Bryant EVOLUTION V 189BNV 13 Installation Instructions Manual Download Page 14

14

NOTE

: The unit may be operated with an Evolution Connex

Control or a standard 2--stage thermostat. Evolution Connex
Control will utilize 5 stages cooling, while 2--stage thermostat will
only allow 2 discrete stages of cooling operation.

Variable Speed Compressor

This unit contains a variable speed rotary compressor that has a

wide operating range. It operates on a variable 3 phase sine wave
provided by the inverter. This compressor can only be operated by

the specific inverter supplied with the unit.

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

and/or improper operation.
Do not attempt to apply line voltage directly to the

compressor. This will destroy the compressor.

CAUTION

!

Field control Connections

For communicating operation use the communication Evolution

plug only. Only two wires, AB (color), are required. If necessary,

connect C for additional grounding (see Fig. 6). If using standard
2--stage thermostat, connect discrete inputs (R,C,Y2,Y1) for

2--stage control in cooling modes.

Pressure Transducer (SPT)

A 5 VDC output low pressure transducer that provides a 0--5 VDC
data for interpretation by the control board for a 0 to 200 psig

range of pressure at the suction tube. This interpreted pressure data
is then intelligently used by the AOC control board for low

pressure cut--out, loss of charge management, compressor

protection,

oil

circulation

management,

and

lubrication

management.

Pressure Equalizer Valve (PEV)

At the end of every compressor operation (after the 3.5 minute

Time Guard period), the equalizer valve opens for 150 seconds
plus an additional 15 seconds of protection before allowing the

compressor to start ramping up.
The PEV is located next to the suction and discharge of the

compressor.

The function of this valve is to prevent the

compressor from starting with a high refrigerant pressure

differential, thus helping the reliability of the compressor.

NOTE

: A hissing sound may be heard during the equalization

process. This is normal.

TROUBLESHOOTING

Systems Communication Failure

If communication is lost with the User Interface (UI), the Green
LED will be off. Check the wiring to the User Interface and the

indoor and outdoor units and power.

Model Plug

Each control board contains a model plug. The correct model plug
must be installed for the system to operate properly (see Table 3).
The model plug is used to identify the type and size of unit to the

control.
On new units, the model and serial numbers are inputted into the

AOC board’s memory at the factory. If a model plug is lost or
missing at initial installation, the unit will operate according to the

information input at the factory and the appropriate error code will
flash temporarily. An RCD replacement AOC board contains no

model and serial information. If the factory control board fails, the

model plug must be transferred from the original board to the
replacement board for the unit to operate.
When installing AC unit with older fan coils, a model plug change
may be required.

NOTE

:

The model plug takes priority over factory model

information input at the factory. If the model plug is removed after
initial power up, the unit will operate according to the last valid
model plug installed, and flash the appropriate fault code
temporarily.

Table 3 – Factory Supplied Model Plug Information

189BNV

MODEL PLUG

NUMBER

PIN RESISTANCE

(K---ohms)

Pins 1---4

Pins 2---3

13

HK70EZ028

11K

180K

24B

HK70EZ010

5.1K

120K

25

HK70EZ011

5.1K

150K

36

HK70EZ012

5.1K

180K

37

HK70EZ025

11K

91K

48

HK70EZ013

5.1K

220K

49

HK70EZ027

11K

150K

60

HK70EZ014

5.1K

270K

Service Tool

A150062

Fig. 27 -- Service Tool Connection

When working on the outdoor unit of a split system, the technician

would usually need to repeatedly walk between the indoor wall

control and the unit outside. To save time, the communicating

controls offer a service tool feature.
By wiring the service tool into the AOC board and powering it

with an external adapter, the technician can have a wall control

capable of running the system right at the outdoor unit.

Summary of Contents for EVOLUTION V 189BNV 13

Page 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Page 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Page 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Page 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Page 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Page 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Page 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Page 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Page 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Page 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Page 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Page 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Page 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Page 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Page 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Page 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Page 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Page 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Page 19: ...19 Table 6 Fault Codes...

Page 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Reviews: