background image

17

SYSTEM MALFUNCTION SCREEN

OUTSIDE: 84

_

| FAN: AUTO

71

_

HVAC SERVICE

1---800---555---1212

SYSTEM MALFUNCTION

CALL TECHNICIAON

A07036

Fig. 31 -- System Malfunction Screen

Fan Coil

The code number represents flash code on circuit board of fan coil.
Certain faults will generate a system malfunction message on the

main screen. When this occurs, a technician should proceed to the

Last 10 System Events screen in the Service Menu to determine
which fault has caused the message.
Below is a list of which faults will result in a System Malfunction
event:
Code 37 -- Heater output sensed On when not energized
Code 41 -- Blower Motor Fault (ventilator, humidifier,
dehumidifier, outdoor unit will be turned off)
Code 44 -- Motor Communication Fault (ventilator, humidifier,
dehumidifier, outdoor unit will be turned off)
Code 45 -- Control failure

Furnace

The code number represents flash code on circuit board of furnace.
Code 13 -- Limit Circuit Lockout
Code 14 -- Ignition Lockout
Code 15 -- Blower Motor Lockout (ventilator, humidifier,

dehumidifier, outdoor unit will be turned off)
Code 21 -- Gas Heating Lockout
Code 22 -- Abnormal Flame Proving Signal
Code 23 -- Pressure Switch Did Not Open
Code 24 -- Secondary Voltage Fuse Open
Code 33 -- Limit Circuit Fault AND high heat only is active
Code 41 -- Blower Motor Fault (cooling mode only) (ventilator,

humidifier, dehumidifier, outdoor unit will be turned off)
Code 45 -- Control Circuitry Lockout

NOTE

: For codes 13, 14 and 21, the system will use heat pump

heating exclusively if available. When the error code is cleared or
disappears, furnace heating will resume if still requested.

Service Tool Mode

The --D model of user interface can be used as a service tool on any

Evolution system. Attach the --D model user interface anywhere on
the ABCD wiring (e.g. at the indoor or outdoor unit). When the

user interface powers up, it will ask the user if they wish to enter

service mode. Selecting “Yes” will allow the --D model user
interface to take over as the system controller, putting the regular

system user interface to sleep. The screen on the regular user
interface will display “IN SERVICE MODE”. The --D model user

interface will then learn all equipment and function as the system

controller. While in service mode, the --D model user interface will
not transfer any settings or information to or from the regular user

interface----it only takes over control of the system. After removing
the --D model user interface from the ABCD wiring, the regular

user interface will take over the system after two minutes.

Outdoor Unit

The code number represents flash code on circuit board of outdoor
unit.
Code 25 -- Invalid model plug
Code 45 -- Control Failure
Code 47 -- No 230V at unit
Code 73 -- Contactor shorted
Code 74 -- No high voltage at compressor
Code 76 -- Low stage didn’t start three times
Code 78 -- High stage didn’t start three times
Code 81 -- Thermal lockout in low stage -- 4 hrs.
Code 82 -- Thermal lockout in high stage -- 4 hrs.
Code 83 -- Low Pressure Lockout -- 4 hrs.
Code 84 -- High Pressure Lockout -- 4 hrs.
Code 85 -- Low contactor open
Code 86 -- Low contactor shorted
Code 87 -- High contactor open

User Interface

S

Temp sensor failed, loss of communication with smart sensor,
smart sensor fault. “NO SENSOR DATA” shown

S

Indoor unit communication fault

S

Outdoor unit communication fault

S

Packaged product communication fault

S

NIM communication fault

S

SAM communication fault

S

Possible Frozen Coil

S

High Room Temp Alert, when 100

_

F exists for at least 10

minutes, and removed when less than or equal to 98

_

F exists

S

Low Room Temp Alert, when 38

_

F exists for at least 10

minutes, and removed when greater than or equal to 40

_

F exists

S

High Humidity Alert, when 80% Rh exists for 30 minutes, and
removed when less than or equal to 78% Rh exists

The user can press the right side button to dismiss the notice. The
regular run mode screen will then appear except “SYSTEM

MALFUNCTION” will appear in place of the day/time. If the error
has not disappeared within 24 hours, the above display will return.

If the error code disappears, “SYSTEM MALFUNCTION” will

disappear and the day/time will reappear.

UID

01

--

D

Summary of Contents for SYSTXBBUID01--D

Page 1: ...tential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in sev...

Page 2: ...S In areas with poor air circulation such as behind a door or in an alcove Remote Room Sensor Option A Remote Room Sensor can be used with the Evolution Control to take the place of the User Interface...

Page 3: ...To remove the control from the base insert a flat screw driver into each of the four slots two on each side and pry towards yourself to release the holding tabs Refer to Fig 7 to locate the slots A100...

Page 4: ...ABCD connector will cause the Evolution System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power CAUTION 9 Push any excess wire int...

Page 5: ...5 Fig 13 Power Up Sequence NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected be...

Page 6: ...ress right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipme...

Page 7: ...g temperature using the RIGHT Up Down button 7 Press the blue COOL button Cooling temperature will be gin flashing 8 Set the cooling temperature using the RIGHT Up Down button 9 Set the remaining peri...

Page 8: ...ttings S Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings S Yes No to reset install settings in Install Service menus to factory default settings La...

Page 9: ...supply products e g fresh air make up air dampers S FAN SPEED select Low Med High for all zones when G terminal is energized S SHUTDOWN shuts off fan and equipment when initiated This function is not...

Page 10: ...alue limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Elect Heat Lockout S NONE default S 5 to 55_F 15 to 13_C Outside temperature above w...

Page 11: ...e settings YES NO HP TO FURNACE STAGING TIME Adjust the minimum amount of time the heat pump will run before furnace will be allowed to run S Default 15 MIN S Available settings 15 60 minutes If a dem...

Page 12: ...own in Fig 28 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER VENTILATOR BACK SELECT A03204 Fig 28 Checkout Menu Checkout Furnace or Gas PAC Make sure the furnace is properly installed...

Page 13: ...S Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service Fan Coil Status Electric Heat S OFF LOW MED HIGH Displays stages...

Page 14: ...he same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsat...

Page 15: ...ings ON and OFF If DEHUMIDIFY is set to ON factory default then the cooling unit will be allowed to overcool the space up to 3_F 2_C if the humidity level is above the cooling humidity target setpoint...

Page 16: ...ectly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage...

Page 17: ...e over as the system controller putting the regular system user interface to sleep The screen on the regular user interface will display IN SERVICE MODE The D model user interface will then learn all...

Page 18: ...hange at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in China Edition Date 0...

Reviews: