Bryant EVOLUTION V 189BNV 13 Installation Instructions Manual Download Page 15

15

To use a service tool, connect the A and B communication bus

wires from this second communicating control to the terminals

marked A and B on the terminal strip located in the bottom left

corner of the AOC board (see Fig. 27). But instead of connecting

the wires on the service tool to the terminals marked C and D,

connect the C and D wires from the service tool to the 24V and C

on ST1 as shown in Fig. 27.
When the service tool is connected and powered up, the

communicating controls inside the home will ”go to sleep” and let

the service tool take control of the system. In this manner, the
service technician can run the diagnostic checkouts right at the

outdoor unit using the service tool.
After the checkouts are completed and it is no longer necessary to

use the service tool, remove it from the communicating controls

and the indoor communicating controls will regain control in about
two minutes.

Pressure Switch Protection

The outdoor unit is equipped with high pressure switch. If the

control senses the opening of a high pressure switch (open 600+/--5
psig, close 470+/--10 psig @77

_

F), it will respond as follows:

1. Display the appropriate fault code (see Table 6).
2. After a 6 minute delay, if there is a call for cooling and HPS

is reset, the PEV opens for 150 seconds to equalize system
pressures. The compressor and fan will then ramp to the
next lower stage of operation until demand is satisfied. In

the next call for cooling system will resume normal opera-
tion.

3. If the opened switch closes at any time after the 6 minute

delay, then the PEV opens for 150 seconds to equalize sys-
tem pressures. The compressor and fan will then ramp to the

next lower stage of operation until demand is satisfied. In
the next call for cooling system will resume normal opera-

tion.

4. If HPS trips when at lowest available stage, the unit opera-

tion is locked out for 4 hours.

5. In the event of a high--pressure switch trip or high--pressure

lockout, check the refrigerant charge, outdoor fan operation,

and outdoor coil (in cooling) for airflow restrictions.

6. In the event of a low--pressure trip or low--pressure lockout,

check the refrigerant charge and indoor airflow (cooling).

Brown--Out Protection

If the line voltage is less than 187V for at least 4 seconds, the

Compressor and OD fan goes to 0 rpm. Compressor and fan
operation are not allowed until voltage is a minimum of 190V. The

control will flash the appropriate fault code (see Table 6).

230V Line (Power Disconnect) Detection

The control board senses the presence of absence of 230V through
inverter feedback. Voltage should present at all times when system

is in service regardless if system is running or standby. If there is
no 230V at the inverter when the indoor unit is powered with a

cooling demand, the appropriate fault code is displayed on UI

(communicating only – see Table 6). If system is configured with
conventional thermostat (non--communicating), no fault code will

be displayed on AOC board, nor will any status LEDs be lit. Use
multimeter to check for the presence of 230V in this situation.

Temperature Thermistors

Thermistors are electronic devices which sense temperature. As the

temperature increases, the resistance decreases.

10Kohm

thermistors are used to sense outdoor air temperature (OAT), coil

temperature (OCT) and the suction line temperature (OST) located
between the reversing valve and the accumulator. A 50Kohm

thermistor is used to sense discharge temperature (ODT).
Refer to Table 4 and Fig. 28 and 29 for resistance values versus

temperature.

Table 4 – 10K/50Kohm Resistance Values vs Temperature

10Kohm

_

C (

_

F)

TEMPERATURE

RESISTANCE (ohms)

25.0 (77.0)

10.0 + / --- 2.3%

0.0 (32.0)

32.6 + / --- 3.2%

-28.0 (-18.4)

85.5 + / --- 3.4%

50Kohm

125.0 (257.0)

1.7 + / --- 1.6%

75.0 (167.0)

7.40 + / --- 2.0%

25.0 (77.0)

50.0 + / --- 2.3%

0

10

20

30

40

50

60

70

80

90

0

20

40

60

80

100

120

TEMPERATURE (DEG. F)

RESISTANCE (KOHMS)

THERMISTOR CURVE

A91431

Fig. 28 -- 10K Thermistor Resistance Versus Temperature

0

50

100

150

200

250

300

350

400

450

0

20

40

60

80

100

120

RE

SISTAN

CE (KOHM

S)

TEMPERATURE (

°

°

F)

50K THERMISTOR

A14022

Fig. 29 -- 50K Thermistor Resistance Versus Temperature

If the outdoor air or coil thermistor should fail, the control will

flash the appropriate fault code (see Table 6).

IMPORTANT:

The outdoor air thermistor, coil thermistor and

suction thermistor should be factory mounted in the final
locations.

Check to ensure thermistors are mounted properly

(See Fig. 30, 31, 32 and 33).

Summary of Contents for EVOLUTION V 189BNV 13

Page 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Page 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Page 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Page 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Page 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Page 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Page 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Page 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Page 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Page 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Page 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Page 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Page 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Page 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Page 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Page 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Page 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Page 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Page 19: ...19 Table 6 Fault Codes...

Page 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Reviews: