock keypad.

Heat and Cool LED

The Heat and Cool LEDs will pulsate during actual equipment

operation. This can be defeated in the Advanced Setup Screens.

Equipment Cycle Timer (adjustable 4--6 cycles per

hour)

This timer prevents the start of a heating or cooling cycle until 15

(or 10) minutes after the last start of the same cycle. Its function is
to assure that the equipment is not cycled more than the selected

times per hour. This timer is adjustable from 4 to 6 cycles per hour.

This timer is defeated for one cycle when the desired temperature is
manually changed. It can also be defeated for one cycle by

simultaneously pressing the Fan and Right Up buttons.

Staging Timer

In multistage heating or cooling, this timer prevents any higher

stage from turning on until the preceding stage has been on for 10

minutes.
For furnace heating, the high stage timer is adjustable to force

longer minimum low stage run time. See Furnace Setup for details.
A demand of 5

_

or more will override the staging timer and allow

higher stages to energize.
In Hybrid Heat, the staging timer is 15 minutes between heat pump

and gas furnace operation. This timer is adjustable in the Hybrid

Heat Setup menu to force longer minimum heat pump run time and
longer low stage furnace run time. A demand of 5

_

F or more will

override the staging timer and allow higher stages to energize.

Three--Minute Minimum On Time

In normal operation, when a stage turns on, it will remain on for a

minimum of three minutes. If the setpoint is changed, this timer is

automatically cancelled, allowing the equipment to turn off
immediately when the demand is removed.

Heat/Cool setpoints (Desired Temperatures)

A minimum difference of 2

_

(default) is enforced between heating

and cooling desired temperatures. This is done by allowing one

setting to “push” the other to maintain this difference. This

difference is adjustable via the Install/Service menu under
Thermostat Setup.

Temperature Display

The actual temperature displayed is always rounded toward the
setpoint. This is because the system is operating and measuring the

temperature in sixteenths of a degree, but displaying in whole

numbers. The system may be turned off and on within .5

_

of

setpoint, but the display may not change. This is by design and

does not indicate a problem with the control.

Auto Changeover

When Auto mode is enabled (factory default) a change from heat

to cool (or vice versa) will not occur until an opposite mode

demand has existed for 30 minutes. If the setpoint is changed, the
30--minute requirement is defeated. This Auto Changeover time is

adjustable via the Install/Service menu under Thermostat Setup.
Range = 5 -- 120 min.

Smart Recovery

With Smart Recovery selected (factory default), transition out of

setback begins 1.5 hours before selected recovery time and
gradually adjusts room temperature so desired temperature will be

UID

01

--

D

Summary of Contents for SYSTXBBUID01--D

Page 1: ...tential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Page 2: ...S In areas with poor air circulation such as behind a door or in an alcove Remote Room Sensor Option A Remote Room Sensor can be used with the Evolution Control to take the place of the User Interface...

Page 3: ...To remove the control from the base insert a flat screw driver into each of the four slots two on each side and pry towards yourself to release the holding tabs Refer to Fig 7 to locate the slots A100...

Page 4: ...ABCD connector will cause the Evolution System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power CAUTION 9 Push any excess wire int...

Page 5: ...5 Fig 13 Power Up Sequence NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected be...

Page 6: ...ress right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipme...

Page 7: ...g temperature using the RIGHT Up Down button 7 Press the blue COOL button Cooling temperature will be gin flashing 8 Set the cooling temperature using the RIGHT Up Down button 9 Set the remaining peri...

Page 8: ...ttings S Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings S Yes No to reset install settings in Install Service menus to factory default settings La...

Page 9: ...supply products e g fresh air make up air dampers S FAN SPEED select Low Med High for all zones when G terminal is energized S SHUTDOWN shuts off fan and equipment when initiated This function is not...

Page 10: ...alue limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Elect Heat Lockout S NONE default S 5 to 55_F 15 to 13_C Outside temperature above w...

Page 11: ...e settings YES NO HP TO FURNACE STAGING TIME Adjust the minimum amount of time the heat pump will run before furnace will be allowed to run S Default 15 MIN S Available settings 15 60 minutes If a dem...

Page 12: ...own in Fig 28 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 28 Checkout Menu Checkout Furnace or Gas PAC Make sure the furnace is properly installed...

Page 13: ...S Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service Fan Coil Status Electric Heat S OFF LOW MED HIGH Displays stages...

Page 14: ...he same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsat...

Page 15: ...ings ON and OFF If DEHUMIDIFY is set to ON factory default then the cooling unit will be allowed to overcool the space up to 3_F 2_C if the humidity level is above the cooling humidity target setpoint...

Page 16: ...ectly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage...

Page 17: ...e over as the system controller putting the regular system user interface to sleep The screen on the regular user interface will display IN SERVICE MODE The D model user interface will then learn all...

Page 18: ...hange at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 0...

Reviews: