Bryant EVOLUTION V 189BNV 13 Installation Instructions Manual Download Page 3

3

8. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with tub-

ing (see Fig. 1).

9. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

10. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation. (See Fig. 1.)

11. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.
If proper lineset routing techniques are not followed, variable

speed systems can be susceptible to lineset transmitted noise

inside the dwelling and, in extreme cases, tubing breakage.

CAUTION

!

INSULATION

SUCTION TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

SUCTION TUBE

INSULATION

CAULK

HANGER STRAP

(AROUND SUCTION

TUBE ONLY)

JOIST

1” (25.4 mm)

 MIN

THROUGH THE WALL

SUSPENSION

A07588

Fig. 1 -- Connecting Tubing Installation

The outdoor unit contains the correct amount of refrigerant charge

for operation with AHRI rated indoor units when connected by 15
ft (4.57 m) of field--supplied or factory accessory tubing.
Adjust refrigerant charge by adding or removing the charge

to/from the unit depending on lineset length and indoor unit as
calculated and displayed on the UI. The user interface (UI)

calculates required charge adjustment and total system charge
required. For proper unit operation, check refrigerant charge using

charging information in the Check Charge section of this
instruction.

IMPORTANT:

Liquid--line size is 3/8--in. OD for all 189BNV

applications. The maximum allowable equivalent line set length is
100 ft. (30.5 m).

IMPORTANT:

Always install the factory--supplied liquid--line

filter drier. Obtain replacement filter driers from your distributor or
branch.

INSTALLATION

Specifications for this unit in residential new construction market
require the outdoor unit, indoor unit (including metering device),

refrigerant tubing sets, and filter drier listed in pre--sale literature.
There can be no deviation. Consult the Service Manual – Air

Conditioners and Heat Pumps Using Puron

Refrigerant to obtain

required unit changes for specific applications and for R--22
retrofit.

Step 1 — Check Equipment and Job Site

Unpack Unit

Move to final location. Remove carton taking care not to damage

unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment

is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.

Check rating plate to be sure unit matches job specifications.

Step 2 — Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts

provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE

(Professional Engineer) Certification, if required.
On rooftop applications, mount on level platform or frame. Place

unit above a load--bearing wall and isolate unit and tubing set from

structure. Arrange supporting members to adequately support unit

and minimize transmission of vibration to building. Consult local

codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require

wind baffles. Consult the Service Manual -- Residential Split

System Air Conditioners and Heat Pumps Using Puron

Refrigerant for wind baffle construction.

NOTE:

Unit must be level to within

2

(

3/8 in./ft,

9.5 mm/m.)

per compressor manufacturer specifications.

Step 3 — Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)

clearance to service end of unit and 48 in. (1219.2 mm) (above

unit. For proper airflow, a 6--in. (152.4 mm) clearance on 1 side of

unit and 12--in. (304.8 mm) on all remaining sides must be

maintained. Maintain a distance of 24 in. (609.6 mm) between

units. Position so water, snow, or ice from roof or eaves cannot fall

directly on unit.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above

roof surface.

3/8---in. (9.53 mm) Dia.

Tie---down Knockouts in

Basepan(2) Places

View From Top

A05177

UNIT BASE PAN

Dimension in. (mm)

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

23 X 23

(596 X 596)

7---13/16 (198)

4---7/16 (102)

18---1/8 (458)

31.2 X 31.2

(792 X 792)

9---1/8 (232)

6---9/16 (167)

24---11/16 (627)

35 X 35

(889 X 889)

9---1/8 (232)

6---9/16 (167)

28---7/16 (722)

Fig. 2 -- Tie--down Knockout Locations

Summary of Contents for EVOLUTION V 189BNV 13

Page 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Page 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Page 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Page 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Page 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Page 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Page 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Page 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Page 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Page 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Page 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Page 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Page 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Page 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Page 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Page 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Page 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Page 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Page 19: ...19 Table 6 Fault Codes...

Page 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Reviews: