Bryant EVOLUTION V 189BNV 13 Installation Instructions Manual Download Page 10

10

Step 11 — System Functions and Sequence of

Operation

The 189BNV models utilize either Evolution

Connex

Communicating User Interface (UI) or conventional thermostat.

When using UI controls, a call for cooling will energize the

outdoor fan and compressor to run at lowest cooling demand. If

this does not satisfy cooling demand, the system will ramp up in

stages until it satisfies the demand. After coping with the higher

demand, the unit returns to lower capacity operation until the

demand is satisfied or until an increase in demand. When using a

conventional thermostat, the thermostat controls the staging of

outdoor unit.
Upon initial start--up (or any power cycle) of unit, there will be a
five minute delay before the unit will start once a call for heating or

cooling is given. The compressor will then ramp to stage 2 and
operate there for one minute. Once the minute has elapsed, status

code 68 will be generated and system will continue to operate at
stage 2 for 10 minutes. This operation is important to system

reliability and cannot be bypassed. Each time high voltage is

removed and reapplied, this behavior will be repeated.
Once 10 minutes has elapsed, the unit will ramp to the stage called

for. It will take approximately three additional minutes to obtain
high stage compressor RPM.
When all demand is satisfied, the compressor will shut off. As the

unit operates at lower capacity, system vapor (suction) pressure will

be higher than it is during a standard single--stage system operation

or during a higher capacity operation.
The user interface (UI) displays the operation mode and fault codes

as specified in the troubleshooting section. See Table 6 for codes

and definitions.
The conventional thermostat inputs are designed to work with most

indoor units. See AHRI for approved combinations. Connections

are Y/Y2, Y1, R and C. Depending on thermostat and indoor unit,

the system will operate at 1 or 2 capacities in cooling mode.

NOTE:

Only one code will be displayed on the outdoor unit

control board (the most recent, with the highest priority). The

latest codes are stored and can be accessed via the UI.
Upon a call for cooling through the UI (or the Y1 and/or Y2

connections in a non--communicating system), the Application

Operation Control (AOC) board (see Fig. 26) will request a

compressor speed and outdoor fan motor speed based on the

indoor space demand and outdoor conditions.
If the conditions are correct for operation, the control board will

allow the requested operation to begin, but if the control board

determines that the conditions are not correct, the board will decide

what other operation nearing that condition is acceptable. The

inverter Motor Operational Control (MOC) then outputs the

three--phase PWM signal and frequency that gently ramps the

compressor speed up to stage 2, and then will adjust to the

demanded speed. The gentle ramp--up results in no locked rotor

amps to the compressor motor. The unit nameplate for compressor

LRA will be stamped N/A (not applicable).
During operation, the AOC monitors itself and the compressor

operation along with the system pressures and temperatures. The

MOC board monitors the temperature, current and operational

status of the compressor, OD fan and the inverter itself. During

operation, the compressor speed will be adjusted to meet the

changes to the demand.

Step 12 — Check Charge

Charge in CHARGING mode (communicating only)

Unit is factory charged for 15ft (4.57 m) of lineset. If any

refrigerant charge adjustment is required due to the user inputted

line set length, the UI will calculate and display the target

subcooling and the amount of additional charge to be added.

Therefore, the UI is your source of information for charging the

system correctly. Refrigerant charge adjustment amount for adding

or removing 0.6 oz/ft (17.74 g/m) of 3/8 liquid line above or below

15ft (4.57 m) respectively. Perform a final charge check only when

in cooling and OD is between 65

_

F (18

_

C) and 100

_

F (38

_

C).

The use of a commercial charge metering device (restrictor) such as

Imperial liquid low side charger model 535--C or Watsco

ChargeFaster model CH200 is recommended when adding

refrigerant to an operating system. This prevents potential damage

of liquid slugging of the compressor and allows the subcooling to

stabilize quicker.
Charging using the subcooling method optimizes charge volume

and is preferred if possible. If the outdoor temperature is between

65

_

F -- 100

_

F (18.3

_

C -- 37.8

_

C) and indoor temperature is 70

_

F

-- 80

_

F (21.1

_

C -- 26.7

_

C), the option to further adjust charge

using “service valve subcool” will be available in the “charging

mode selection” screen. If temperatures are outside of range, this

option will be greyed out and not selectable.
Initial start--up can be performed using calculated charge only and

once conditions are within range, the ”Service Valve Subcool”

option will become selectable. Inaccurate charging may result in

nuisance fault codes.
Once start is selected the system will operate in a preset mode until

“done” is selected. Wait for required stabilization time then check

subcooling at service valve.
Adjust charge as required to meet target service valve subcooling

shown on screen --3/+0 degree. If any adjustment is necessary, add

or remove the charge slowly (no greater than .5 lb per minute) and

allow system to operate for 25 minutes to stabilize, before

declaring a properly charged system.

A14573

Fig. 15 -- Adjusting Charge Using Service Valve Subcool

A14574

Fig. 16 -- Service Valve Subcool Target Value

A14575

Fig. 17 -- Stabilization Time

Summary of Contents for EVOLUTION V 189BNV 13

Page 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Page 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Page 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Page 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Page 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Page 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Page 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Page 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Page 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Page 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Page 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Page 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Page 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Page 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Page 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Page 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Page 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Page 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Page 19: ...19 Table 6 Fault Codes...

Page 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Reviews: