background image

B.

Step 2 — Evolution Control™ Location and Wiring

Considerations

WARNING:

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal
injury or possible equipment damage.
Disconnect Power before routing control wiring.

All wiring must comply with national, local, and state codes.

EVOLUTION CONTROL™ LOCATION— The Evolution Con-
trol™ is the command center for the Evolution System. It should
be located where it is easily accessible and visible to the adult
homeowner or end user.

For accurate temperature measurement, the following guidelines
should be followed:

The Evolution Control™ should be mounted:

Approximately 5 feet (1.5 meters) from the floor.

Close to or in a frequently used room, preferably on an inside
partitioning wall.

On a section of wall without pipes or duct work.

The Evolution Control™ should NOT be mounted:

Close to a window, on an outside wall, or next to a door leading
to the outside.

Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature-radiating objects which could cause a false
reading.

Close to or in direct airflow from supply registers.

In areas with poor air circulation, such as behind a door or in
an alcove.

REMOTE SENSOR OPTION — A remote room sensor can be
used with the Evolution Control™ to take the place of the internal
temperature sensor. This allows the control to be mounted in areas
with less than optimal airflow (such as near an exterior door,
window or in a closet). The remote sensor is wired to the terminal
block connectors labeled S1 and S2. The Evolution Control™ will
automatically detect the remote sensor and ignore its internal
sensor. It is also important to note the humidity sensor cannot be
remotely located, so do not locate the Evolution Control™ in an
area where humidity sensing may not be accurate.

NOTE:

S1 & S2 connection on UI back-plate is now used for the

Remote Room Sensor, NOT for OAT Sensor hookup (S1 & S2
was previously used for OAT).

WIRING CONSIDERATIONS — Ordinary thermostat wire is
recommended. Use 22 AWG or larger for normal wiring applica-
tions. Continuous wire lengths over 100 ft. should use 20 AWG or
larger.

NOTE:

ABCD bus wiring only requires a four-wire connection;

however, it is good practice to run thermostat cable having more
than four wires in the event of a damaged or broken wire during
the installation.

Each device in the Evolution System has a four-pin connector
labeled ABCD. It is recommended that the following color code be
used when wiring each device:

A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)

It is not mandatory that the above color code be used, but each
ABCD connector in the system MUST be wired consistently.

MOUNTING EVOLUTION CONTROL™ — There are two
options for mounting the Evolution Control™ to the wall. First,
familiarize yourself with all plastic assembly pieces shown in Figs.
2 through 9. The User Interface will snap together with either the
Recess Mount or the Surface Mount backplate.

RECESS MOUNT — This provides the thinnest mounting con-
figuration (See Fig. 3). The backplate containing the recessed
terminal block can be mounted directly to the wall by cutting a
hole 1 ½

wide by 2 1/8

high. Mark location and cut hole in wall.

NOTE:

Always ensure the Evolution Control™ location is ac-

ceptable before cutting any holes in wall.

SURFACE MOUNT — This provides surface mounting configu-
ration, which allows use of a small hole in the wall. A surface
mount backplate is supplied (See Fig. 4). Attach backplate as
shown in figure 7, and the assembly will mount directly to the wall
requiring only a small hole in the wall allowing a four wire
connection to pass through.

NOTE:

Once Evolution Control™ is secured to wall with the

backplate assembly (snapped together), care must be taken not to
bend or break the interlocking tabs when removing. Gently remove
Evolution Control by rocking up/down until interlocking tabs
release.

DECORATIVE BACKPLATE — Supplied, is a thin, decorative
backplate (see Fig. 5), to hide any marks/screw holes left from the
previous thermostat. This decorative backplate (or beauty ring) can
be used in either the recess or surface mount installation by
snapping it onto the back of the recessed mount backplate or
surface mount backplate before securing to the wall. See Fig. 8 and
9 for a larger decorative backplate (5.75

wide X 6

tall), which

can be ordered separately.

Fig. 2—Evolution Control™

A03185

Fig. 3—Recessed Mount Backplate

A03186

—2—

Summary of Contents for Evolution Control SYSTXBBUID01

Page 1: ...rmo stat plus much more and a variable speed furnace or FE fan coil They support controlled ventilation humidification dehumidifica tion and air quality control Either a two speed communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the variable speed furnace or fan coil provides the 24 volt signals needed to control them Also the Evolution N...

Page 2: ...WG or larger NOTE ABCD bus wiring only requires a four wire connection however it is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during the installation Each device in the Evolution System has a four pin connector labeled ABCD It is recommended that the following color code be used when wiring each device A Green Data A B Yellow Data B...

Page 3: ...volution Control mounting plastic recess mount or surface mount and decorative backplate if desired 4 Route wires through large hole in mounting plastic Level rear plastic against wall for aesthetic value only Evolution Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 inch mounting holes in wall where marked Fig 4 Surface Mount Backplate A0318...

Page 4: ...perature sensor may be installed not required at the indoor furnace or fan coil OAT terminals When OAT is applied the Evolution System will provide full system features and benefits See wiring diagram Fig 14 for a Typical Connection Diagram for FE fan coil with a 1 speed heat pump using non communicating outdoor unit When OAT is applied the Evolution System will provide full system features and be...

Page 5: ...None no unit installed Press the right side button to continue to the next screen If you have selected either AC or HP as the outdoor unit type the following middle screen will appear See figure 16 Press either Time or Temp buttons to select appropriate Btu size of outdoor unit then press right side button to continue If a NIM Network Interface Module is applied for non communicating two speed out...

Page 6: ...lso after selecting YES if the filter type is not an EAC the indoor unit will operate the blower for one minute to do a system static pressure check QUICK START For first time installers Quick Start will allow you to start up the Evolution System before you have the chance to learn all the details of system operation However for the best possible comfort and operation we recommend that you refer t...

Page 7: ...RVICE MENUS The INSTALL SERVICE menus contain a set of vital information This information enables the Installer or Service person to view a summary of what has been installed etc To enter INSTALL SERVICE menus press and hold the ADVANCED button for at least ten seconds The following menu will appear See figure 20 NOTE The INSTALL SERVICE menu will automatically exit after 60 minutes of no push but...

Page 8: ...ncreased comfort AC AIRFLOW COMFORT default EFFICIENCY MAXIMUM Selects the airflow of the furnace when cooling COMFORT is a decreased airflow used to improve humidity control EFFI CIENCY is the airflow used to meet specified ratings MAXI MUM is a fixed airflow speed of 400 CFM ton based on the outdoor unit size DEHUM AIRFLOW NORMAL default HIGH NORMAL airflow adjustment is used during dehumidifyin...

Page 9: ...turn on SETUP UV LIGHTS UV LIGHTS INSTALLED NO YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed SETUP SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adjust the timer interval in which the normal System Maintenanc...

Page 10: ...lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service FAN COIL ELECTRIC HEAT STATUS OFF LOW MED HIGH Displays stages of electric heat that the fan coil is currently delivering AIRFLOW CFM fan coil model dependent Cubic Feet per Minute of air the blower is currently delivering BLOWER RPM Blower motor RPM value STATIC PRESS Inches of w...

Page 11: ...e equipment is not cycled more than the selected times per hour This timer is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan and Temp buttons Ten Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning...

Page 12: ...l fuel Code 41 Blower Motor Fault USER INTERFACE No communication with indoor unit SYSTEM MALFUNCTION SCREEN The following errors will cause a System Malfunction Screen to pop up FAN COIL Code 37 Heater output sensed ON when not energized FURNACE Code 13 Limit Circuit Lockout Code 14 Ignition Lockout Code 21 Gas Heating Lockout Code 22 Abnormal Flame Proving Signal dual fuel only Code 23 Pressure ...

Reviews: