background image

6. Secure mounting plastic to wall using two screws and

anchors provided.

7. Adjust length and routing of each wire to reach each wire

entry on the connector backplate. Strip ¼ inch of insulation
from each wire.

8. Match and connect thermostat wires to proper terminals on

User Interface backplate. See wiring diagram figures 12, 13
and 14.

A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)

NOTE:

It is not mandatory that the above color code be used, but

each ABCD connection in the system MUST be wired consis-
tently. A separate ABCD Connector comes inside packaging and
should be used when connecting to the furnace (or fan coil). (See
Fig. 10)

NOTE:

Insert connector properly into circuit board.

CAUTION:

ELECTRICAL OPERATION HAZARD
Failure to follow this caution will result in equipment
damage or improper operation.
Improper wiring of the ABCD connector will cause the
Evolution Control™ to operate improperly. Check to
make sure all wiring is correct before proceeding with
installation or turning on power.

9. Push any excess wire into the wall. Seal hole in wall to

prevent any air leaks. Leaks can affect operation.

10. Attach Evolution Control™ to the mounting plastic by

lining up the plastic guides on the back of the control with
the opening on the mounting plastic and push on.

11. Perform installation of all other system equipment (i.e.

humidifier, ventilator, UV lights, etc.)

12. Turn on power to equipment.

EQUIPMENT WIRING DIAGRAMS:

See wiring diagram Figs. 12, 13 and 14.

NOTE:

For other applications not listed, refer to the Network

Interface Module (NIM) Installation Instructions.

See wiring diagram figure 12 for a Typical Four-Wire Connection
Diagram, which includes an Evolution indoor communicating
furnace or FE fan coil with a 2-speed Puron® communicating
outdoor unit. No additional OAT (outdoor air temperature) sensor
is required because the Evolution Control will use the temperature
sensor inside the 2-speed unit.

See wiring diagram figure 13 for a Typical Connection Diagram,
which includes a variable-speed indoor communicating furnace or
FE fan coil, with a 1-speed air conditioning unit (non-
communicating outdoor). An Outdoor Air Temperature sensor
may be installed (not required) at the indoor furnace or fan coil
OAT terminals. When OAT is applied, the Evolution System will
provide full system features and benefits.

See wiring diagram Fig. 14 for a Typical Connection Diagram for
FE fan coil with a 1-speed heat pump (using non-communicating
outdoor unit). When OAT is applied, the Evolution System will
provide full system features and benenfits.

HUMIDIFIER CONNECTION — A 24vac bypass or fan
powered humidifier may be installed.

NOTE:

Do Not Use a traditional humidistat to control humidifier

operation. If a humidifier is installed, let the Evolution System
control humidifier operation.

Bypass Humidifiers — A bypass humidifier should be wired
directly to the furnace or fan coil HUM and 24vac COM terminals.
The Evolution Control will automatically energize the HUM
output during a call for humidification.

Fan Powered Humidifiers — Most fan powered humidifiers
produce internal 24vac in order to energize upon a switch or
contact closure. For this application, a 24vac N.O. Isolation Relay
(DPST) MUST be used to prevent mixing the internal humidifier
power with the indoor equipment transformer. Applying 24vac
isolation relay coil to furnace or fan coil HUM and COM terminals
will allow the Evolution Control to automatically energize the
HUM output during a call for humidification. The N.O. relay
contacts will be used to energize the humidifier. See fan powered
humidifier installation instructions for more details.

Fig. 10—4–Wire ABCD Connector

A03193

A

B

C

D

Fig. 11—Functional Overview

A03194

HOLD

COOL

HEAT

SCHEDULE

VACATION

PROGRAM

SCROLL

BASIC

ADVANCED

SETUPS

Schedule

to program

temperature

schedule

Vacation

to start/end

vacation

Basic

to set time,

humidity

Advanced

for all other

settings

Scroll

up & down

Fan Button

Display Screen
(LCD)

Right-Side
Button

Heat Button

Cool Button

Temperature
(+/-) Button

System
On/Off Button

Basic & Advanced
Setup Buttons

Flip Down
Door

Left-Side
Button

Humidity/OAT
Button

Hold
Button

Time (+/-)
Button

Schedule & Vacation
Program Buttons

Up/Down
Scroll Buttons

A

B

C

D

A

B

C

D

User Interface

Green

Yellow

White

Red

OAT

Optional Remote

Room Sensor

HUM

COM
24V

Humidifier

Connection

S2

S1

A

B

C

D

ABCD

Connections

2-Spd. AC or HP

Green

Yellow

White

Red

OAT

Sensor

(Optional)

Variable-Speed

Furnace/ Fan Coil

Fig. 12—Universal Four-Wire Connection Diagram

A03146

—4—

Summary of Contents for Evolution Control SYSTXBBUID01

Page 1: ...rmo stat plus much more and a variable speed furnace or FE fan coil They support controlled ventilation humidification dehumidifica tion and air quality control Either a two speed communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the variable speed furnace or fan coil provides the 24 volt signals needed to control them Also the Evolution N...

Page 2: ...WG or larger NOTE ABCD bus wiring only requires a four wire connection however it is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during the installation Each device in the Evolution System has a four pin connector labeled ABCD It is recommended that the following color code be used when wiring each device A Green Data A B Yellow Data B...

Page 3: ...volution Control mounting plastic recess mount or surface mount and decorative backplate if desired 4 Route wires through large hole in mounting plastic Level rear plastic against wall for aesthetic value only Evolution Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 inch mounting holes in wall where marked Fig 4 Surface Mount Backplate A0318...

Page 4: ...perature sensor may be installed not required at the indoor furnace or fan coil OAT terminals When OAT is applied the Evolution System will provide full system features and benefits See wiring diagram Fig 14 for a Typical Connection Diagram for FE fan coil with a 1 speed heat pump using non communicating outdoor unit When OAT is applied the Evolution System will provide full system features and be...

Page 5: ...None no unit installed Press the right side button to continue to the next screen If you have selected either AC or HP as the outdoor unit type the following middle screen will appear See figure 16 Press either Time or Temp buttons to select appropriate Btu size of outdoor unit then press right side button to continue If a NIM Network Interface Module is applied for non communicating two speed out...

Page 6: ...lso after selecting YES if the filter type is not an EAC the indoor unit will operate the blower for one minute to do a system static pressure check QUICK START For first time installers Quick Start will allow you to start up the Evolution System before you have the chance to learn all the details of system operation However for the best possible comfort and operation we recommend that you refer t...

Page 7: ...RVICE MENUS The INSTALL SERVICE menus contain a set of vital information This information enables the Installer or Service person to view a summary of what has been installed etc To enter INSTALL SERVICE menus press and hold the ADVANCED button for at least ten seconds The following menu will appear See figure 20 NOTE The INSTALL SERVICE menu will automatically exit after 60 minutes of no push but...

Page 8: ...ncreased comfort AC AIRFLOW COMFORT default EFFICIENCY MAXIMUM Selects the airflow of the furnace when cooling COMFORT is a decreased airflow used to improve humidity control EFFI CIENCY is the airflow used to meet specified ratings MAXI MUM is a fixed airflow speed of 400 CFM ton based on the outdoor unit size DEHUM AIRFLOW NORMAL default HIGH NORMAL airflow adjustment is used during dehumidifyin...

Page 9: ...turn on SETUP UV LIGHTS UV LIGHTS INSTALLED NO YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed SETUP SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adjust the timer interval in which the normal System Maintenanc...

Page 10: ...lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service FAN COIL ELECTRIC HEAT STATUS OFF LOW MED HIGH Displays stages of electric heat that the fan coil is currently delivering AIRFLOW CFM fan coil model dependent Cubic Feet per Minute of air the blower is currently delivering BLOWER RPM Blower motor RPM value STATIC PRESS Inches of w...

Page 11: ...e equipment is not cycled more than the selected times per hour This timer is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan and Temp buttons Ten Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning...

Page 12: ...l fuel Code 41 Blower Motor Fault USER INTERFACE No communication with indoor unit SYSTEM MALFUNCTION SCREEN The following errors will cause a System Malfunction Screen to pop up FAN COIL Code 37 Heater output sensed ON when not energized FURNACE Code 13 Limit Circuit Lockout Code 14 Ignition Lockout Code 21 Gas Heating Lockout Code 22 Abnormal Flame Proving Signal dual fuel only Code 23 Pressure ...

Reviews: