Bryant EVOLUTION V 189BNV 13 Installation Instructions Manual Download Page 17

17

Variable Speed Compressor Winding Resistance

This compressor operates with 3--phase variable frequency PWM

variable voltage. For troubleshooting certain fault codes related to
compressor resistances, follow these steps:

1. Disconnect compressor power leads from the inverter MOC

terminals, U (YEL), V (RED), and W (BLK).

2. Measure the resistance between YEL to RED, YEL to BLK,

and RED to BLK and compare to Table 5 values. Each re-
sistance set should be equal.

3. Measure the resistance to ground for each lead.
4. If the resistances check out, reconnect power leads to

appropriate terminal.

5. If the resistances appear to be abnormal, it will be necessary

to measure the resistance at the compressor fusite terminals.

6. During the removal of the compressor fusite cap, do not re-

move the RTV sealant. Remove the harness plug, measure

the resistances, and compare to Table 5.

7. Special care will need to be taken with the replacement of

the compressor fusite cap. Make sure the two holes in the

compressor fusite terminal box are still full of RTV sealant
before the cap is reinstalled. The factory RTV can be reused

as long as none of it has been removed during the cap
removal.

8. Reinstall compressor sound blanket making sure discharge

thermistor and compressor power harness are routed as they
were from the factory

Table 5 – Variable Speed Compressor Resistance

(winding resistance at 70

_

F

20

_

F)

WINDING

MODEL 189BNV (OHMs)

13, 24B

25

36

37, 48

49, 60

Between

terminals

1.13

.59

.59

.37

.24

Between

terminal &

ground

>1 mega

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

and/or improper operation.
Do not use Meggar for measuring the winding resistance.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

and/or improper operation.
To maintain water integrity of the compressor fusite terminal

box, the two holes in outer ring need to be full of RTV sealant.

CAUTION

!

Fan Motor

If verification of proper operation is required for the fan motor

used in this unit, follow these steps:

1. Disconnect fan motor connector from control board.
2. Measure resistance between any 2 of the 3 leads present.
3. Compare measurement to values below

Fan Motor Resistance

Unit Size

Resistance (Ohms)

13, 24B

21.2

25, 36, 37, 48, 49, 60

11.1

Status Codes

Unit may occasionally become unresponsive due to certain

combinations of previous fault codes. There may not be

anything wrong with the unit or components. The unit may

require a high voltage power cycling for at least 2 minutes or

longer to clear the condition. If the condition persists, conduct

further troubleshooting per Service Manual.

ATTENTION

!

Table 6 shows the status codes flashed by the amber status light.

Most system problems can be diagnosed by reading the status code

as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the

status light. The short flashes indicate the first digit in the status
code, followed by long flashes indicating the second digit of the

error code.
The short flash is 0.25 seconds ON and the long flash is 1.0 second
ON. Time between flashes is 0.25 seconds. Time between short

flash and first long flash is 1.0 second. Time between code
repeating is 2.5 seconds with LED OFF.
Codes are easily read from user interface (UI)

EXAMPLE

:

3 short flashes followed by 2 long flashes indicates a 32 code.

Table 6 shows this to be low pressure switch open.

Status Code Recall Mode

Active status codes are stored in memory even when power is
absent. The most recent flashing status code (highest priority

active) can be recalled from memory via Status Code Recall Mode
and displayed using the amber LED. The Status Code Recall

Mode is accessed by shorting (use a clip wire) the “force defrost”

connector (labeled J2 on the board) and then power ON the unit.
Please make sure the unit is turned OFF before shorting the pins.

Status Code Recall Mode will continue as long as the “force
defrost” terminals remain shorted. The unit will not attempt to heat

or cool while the terminals remain shorted. Once the status code is

read, power--down the unit and remove the short.

Utility Interface With Evolution Connex Control

The utility curtailment relay should be wired between the two
UTIL connections on the control board for this Evolution

Communicating System (see Fig. 34). This input allows a power
utility device to interrupt compressor operation during peak load

periods. When the utility sends a signal to shut the system down,

the User Interface status screen will display, ”Curtailment Yes”.
See UI installation instructions for setup details.

Summary of Contents for EVOLUTION V 189BNV 13

Page 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Page 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Page 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Page 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Page 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Page 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Page 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Page 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Page 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Page 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Page 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Page 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Page 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Page 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Page 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Page 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Page 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Page 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Page 19: ...19 Table 6 Fault Codes...

Page 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Reviews: